SiBE05-513A
Control Specification
Function and Control
35
3.3.4
3-minute Standby
Prohibit to turn ON the compressor for 3 minutes after turning it off.
(Except when defrosting. (Only for Heat Pump Model).)
3.3.5
Compressor Protection Function
When turning the compressor from OFF to ON, the upper limit of frequency must be set as
follows. (The function must not be used when defrosting (only for heat pump model).)
3.4
Discharge Pipe Control
Outline
The discharge pipe temperature is used as the compressor's internal temperature. If the
discharge pipe temperature rises above a certain level, the operating frequency upper limit is
set to keep this temperature from going up further.
Detail
Divide the Zone
Management within the Zones
FCG 3
FCG 2
FCG 1
TCG 1
TCG 2
TCG 3
88
64
48
240
360
180
Zone
Control contents
Stop zone
When the temperature reaches the stop zone, stop the compressor and
correct abnormality.
Drooping zone
Start the timer, and the frequency will be drooping.
Keep zone
Keep the upper limit of frequency.
Return / Reset zone
Cancel the upper limit of frequency.
Summary of Contents for Inverter FLKS25BVMB
Page 10: ...SiBE05 513A List of Functions 1 Part 1 List of Functions 1 List of Functions 2 ...
Page 13: ...List of Functions SiBE05 513A 4 List of Functions ...
Page 19: ...Specifications SiBE05 513A 10 Specifications ...
Page 55: ...Control Specification SiBE05 513A 46 Function and Control ...
Page 83: ...Instruction SiBE05 513A 74 System Configuration ...
Page 129: ...Check SiBE05 513A 120 Service Diagnosis ...
Page 167: ...Outdoor Unit SiBE05 513A 158 Removal Procedure ...
Page 171: ...Others SiBE05 513A 162 Others ...
Page 177: ...Wiring Diagrams SiBE05 513A 168 Appendix ...
Page 181: ...SiBE05 513A iv Index ...