SiBE05-513A
Control Specification
Function and Control
37
3.6
Freeze-up Protection Control
Outline
During cooling operation, the signals being sent from the indoor unit allow the operating
frequency limitation and then prevent freezing of the indoor heat exchanger. (The signal from
the indoor unit must be divided into the zones as the followings.
Detail
Conditions for Start Controlling
Judge the controlling start with the indoor heat exchanger temperature after 2 sec from
operation start.
Control in Each Zone
3.7
Heating Peak-cut Control
Outline
Heat Pump Only
During heating operation, the signals being sent from the indoor unit allow the operating
frequency limitation and prevent abnormal high pressure. (The signal from the indoor unit must
be divided as follows.)
Detail
Conditions for Start Controlling
Judge the controlling start with the indoor heat exchanger temperature after 2 sec. from
operation start.
Control in Each Zone
The heat exchange intermediate temperature of indoor unit controls the following.
(R4561)
Return from stop
Reset zone
Heat exchanger
thermistor temperature
Up zone
Keep zone
Drooping zone
Stop zone
0˚C
3˚C
5˚C
7˚C
13˚C
Summary of Contents for Inverter FLKS25BVMB
Page 10: ...SiBE05 513A List of Functions 1 Part 1 List of Functions 1 List of Functions 2 ...
Page 13: ...List of Functions SiBE05 513A 4 List of Functions ...
Page 19: ...Specifications SiBE05 513A 10 Specifications ...
Page 55: ...Control Specification SiBE05 513A 46 Function and Control ...
Page 83: ...Instruction SiBE05 513A 74 System Configuration ...
Page 129: ...Check SiBE05 513A 120 Service Diagnosis ...
Page 167: ...Outdoor Unit SiBE05 513A 158 Removal Procedure ...
Page 171: ...Others SiBE05 513A 162 Others ...
Page 177: ...Wiring Diagrams SiBE05 513A 168 Appendix ...
Page 181: ...SiBE05 513A iv Index ...