IM 1193 / Page 19 of 32
Simple to operate, single push button for one-stage heating
and cooling, or single stage heat pump. Zone compatible and
4- or 5 wire compatible (terminal “C” is optional for non-
heat pump systems). System “heat-off-cool” switch and fan
“on-off” switch.
Specifications
Electrical Rating:
• 24 VAC (18 to 30 VAC)
• 1 amp maximum per terminal
• 3 amp maximum total load
• 30-minute power loss memory retention
Temperature Control Ranges:
• 45°F to 90°F, Accuracy: ± 1°F
System Configurations:
• 1 stage heat, 1 stage cool or single stage electric heat pump
Terminations:
• R, C, W, Y, O, B, G
Wall-Mounted, 7, 5-2 & 5-1-1
Programmable Thermostat Specs
Manual Changeover One-Stage Heat and Cool or
One-Stage Heat Pump
Part No. 910116772 (1-Pk, White with Wall Plate)
Specifications
Electrical Rating:
• 24 VAC (18 to 30 VAC)
• 1 amp maximum per terminal
• 3 amp maximum total load
• 30-minute power loss memory retention
• Easy access terminal block
Temperature Control Ranges:
• 45°F to 90°F, Accuracy: ± 1°F
System Configurations:
• 1 stage heat, 1 stage cool or single stage electric heat pump
Terminations:
• RC, RH, C, W, Y, O, B, G
Figure 33: Internal Control Board - Remote Control
Terminations
DS1 DS2 MS1 MS2 EH IN LS FD1 FD2 TF- TF+ C
R GL W2 Y/W1 B GH
REMOTE THERMOSTAT
AUXILIARY
Y
W
GH
R
Thermostat Connections
Control Board Connections
C
GL
Remote Thermostat Operation
Approved thermostats vary slightly in construction and, with
few exceptions, are operated similarly. The following opera
-
tional description pertains to approved non-programmable
thermostats that energize G in Heat and Cool mode.
Heat/Off/Cool Switch
•
OFF
- cooling and heating functions are defeated.
•
HEAT
- the selected room temperature is maintained by
cycling the hydronic control valve.
•
COOL
- the selected room temperature is maintained by
cycling the air conditioner.
Table 14: Maximum Wire Length for Remote Control
Connection
Maximum Wire Length
Wire Size (AWG)
Maximum Length Allowed
#24
400 ft.
#22
600 ft.
#20
900 ft.
#18
1500 ft.
#16
2000 ft.
Non-Programmable Thermostat Specs
Manual Changeover One-Stage Heat and Cool or
One-Stage Heat Pump
Part No. 910116771 (1-Pk, White with Wall Plate)