EDUS04-924A
Installation Manual
Room Air Conditioners H-Series
39
Outdoor Unit Installation (2)
4.
Refrigerant piping.
3.
Flaring the pipe end.
1) Cut the pipe end with a pipe cutter.
2) Remove burrs with the cut surface facing
downward so that the chips do not enter
the pipe.
3) Put the flare nut on the pipe.
4) Flare the pipe.
5) Check that the flaring is properly made.
1) Do not use mineral oil on flared part.
2) Prevent mineral oil from getting into the system as this would reduce the lifetime of the units.
3) Never use piping which has been used for previous installations. Only use parts which are delivered with
the unit.
4) Do never install a drier to this R410A unit in order to guarantee its lifetime.
5) The drying material may dissolve and damage the system.
6) Incomplete flaring may cause refrigerant gas leakage.
WARNING
Liquid side
3/8 inch(9.5mm)
24.1-29.4ft
•
lbf
(32.7-39.9N
•
m)
Gas side
5/8 inch(15.9mm)
45.6-55.6ft
•
lbf
(61.8-75.4N
•
m)
Flare nut tightening torque
Liquid side
3/8 inch(9.5mm)
15.9-20.2ft
•
lbf
(21.6-27.4N
•
m)
Gas side
5/8 inch(15.9mm)
35.5-44.0ft
•
lbf
(48.1-59.7N
•
m)
Valve cap tightening torque
Service port cap tightening torque
7.9-10.8ft
•
lbf (10.8-14.7N
•
m)
CAUTION
1) Use the flare nut fixed to the main unit. (To prevent cracking of the flare nut by aged deterioration.)
2) To prevent gas leakage, apply refrigeration oil only to the inner surface of the flare. (Use refrigeration oil
for R410A.)
3) Use torque wrenches when tightening the flare nuts to prevent damage to the flare nuts and gas
leakage.
Align the centers of both flares and tighten the flare nuts 3 or 4 turns by hand. Then tighten them fully
with the torque wrenches.
(Cut exactly at
right angles.)
Remove burrs
Set exactly at the position shown below.
A
Flaring
Die
A
0-0.020 inch
(0-0.5mm)
Flare tool for R410A
0.039-0.059 inch
(1.0-1.5mm)
0.059-0.079 inch
(1.5-2.0mm)
Conventional flare tool
Check
Flare’s inner
surface must
be flaw-free.
The pipe end must
be evenly flared in a
perfect circle.
Make sure that the
flare nut is fitted.
Do not apply
refrigeration oil to the
outer surface.
Flare
Apply refrigeration
oil to the inner
surface of the flare.
Do not apply refrigeration
oil to the flare nut avoid
tightening with over torque.
[Apply oil]
Clutch-type
Clutch-type
(Rigid-type)
Wing-nut type
(Imperial-type)
Summary of Contents for H-Series
Page 1: ...EDUS04 924A H Series Cooling Only Heat Pump...
Page 50: ...EDUS04 924A Operation Manual Safety Considerations Room Air Conditioners H Series 49...
Page 51: ...Operation Manual Safety Considerations EDUS04 924A 50 Room Air Conditioners H Series...
Page 52: ...EDUS04 924A Operation Manual Safety Considerations Room Air Conditioners H Series 51...
Page 53: ...Operation Manual Safety Considerations EDUS04 924A 52 Room Air Conditioners H Series...
Page 54: ...EDUS04 924A Operation Manual Safety Considerations Room Air Conditioners H Series 53...
Page 55: ...Operation Manual Safety Considerations EDUS04 924A 54 Room Air Conditioners H Series...
Page 56: ...EDUS04 924A Operation Manual Safety Considerations Room Air Conditioners H Series 55...
Page 57: ...Operation Manual Safety Considerations EDUS04 924A 56 Room Air Conditioners H Series...
Page 58: ...EDUS04 924A Operation Manual Safety Considerations Room Air Conditioners H Series 57...
Page 59: ...Operation Manual Safety Considerations EDUS04 924A 58 Room Air Conditioners H Series...
Page 60: ...EDUS04 924A Operation Manual Safety Considerations Room Air Conditioners H Series 59...
Page 61: ...Operation Manual Safety Considerations EDUS04 924A 60 Room Air Conditioners H Series...
Page 63: ...Operation Manual Safety Considerations EDUS04 924A 62 Room Air Conditioners H Series...
Page 64: ...EDUS04 924A Operation Manual Safety Considerations Room Air Conditioners H Series 63...
Page 65: ...Operation Manual Safety Considerations EDUS04 924A 64 Room Air Conditioners H Series...
Page 66: ...EDUS04 924A Operation Manual Safety Considerations Room Air Conditioners H Series 65...
Page 67: ...Operation Manual Safety Considerations EDUS04 924A 66 Room Air Conditioners H Series...
Page 68: ...EDUS04 924A Operation Manual Safety Considerations Room Air Conditioners H Series 67...
Page 69: ...Operation Manual Safety Considerations EDUS04 924A 68 Room Air Conditioners H Series...
Page 70: ...EDUS04 924A Operation Manual Safety Considerations Room Air Conditioners H Series 69...
Page 71: ...Operation Manual Safety Considerations EDUS04 924A 70 Room Air Conditioners H Series...
Page 72: ...EDUS04 924A Operation Manual Safety Considerations Room Air Conditioners H Series 71...
Page 73: ...Operation Manual Safety Considerations EDUS04 924A 72 Room Air Conditioners H Series...
Page 74: ...EDUS04 924A Operation Manual Safety Considerations Room Air Conditioners H Series 73...
Page 75: ...Operation Manual Safety Considerations EDUS04 924A 74 Room Air Conditioners H Series...
Page 76: ...EDUS04 924A Operation Manual Safety Considerations Room Air Conditioners H Series 75...
Page 77: ...Operation Manual Safety Considerations EDUS04 924A 76 Room Air Conditioners H Series...
Page 78: ...EDUS04 924A Operation Manual Safety Considerations Room Air Conditioners H Series 77...
Page 79: ...Operation Manual Safety Considerations EDUS04 924A 78 Room Air Conditioners H Series...
Page 80: ...EDUS04 924A Operation Manual Safety Considerations Room Air Conditioners H Series 79...
Page 100: ...EDUS04 924A Optional Accessories Room Air Conditioners H Series 99...
Page 101: ...Optional Accessories EDUS04 924A 100 Room Air Conditioners H Series 3P248024 2...