background image

IM 1193 / Page 24 of 32

Adverse Operating Conditions Maintenance

Units operating in dusty or corrosive locations; i.e. dusty 

construction site or sea coast, must be cleaned more often. 

A minimum of four (4) times a year will maintain proper 

operational conditions and protect unit components.

Wall Sleeve

Clean the wall sleeve while cleaning the unit. The caulking 

around the sleeve should be checked to make sure that any 

potential air and water openings around the sleeve are prop

-

erly sealed. The wall sleeve’s level should also be rechecked. 

Proper leveling for most installations are a 1/4

"

 bubble tilt 

to the outside and level from right to left. Contact your sales 

person for detailed maintenance or cleaning instructions.

Base Pan and Condenser Coil

 

CAUTION

  Do  not  use  commercial  grade  coil  cleaners.  Some  of  these 

cleaners may contain Ethylene Diamine Tetracetic Acid 

(EDTA), which can shorten the life of the condenser coil.

Before cleaning the basepan and condenser coil, discon

-

nect power to the unit. To disconnect power, either unplug 

the power cord at the wall outlet or subbase, or disconnect 

power at the fuse box or circuit breaker.

1. 

  Create a water-tight seal by tightly covering the entire 

control panel area and fan motor with plastic. Creating 

this seal prevents water from entering the control area or 

the fan motor and damaging the unit.

2. 

  Spray condenser coil and base pan down with water. 

Next spray a mild biodegradable detergent such as 

Simple Green™ onto the condenser coil and base pan. 

Let set for five (5) minutes.

3. 

  Rinse condenser coil and base pan with water again.

Note:

  Ensure water pressure is no higher than that of an 

ordinary garden hose and the water temperature no 

higher than 120°F.

4. 

  Tilt the non-compressor side of the unit up no higher 

than 45 degrees and allow water to drain out the other 

side of the unit.

5. 

  Remove excess water left in the base pan by wiping the 

base pan with a dry cloth.

6.    Remove the water-tight seal from the motor and control 

panel area.

7. 

  Reinstall unit back into wall sleeve.

8. 

  Allow unit to dry for 24 hours before reapplying power. 

When power is reapplied test unit for proper operation.

9.    Place a non-acidic algaecide in the base pan to inhibit 

bacteria growth. Ensure the algaecide is compatible with 

wet coil operation and is not corrosive to the coil.

 

CAUTION

  High pressure and high temperature cleaning is not recom-

mended. Doing so could damage the aluminum fin stock and 

electrical components.

Monthly Maintenance and Cleaning

Intake Air Filters

To properly maintain the operational performance of your 

PTAC unit, it is extremely important that the inlet air filters 

be cleaned once per month or more often if operated in dusty 

or dirty locations or conditions. The intake air filters are 

constructed of durable polypropylene. The “air intake” air 

filters can be easily inserted into the cabinet front using the 

cabinet filter guides. Before cleaning the intake filter, turn 

the unit off by setting the mode switch to the OFF position. 

Filter should be cleaned as required.

Vent Screen

Before cleaning the vent screen, disconnect power to the unit 

by unplugging the power cord at the wall outlet or subbase, 

or disconnect power at the fuse box or circuit breaker. If unit 

is operated with vent door closed, the vent screen does not 

need to be cleaned.
1.  Remove the cabinet front as described in Front Removal.
2.  Remove the four screws securing the chassis to the wall 

sleeve.

3.  Slide the chassis out of the wall sleeve far enough so that 

the vent screen is accessible.

4.  Clean the vent screen, slide the chassis back into the wall 

sleeve, secure it in place with four screws and reinstall 

the front cabinet.

Cabinet Front

The cabinet front and discharge air grille can be cleaned with 

a water dampened cloth. Under no circumstances should 

hydrocarbon- based cleaners (e.g. acetone, benzene, naphtha 

gasoline, etc.) or ammonia based cleaners be used to clean 

the front or air grilles. Use care when cleaning the control 

area.

Yearly Maintenance and Cleaning

Note:

  Use a mild biodegradable detergent such as Simple 

Green™ when cleaning the unit. Special care must 

be taken to protect the unit’s control board and other 

electrical components from getting any water on them 

while cleaning. The use of harsh or caustic cleaning 

agents or materials such as bleach or coil cleaners 

that are not designed for PTAC products will cause 

damage or deterioration of the aluminum fin or coil 

material and is not recommended. Care must be 

taken not to bend the aluminum fin stock.

Routine Scheduled Maintenance

To achieve continuing top performance and high efficiency,
establish a “once a year” cleaning/inspection schedule for 

the unit. Take the unit out of the sleeve and thoroughly 

clean and rinse. Be sure to include in the yearly cleaning the 

evaporator coils, and condenser coils, base pan, and drain 

passages. Scheduled maintenance can be accomplished by 

either qualified local maintenance staff or by an authorized 

servicer. They must follow the instructions described in this 

manual.

Summary of Contents for IM 1193

Page 1: ...is type of equipment Caution Sharp edges and coil surfaces are potential injury hazards This manual must be left with the owner of the equipment Installation Maintenance Data IM 1193 Group PTAC Part Number 910140864 Date October 2013 Packaged Terminal Air Conditioner 16 x 42 PGAN with Top Mounted Hydronic Heat 2013 Daikin Applied www DaikinAP com 800 432 1342 ...

Page 2: ...ctronic Thermostat P N 910140678 17 Operating Instructions 18 Cooling or Heating Manual Operation 18 Remote Thermostats 18 Thermostat Location 18 Remote Thermostat Operation 19 Non Programmable Thermostat Specs 19 Wall Mounted 7 5 2 5 1 1 Programmable Thermostat Specs 19 Standard Auto or Manual Changeover Two Stage Heat Two Stage Cool Specs 20 Configuration Settings for Internal Control Touchpad 2...

Page 3: ...has been unpacked The contents may be damaged in transit due to rough han dling even though the carton may not show external damages When the damage is discovered upon unpacking make a writ ten request for inspection by the carrier s agent within fifteen 15 days of the delivery date File a claim with the carrier since such damage is the carrier s responsibility Safety Information Follow all safety...

Page 4: ...012 12 000 015 15 000 Voltage A 115 60 1 future E 208 230 60 1 J 265 277 60 1 Brand Name D Daikin Refrigerant A R 410A SKU B Build to Order P GAN 1 009 E D A AY YYYYY LB SYY B L Application Type YYYYY None Power Connection LB Long Cord 64 Standard YY None Hardwired to unit Upgrade Packages SYY Seacoast AYY Acoustics BYY Seacoast and Acoustics YYY None Warranty A Standard C 4 Yr Extnd Comp L 4 Yr E...

Page 5: ...om Cabinet D Wall Sleeve B Wall Thickness 18 13 4 5 17 13 5 6 16 13 6 7 15 13 7 8 14 13 8 9 13 13 9 10 12 13 10 11 11 13 11 12 10 13 12 13 10 14 13 14 10 15 14 15 10 16 15 16 10 17 16 17 Standard Size Wall Sleeve Figure 1 PGAN 16 x 42 with top mounted hydronic heat Removable Front Panel Digital Touchpad Control 16 x 42 Wall Sleeve Louver Architectural Top Mount Hydronic Heat Section Cooling Chassi...

Page 6: ...is sufficient clearance from the walls and floor The wall sleeve should be positioned a minimum of 1 5 8 in from the room side finished wall to accommodate the room cabinet and the hydronic heat section mounting A minimum distance of 3 above the finished floor is required for return air although when using a louver frame in panel wall or thin wall construction the opening must start 4 above the fi...

Page 7: ...ction from the flanges 3 Manipulate the grille out through the rear sleeve opening using the plastic handle provided 4 Align the guide pins located in the lower right and left hand corners of the grille with the corresponding holes in the rear of the wall sleeve 5 Secure the grille by threading each of the six screws into the plastic grommets 6 Remove the plastic handle from the center of the gril...

Page 8: ...3 3 4 Optional Continuous Flange Note Given dimensions are standard Installation of wall sleeves with continuous louvers is very similar to that of applications with factory furnished louvers Assuming the louver meets Daikin s criteria as stated previ ously proceed to install the wall sleeve as follows 1 Clean the opening of all debris that may interfere with installation 2 Position the wall sleev...

Page 9: ...on using top angles and field supplied louver 133 4 349mm 11 4 38mm Insulated Panel Optional Top Flange 16 406mm Outside Edge of Sleeve Wall Sleeve Turndown Flange See Detail Finished Floor Including Carpet Outside Louver By Others Resilient Caulking see Note 2 Turndown Flange Resilient Caulking see Note 2 Wall Sleeve Wall Frame By Others Optional Top Flange 42 1069mm Optional Subbase 16 406mm 101...

Page 10: ...the finished interior wall surface This allows room to attach the heat section and room cabinet The wall sleeve should also be recessed enough to accommodate the outside louver Level wall sleeve side to side and pitch to outside 1 8 ft to assure proper sleeve drainage to outside 5 After the mortar has dried remove the masonry support from the wall sleeve Note The wall sleeve is not intended to rep...

Page 11: ...Kit Cripple Stud Main Stud Rubber Isolation Washer Note All anchoring hardware field supplied 4 Attach the provided hydronic coil blockoff plate to the under side of the hydronic heat section with the two 2 screws as shown in Figure 14 5 Firmly attach the heat section to the wall sleeve by lining up the heat section hooks with the square holes supplied in the wall sleeve Snap the heat section in p...

Page 12: ...tion Piping Recommended Piping Detail Field Installed Figure 16 Typical hot water coil piping Coil Air Vent Balancing Valve Gate Valve Plug to Control Box Automatic Valve Gate Valve Supply Return Side View Figure 17 Typical steam coil piping Coil Supply Return Gate Valve Automatic Valve Plug to Control Box Gate Valve Steam Trap Side View ...

Page 13: ...tion that matches the coil supplied and pipe it according to the illustration Install valve and other accessories including air vents steam traps stop balance valves etc as specified by the design engineer 2 For valve installed on right side of the unit make electrical connection to matching cap extending from the control box For left side valve make electrical connection to cap mounted to left si...

Page 14: ...ply Return Figure 22 Right hand supply left hand return Supply Return Figure 23 Left hand supply right hand return Supply Return Hot Water Figure 24 Left hand supply and return Supply Return Figure 25 Right hand supply and return Return Supply Figure 26 Left hand supply right hand return or Right hand supply left hand return Return or Supply Return or Supply ...

Page 15: ...e Vent Control Lever 7 Do not lubricate motors before start up Motors are permanently lubricated 8 Place Tinnerman clips from bag onto wall sleeve Clips and mounting screws are enclosed in a bag attached to the top of the condenser coil housing 9 If louver has not been previously installed connect to wall sleeve as described above 10 If louver is supplied by others as illustrated in Figure 10 on p...

Page 16: ... firmly push the cabinet downward until it seats on the wall sleeve see Figure 30 Figure 30 Room cabinet detail Screw slots on back of cabinet for securing to wall 2 each side Notch on back of cabinet to set on wall sleeve 3 Screw the cabinet to the wall using the screws provided There are two 2 screw holes provided on each side located on the inner flanges of the room cabinet 4 Loosen the four 4 ...

Page 17: ...operation and application refer to Operation Application Guide LIAF187 Unit Mounted Controller Remote Thermostats Programmable Electronic Thermostat P N 910140679 7 Day Programmable Auto Changeover Fan Speed Control Hardwired 7 Day Programmable Single Stage Heat Pump Non Heat Pump Systems Backlit Display Single Stage Heat Cool Systems Field Calibration Auto Changeover Button Lockout Function Two S...

Page 18: ...thers There are two basic types of thermostats manufactured today those with relay contacts and those with solid state triacs If you open the thermostat and don t see relays then you can assume it to be solid state Manufacturers of solid state output thermostats include loading resistors on their installation kits These are of low Ohm value approximately 560 Ohm and 3W The resistors are meant to l...

Page 19: ... F Accuracy 1 F System Configurations 1 stage heat 1 stage cool or single stage electric heat pump Terminations RC RH C W Y O B G Figure 33 Internal Control Board Remote Control Terminations DS1 DS2 MS1 MS2 EH IN LS FD1 FD2 TF TF C R GL W2 Y W1 B GH REMOTE THERMOSTAT AUXILIARY Y W GH R Thermostat Connections Control Board Connections C GL Remote Thermostat Operation Approved thermostats vary sligh...

Page 20: ...option code to change from the factory default setting The Internal Control Board must be set up for Remote Thermostat Operation configuration mode C 1 and Option code L 5 as the Daikin Touchpad controller is connected to the Remote Thermostat terminals on the Internal Control Board To enter configuration feature mode 1 Press and hold the up and down arrow keys at the same time and press the OFF k...

Page 21: ... Wireless Occupancy 0 Off 1 On 18 18 Hour Automatic Entry C8 Temp Limiting Cool 60 72 60 72 C9 Temp Limiting Heat 68 90 80 68 90 80 Cd English Metric Temp F Fahrenheit Scale C Celsius Scale d6 Sensorless Un Occ Time 1 32 18 1 32 18 d7 1st Un Occ Set Back Temp 1 16 2 1 16 2 d8 1st Un Occ Set Back Time 1 5 1 24 1 5 1 24 5 d9 2nd Un Occ Set Back Temp 1 16 3 1 16 3 dA 2nd Un Occ Set Back Time 1 5 1 24...

Page 22: ...re Id the outdoor coil temperature OC the outdoor ambient temperature OA and the spare probe temperature IH If any of the probes are not populated the display will show the corresponding failure code Past Failure Log If not in Diagnostic Status Report Mode enter as instructed above and press the Fan Speed key twice If already in Diagnostic Status Report mode press the Fan Speed key While the displ...

Page 23: ...mostat reads outside the range 20 F to 200 F F2 Wireless Remote Thermostat failure N N Replace Wireless Thermostat F3 Indoor Ambient Thermistor reads outside the range 20 F to 200 F Y N Replace black Indoor Ambient Thermistor F4 Indoor Coil Thermistor either above or below operating toler ances N Y Replace Red Indoor Coil Thermistor F5 Wireless Thermostat failure N Y Attempt to rebind Wireless The...

Page 24: ...he aluminum fin stock and electrical components Monthly Maintenance and Cleaning Intake Air Filters To properly maintain the operational performance of your PTAC unit it is extremely important that the inlet air filters be cleaned once per month or more often if operated in dusty or dirty locations or conditions The intake air filters are constructed of durable polypropylene The air intake air fil...

Page 25: ... Rotate Freely Without Striking Fan Housing Condenser Air Free of Obstruction Cycle Continuous Fan if so equipped Other Conditions Found ___________________________________________________________ _______________________________________________________________________________ _______________________________________________________________________________ Note No answers above require notice to ins...

Page 26: ...r blower motor not up to speed 7 Evaporator motor slipping on motor shaft d Heat load in room exceeds capacity of equipment e Windows and doors in room are open f Compressor not pumping indicated by 1 Low wattage 2 Condenser not warm evaporator only partially cool or not at all g Restricted capillary or strainer 1 Frost on capillary or strainer 2 Low wattage 3 Condenser not warm 4 Evaporator parti...

Page 27: ... thermostat e Thermostat set too high f Thermostat faulty g No power output on transformer secondary h Inoperative valve 1 Steam valve N C 2 Hot water valve N C a Adjust b Replace a Remove obstructions to water flow b Adjust or replace c Check for correct voltage Replace motor if necessary d Tighten a See No 1 b Open heat valve or turn on heating system c Replace d Tighten e Adjust room temperatur...

Page 28: ...AN REVERSING VALVE TRANSFORMER VARIABLE SPEED MOTOR VARIABLE SPEED TERMINAL BOARD LINE 1 HEATER 1 HEATER 2 LINE 2 COMPRESSOR FAN HIGH FAN LOW REV VALVE RD RD R RD BL BK BK COM GND 230 265 TO MOTOR VSTM OD 485 RS 7 7 BK RD RD BK BK Model or Mfg Starts With High Speed VSTM Black Low Speed VSTM Red MTC15 1650 1350 Outdoor Motor Speed Selection Wiring is subject to change HIGH VOLTAGE DISCONNECT ALL P...

Page 29: ...MPRESSOR AND FAN REVERSING VALVE TRANSFORMER VARIABLE SPEED MOTOR VARIABLE SPEED TERMINAL BOARD Model or Mfg Starts With High Speed VSTM Black Low Speed VSTM Red MTC15 1650 1350 Outdoor Motor Speed Selection LINE 1 HEATER 1 HEATER 2 LINE 2 COMPRESSOR FAN HIGH FAN LOW REV VALVE OR BR RD PK PK VT GY PK RD 6 R COM GND 230 265 TO MOTOR VSTM OD R 485 S OR Wiring is subject to change HIGH VOLTAGE DISCON...

Page 30: ... 2 COMPRESSOR FAN HIGH FAN LOW REV VALVE COM GND 230 265 TO MOTOR VSTM ID R 485 S VSM EM EVAP MOTOR VT BK RD RD COM GND 230 265 TO MOTOR VSTM OD R 485 S VSM CM FAN MOTOR WH WH BK 1650 1500 1350 1170 BK WH BK BK RD OR Model or Mfg Starts With High Speed VSTM Black Low Speed VSTM Red MTC07 1400 1250 MTC09 1400 1250 MTC12 1400 1250 Model or Mfg Starts With High Speed VSTM Black Low Speed VSTM Red MTC...

Page 31: ...EVAP MOTOR LINE 1 HEATER 1 HEATER 2 LINE 2 COMPRESSOR COM GND 230 265 TO MOTOR VSTM ID R 485 S FAN HIGH FAN LOW REV VALVE OR BR RD PK PK VT GY PK RD 6 COM GND 230 265 TO MOTOR VSTM OD R 485 S VSM CM FAN MOTOR WH WH OR Model or Mfg Starts With High Speed VSTM Black Low Speed VSTM Red MTC07 1400 1250 MTC09 1400 1250 MTC12 1400 1250 Model or Mfg Starts With High Speed VSTM Black Low Speed VSTM Red MT...

Page 32: ...d pursuant to its standard terms and conditions of sale including Limited Product Warranty Consult your local Daikin Representative for warranty details Refer to Form 933 430285Y To find your local Daikin Representative go to www DaikinAP com Aftermarket Services To find your local parts office visit www DaikinAP com or call 800 37PARTS 800 377 2787 To find your local service office visit www Daik...

Reviews: