Installation and operation manual

5

FXZQ15~50A2VEB

VRV System air conditioners

4P341102-1B – 2013.06

Cautions for brazing

Be sure to carry out a nitrogen blow when brazing.
Brazing without carrying out nitrogen replacement or releasing
nitrogen into the piping will create large quantities of oxidized
film on the inside of the pipes, adversely affecting valves and
compressors in the refrigerating system and preventing normal
operation.

When brazing while inserting nitrogen into the piping, nitrogen
must be set to 0.02 MPa with a pressure-reducing valve (=just
enough so that it can be felt on the skin).

Drain piping work

Installation of drain piping

Install the drain piping as shown in the figure and take measures
against condensation. Improperly rigged piping could lead to leaks
and eventually wet furniture and belongings.

Install the drain pipes.
- Keep piping as short as possible and slope it downwards at a 

gradient of at least 1/100 so that air may not remain trapped 
inside the pipe.

- Keep pipe size equal to or greater than that of the connecting 

pipe (vinyl pipe of 20 mm nominal diameter and 26 mm outer 
diameter).

- Push the supplied drain hose as far as possible over the 

drain socket.

- Tighten the metal clamp as indicated in the illustration.

- After the testing of drain piping is finished, attach the drain 

sealing pad (4) supplied with the unit over the uncovered part 
of the drain socket (= between drain hose and unit body).

- Wrap the supplied large sealing pad over the metal clamp 

and drain hose to insulate and fix it with clamps.

- Insulate the complete drain piping inside the building (field 

supply).

- If the drain hose cannot be sufficiently set on a slope, fit the 

hose with drain raising piping (field supply).

How to perform piping 

(See figure 6)

- Connect the drain hose to the drain raising pipes, and 

insulate them.

- Connect the drain hose to the drain outlet on the indoor unit, 

and tighten it with the clamp.

Precautions
- Install the drain raising pipes at a height of less than H2.
- Install the drain raising pipes at a right angle to the indoor 

unit and no more than 300 mm from the unit.

- To prevent air bubbles, install the drain hose level or slightly 

tilted up (

75 mm).

- Drain pump mounted in this unit is high lift type. 

Characteristic of this pump is that the higher pump is the 
lower drainage sound becomes. Therefore drain pump height 
of 300mm is recommended. 

1

Refrigerant piping

2

Part to be brazed

3

Taping

4

Hands valve

5

Pressure-reducing valve

6

Nitrogen

1

Hanging bar

1

Drain socket (attached to the unit)

2

Drain hose (supplied with the unit)

1

2

3

4

5

6

6

2

1

1

Drain socket (attached to the unit)

2

Drain hose (supplied with the unit)

3

Metal clamp (supplied with the unit)
NOTE: Bend the tip of the metal clamp without tearing 
the sealing.

4

Large sealing pad (supplied with the unit)

5

Drain piping (field supply)

1

Ceiling slab

2

Hanger bracket

3

Adjustable range

4

Drain raising pipe (nominal diameter of vinyl pipe = 25 mm)

5

Drain hose (supplied with the unit)

6

Metal clamp (supplied with the unit)

Decoration panel

H2

BYFQ60C

645 mm

BYFQ60B

630 mm

NOTE

The incline of attached drain hose should be
75 mm or less so that the drain socket does
not have to withstand additional force.
To ensure a downward slope of 1:100, install
hanging bars every 1 to 1.5 m.
When unifying multiple drain pipes, install the
pipes as shown in 

figure 8

. Select converging

drain pipes whose gauge is suitable for the
operating capacity of the unit. 

1

T-joint converging drain pipes

1

5

2

3

4

3

4

2

A

A'

A-A'

1

Summary of Contents for FXZQ15A2VEB

Page 1: ...INSTALLATION AND OPERATION MANUAL FXZQ15A2VEB FXZQ20A2VEB FXZQ25A2VEB FXZQ32A2VEB FXZQ40A2VEB FXZQ50A2VEB System air conditioners ...

Page 2: ...75 a 700 700 a 575 8 7 3 2 1 4 1 1 2 3 2 1 2 2 3 2 4 5 1 5 6 575 a a 575 a 8 7 3 2 1 4 2 3 4 1 2 1 4 2 1 3 4 5 2 1 5 6 1 H2 1 PP 9 10 7 6 8 4 4 PP H2 PP PP PP 4 4 PP H1 H2 PP 2 1 5 4 3 11 2 2 1 8 8 2 4 7 1 9 10 5 5 2 7 4 3 L N 1 3 1 2 4 5 7 11 3 2 6 8 9 10 ...

Page 3: ...lineato nel A e giudicato positivamente da B secondo il Certificato C 07 Σημείωση όπως καθορίζεται στο A και κρίνεται θετικά από το B σύμφωνα με το Πιστοποιητικό C 08 Nota tal como estabelecido em A e com o parecer positivo de B de acordo com o Certificado C 09 Примечание как указано в A и в соответствии с положительным решением B согласно Свидетельству C 10 Bemærk som anført i A og positivt vurde...

Page 4: ...n kitchens Plastic parts may deteriorate Where corrosive gas like sulphurous gas exists Copper tubing and brazed spots may corrode Where volatile flammable gas like thinner or gasoline is used Where machines generating electromagnetic waves exist Control system may malfunction Where the air contains high levels of salt such as air near the ocean and where voltage fluctuates a lot e g in factories ...

Page 5: ...ht However it becomes necessary to make field settings using the remote controller when installing the unit at a height over 2 7 m To avoid accidental touching it is recommended to install the unit higher than 2 5 m Refer to Field setting on page 8 and to the decoration panel installation manual 3 Air flow directions Select the air flow directions best suited to the room and point of installation ...

Page 6: ...nger bracket Securing the hanger bracket See figure 5 2 Fix the paper pattern for installation For new ceilings only The paper pattern for installation corresponds with the measurements of the ceiling opening Consult the builder for details The centre of the ceiling opening is indicated on the paper pattern for installation The centre of the unit is indicated on the unit casing After removing the ...

Page 7: ...as being exposed to a fire Make sure there is no refrigerant gas leak A toxic gas may be released by the refrigerant gas leaking indoor and being exposed to flames from an area heater cooking stove etc Finally insulate as shown in the figure below use the supplied accessory parts Piping insulation procedure Installation shall be done by a licensed refrigeration technician the choice of materials a...

Page 8: ...ently set on a slope fit the hose with drain raising piping field supply How to perform piping See figure 6 Connect the drain hose to the drain raising pipes and insulate them Connect the drain hose to the drain outlet on the indoor unit and tighten it with the clamp Precautions Install the drain raising pipes at a height of less than H2 Install the drain raising pipes at a right angle to the indo...

Page 9: ...e remote controller refer to the Installation manual of the remote controller All wiring must be performed by an authorized electrician A main switch or other means for disconnection having a contact separation in all poles must be incorporated in the fixed wiring in accordance with relevant local and national legislation Note that the operation will restart automatically if the main power supply ...

Page 10: ...s in the casing wiring holes with putty or insulation material field supply thus to prevent small animals or dirt from entering the unit from outside and causing short circuits in the control box 2 Keep total current of crossover wiring between indoor units less than 12 A Branch the line outside the terminal block of the unit in accordance with electrical equipment standards when using two power w...

Page 11: ...between 2 filter cleaning display indications Long life filter Light 2 500 hrs Heavy 1 250 hrs 2 Thermostat sensor selection Use both the unit sensor or remotesensorif installed AND the remote controller sensor See note 5 6 Use unit sensor only or remote sensor if installed See note 5 6 Use remote controller sensor only See note 5 6 3 Setting for display of time between 2 filter cleaning display i...

Page 12: ...re obtaining access to terminal devices all power supply circuits must be interrupted To clean the air conditioner be sure to stop operation and turn the power switch off Otherwise an electric shock and injury may result Do not wash the air conditioner with water Doing so may result in an electric shock Be careful with scaffoldings Caution must be exercised when working in high places After a long...

Page 13: ...ang only on the hinges Press both wires hinges inward as shown in the figure 23A B Open the suction grille 45 degrees and lift it upward as shown in the figure 23B 3 Remove the air filter actions 2 to 4 in the illustration Refer to procedure step 2 in How to clean the air filter on page 9 4 Clean the suction grille Wash with a soft bristle brush and neutral detergent or water and dry thoroughly Se...

Page 14: ...35A Connector power supply for adaptor X81A Connector sensor kit Connector for optional parts F2U Fuse Q1DI Earth leak detector Notes 1 Terminal block Connector Field wiring 2 In case of using a central remote controller connect it to the unit in accordance with the supplied installation manual 3 X2A X8A X24A X33A X35A X36A and X38A are connected when the optional accessories are being used In cas...

Page 15: ...F1 F2 Control box LN P1 P2 P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 P1 P2 P1 P2 1 4 2 3 5 IN D OUT D F1 F2 F1 F2 Control box LN P1 P2 P1 P2 F1 F2 T1 T2 P1 P2 P1 P2 F1 F2 T1 T2 LN P1 P2 P1 P2 F1 F2 T1 T2 LN LN P1 P2 P1 P2 F1 F2 T1 T2 N L N L N L N L N L N L 1 4 2 3 24 2 3 4 5 6 1 26 25 20 21 22 23 A B A B A B A B 1 4 4 4 4 2 3 2 3 5 5 12 13 14 15 16 17 18 19 ...

Page 16: ...4P341102 1B 2013 06 Copyright 2013 Daikin ...

Reviews: