Outdoor Unit Installation Drawings
Installation Guidelines
• Where a wall or other obstacle is in the path of outdoor unit’s intake or exhaust airflow, follow the
installation guidelines below.
• For any of the below installation patterns, the wall height on the exhaust side should be 47-1/4 inch
(1200mm) or less.
* Be sure to add the proper amount of additional refrigerant.
Failure to do so may result in reduced performance.
Max. allowable height
Max. allowable length
98.4ft (30m)
65.6ft (20m)
Model
30/36 class
Liquid pipe
Gas pipe
O.D. 3/8 inch (9.5mm)
O.D. 5/8 inch (15.9mm)
0.55oz/ft
(50g/m)
Additional refrigerant
required for refrigerant
pipe exceeding 32ft
(10m) in length.
Min. allowable length
6.6ft (2m)
More than 1-15/16”
(50mm)
More
than
3-15/16”
(100mm)
More than 13-3/4” (350mm)
47-1/4”
(1200mm)
or less
More than 1-15/16”
(50mm)
More than
13-3/4”
(350mm)
Wrap the insulation
pipe with the finishing
tape from bottom to top.
Allow 11-13/16 inch (300mm)
of work space below the
ceiling surface.
9-7/8” (250mm) from w
all
Allow space for piping
and electrical servicing.
Right side plate
13-5/8”
(345mm)
Clamping material
Insulation tube
Bottom frame
Tape
Also insulate the connection on the outdoor unit.
Use tape or insulating material on all connections
to prevent air from getting in between the copper
piping and the insulation tube.
Be sure to do this if the outdoor unit is installed
above.
(F
oot bolt-hole
centres)
(Foot bolt-hole centres)
24-7/16”
(620mm)
Level mounting base
(available separately)
If there is the danger of the unit falling
or overturning, fix the unit with
foundation bolts, or with wire or other
means.
If the location does not have good
drainage, place the unit on a level
mounting base (or a plastic pedestal).
Install the outdoor unit in a level
position. Failure to do so may result in
water leakage or accumulation.
More than 3-15/16”
(100mm)
Side view
Wall facing one side
Top view
Walls facing two sides
Top view
More than 3-15/16”
(100mm)
More than 13-3/4”
(350mm)
More than 1-15/16”
(50mm)
Walls facing three sides
CAUTION
Set the piping length
from 6.6ft (2m) to 98.4ft (30m).
Summary of Contents for H-Series
Page 1: ...EDUS04 924A H Series Cooling Only Heat Pump...
Page 50: ...EDUS04 924A Operation Manual Safety Considerations Room Air Conditioners H Series 49...
Page 51: ...Operation Manual Safety Considerations EDUS04 924A 50 Room Air Conditioners H Series...
Page 52: ...EDUS04 924A Operation Manual Safety Considerations Room Air Conditioners H Series 51...
Page 53: ...Operation Manual Safety Considerations EDUS04 924A 52 Room Air Conditioners H Series...
Page 54: ...EDUS04 924A Operation Manual Safety Considerations Room Air Conditioners H Series 53...
Page 55: ...Operation Manual Safety Considerations EDUS04 924A 54 Room Air Conditioners H Series...
Page 56: ...EDUS04 924A Operation Manual Safety Considerations Room Air Conditioners H Series 55...
Page 57: ...Operation Manual Safety Considerations EDUS04 924A 56 Room Air Conditioners H Series...
Page 58: ...EDUS04 924A Operation Manual Safety Considerations Room Air Conditioners H Series 57...
Page 59: ...Operation Manual Safety Considerations EDUS04 924A 58 Room Air Conditioners H Series...
Page 60: ...EDUS04 924A Operation Manual Safety Considerations Room Air Conditioners H Series 59...
Page 61: ...Operation Manual Safety Considerations EDUS04 924A 60 Room Air Conditioners H Series...
Page 63: ...Operation Manual Safety Considerations EDUS04 924A 62 Room Air Conditioners H Series...
Page 64: ...EDUS04 924A Operation Manual Safety Considerations Room Air Conditioners H Series 63...
Page 65: ...Operation Manual Safety Considerations EDUS04 924A 64 Room Air Conditioners H Series...
Page 66: ...EDUS04 924A Operation Manual Safety Considerations Room Air Conditioners H Series 65...
Page 67: ...Operation Manual Safety Considerations EDUS04 924A 66 Room Air Conditioners H Series...
Page 68: ...EDUS04 924A Operation Manual Safety Considerations Room Air Conditioners H Series 67...
Page 69: ...Operation Manual Safety Considerations EDUS04 924A 68 Room Air Conditioners H Series...
Page 70: ...EDUS04 924A Operation Manual Safety Considerations Room Air Conditioners H Series 69...
Page 71: ...Operation Manual Safety Considerations EDUS04 924A 70 Room Air Conditioners H Series...
Page 72: ...EDUS04 924A Operation Manual Safety Considerations Room Air Conditioners H Series 71...
Page 73: ...Operation Manual Safety Considerations EDUS04 924A 72 Room Air Conditioners H Series...
Page 74: ...EDUS04 924A Operation Manual Safety Considerations Room Air Conditioners H Series 73...
Page 75: ...Operation Manual Safety Considerations EDUS04 924A 74 Room Air Conditioners H Series...
Page 76: ...EDUS04 924A Operation Manual Safety Considerations Room Air Conditioners H Series 75...
Page 77: ...Operation Manual Safety Considerations EDUS04 924A 76 Room Air Conditioners H Series...
Page 78: ...EDUS04 924A Operation Manual Safety Considerations Room Air Conditioners H Series 77...
Page 79: ...Operation Manual Safety Considerations EDUS04 924A 78 Room Air Conditioners H Series...
Page 80: ...EDUS04 924A Operation Manual Safety Considerations Room Air Conditioners H Series 79...
Page 100: ...EDUS04 924A Optional Accessories Room Air Conditioners H Series 99...
Page 101: ...Optional Accessories EDUS04 924A 100 Room Air Conditioners H Series 3P248024 2...