Refrigerant piping work
2-2. Selection of Copper and Heat Insulation materials
• When using commercial copper pipes and fittings, observe the following:
1) Insulation material: Polyethylene foam
Heat transfer rate: 0.041 to 0.052kW/mK (0.035 to 0.045 kcal/mh
°
C)
Refrigerant gas pipe’s surface temperature reaches 110
°
C max.
Choose heat insulation materials that will withstand this temperature.
2) Be sure to insulate both the gas and liquid piping and to provide insulation dimen-
sions as below.
3) Use separate thermal insulation pipes for gas and liquid refrigerant pipes.
Gas side
Liquid side
25/35 class
50/60 class
25/35/50/60 class
O.D. 9.5mm
O.D. 12.7mm
O.D. 6.4mm
Thickness 0.8mm
Thickness 0.8mm
Gas pipe thermal insulation
Liquid pipe thermal insulation
25/35 class
50/60 class
25/35/50/60 class
I.D. 12-15mm
I.D. 14-16mm
I.D. 8-10mm
Thickness 10mm Min.
Gas pipe
Liquid pipe
Gas pipe
insulation
Liquid pipe
insulation
Finishing tape
Drain hose
Inter-unit wiring