background image

 

FXZQ15~50A2VEB
VRV System air conditioners
4P341102-1B – 2013.06

Installation and operation manual

8

Wiring example

Fit the power supply wiring of each unit with a switch and fuse as
shown in 

figure 16

.

Complete system example (3 systems)

See figures 

12

13

 and 

14

.

When using 1 remote controller for 1 indoor unit. (Normal
operation) 

(See figure 12)

.

For group control or use with 2 remote controllers 

(See figure 13)

.

When including BS unit 

(See figure 14)

.

Precautions

1.

A single switch can be used to supply power to units on the
same system. However, branch switches and branch circuit
breakers must be selected carefully.

2.

For a group control remote controller, choose the remote
controller that suits the indoor unit which has the most functions.

3.

Do not ground the equipment on gas pipes, water pipes,
lightning rods or crossground with telephones. Improper
grounding could result in electric shock.

Installation of the decoration panel

Refer to the installation manual delivered with the decoration panel.

After installing the decoration panel, ensure that there is no space
between the unit body and decoration panel. Otherwise air may leak
through the gap and cause dewdrop.

Field setting

Field setting must be made from the remote controller in accordance
with the installation condition.

Setting can be made by changing the "Mode number", "First
code No." and "Second code No.".

For setting and operation, refer to the "Field setting" in the
installation manual of the remote controller.

Summary of field settings

When using wireless remote controllers it is necessary to use
address setting. Refer to the installation manual attached to the
wireless remote controller for the setting instructions.

1

Power supply

2

Main switch

3

Power supply wiring

4

Unit transmission wiring

5

Switch

6

Fuse

7

BS unit (REYQ only)

8

Indoor unit

9

Remote controller

1

Outdoor unit

2

Indoor unit

3

Remote controller (Optional accessories)

4

Most downstream indoor unit

5

For use with 2 remote controllers

6

BS unit

NOTE

It is not necessary to designate indoor unit address
when using group control. The address is
automatically set when the power is activated.

Mode 

No.

(Note 1)

First 

code 

No. Description of setting

Second code No. (Note 2)

01

02

03

04

10 

(20)

0

Filter contamination 
- Heavy/Light

= Setting to define 

time between 2 filter 

cleaning display 

indications. (When 

contamination is 

high, setting can be 

changed to half the 

time inbetween 2 

filter cleaning 

display indications.)

Long-life 
filter

Li

gh

t

±2,500 hrs.

He

av

y

±1,250 hrs.

2

Thermostat sensor selection

Use both the 
unit sensor (or 
remote sensor if 
installed) AND 
the remote 
controller 
sensor. 
(See note 5+6)

Use unit sensor 
only (or remote 
sensor if 
installed). 
(See note 5+6)

Use remote 
controller 
sensor only.
(See note 5+6)

3

Setting for display of time 
between 2 filter cleaning display 
indications

Display

Do not display

5

Information to I-manager, 
I-touch controller

Only unit sensor 
value (or remote 
sensor value if 
installed).

Sensor value as 
set by 10-2-0X 
or 10-6-0X.

6

Thermostat sensor in group 
control

Use unit sensor 
only (or remote 
sensor if 
installed). 
(See note 6)

Use both the 
unit sensor (or 
remote sensor if 
installed) AND 
the remote 
controller 
sensor. (See 
note 4+5+6)

12 

(22)

0

Output signal X1-X2 of the 
optional KRP1B PCB kit

Thermostat-on + 
compressor run

Operation

Mal-
function

1

ON/OFF input from outside 
(T1/T2 input) = Setting when 
forced ON/OFF is to be 
operated from outside.

Forced OFF

ON/OFF
operation

2

Thermostat differential 
changeover = Setting when 
remote sensor is used.

1°C

0.5°C

3

Fan setting during thermostat 
OFF at heating operation

LL

Set speed

OFF 
(See note 3)

4

Differential automatic 
changeover

0°C

1°C

2°C

3°C
(See 
note 7)

5

Auto-restart after power failure Disabled

Enabled

13 

(23)

0

Setting for air outlet velocity 
This setting is to be changed in 
function of ceiling height.

2.7 m

>2.7 

3.0 m

>3.0 

3.5 m

1

Selection for air flow direction
This setting is to be changed 
when blocking pad optional kit 
is used.

4-way flow

3-way flow

2-way flow

4

Airflow direction range setting
This setting is to be changed 
when range of swing flap 
movement needs to be 
changed.

Upper

Medium

Lower

Note 1 :

Setting is carried out in the group mode, however, if the mode number inside parentheses is selected, 
indoor units can also be set individually.

Note 2 :

Factory settings of the Second code No. are marked in grey backgrounds.

Note 3 :

Only use in combination with optional remote sensor or when setting 10-2-03 is used.

Note 4 :

If group control is selected and remocon sensor is to be used, then set 10-6-02 & 10-2-03.

Note 5 :

If setting 10-6-02 + 10-2-01 or 10-2-02 or 10-2-03 are set at the same time, then setting 10-2-01, 
10-2-02 or 10-2-03 have priority.

Note 6 :

If setting 10-6-01 + 10-2-01 or 10-2-02 or 10-2-03 are set at the same time, then setting for group 
connection, 10-6-01 has priority and for individual connection, 10-2-01, 10-2-02 or 10-2-03 have priority.

Note 7 :

More settings for Differential automatic change over temperatures are:
Second code No.

05

4°C

06

5°C

07

6°C

08

7°C

Summary of Contents for FXZQ15A2VEB

Page 1: ...INSTALLATION AND OPERATION MANUAL FXZQ15A2VEB FXZQ20A2VEB FXZQ25A2VEB FXZQ32A2VEB FXZQ40A2VEB FXZQ50A2VEB System air conditioners ...

Page 2: ...75 a 700 700 a 575 8 7 3 2 1 4 1 1 2 3 2 1 2 2 3 2 4 5 1 5 6 575 a a 575 a 8 7 3 2 1 4 2 3 4 1 2 1 4 2 1 3 4 5 2 1 5 6 1 H2 1 PP 9 10 7 6 8 4 4 PP H2 PP PP PP 4 4 PP H1 H2 PP 2 1 5 4 3 11 2 2 1 8 8 2 4 7 1 9 10 5 5 2 7 4 3 L N 1 3 1 2 4 5 7 11 3 2 6 8 9 10 ...

Page 3: ...lineato nel A e giudicato positivamente da B secondo il Certificato C 07 Σημείωση όπως καθορίζεται στο A και κρίνεται θετικά από το B σύμφωνα με το Πιστοποιητικό C 08 Nota tal como estabelecido em A e com o parecer positivo de B de acordo com o Certificado C 09 Примечание как указано в A и в соответствии с положительным решением B согласно Свидетельству C 10 Bemærk som anført i A og positivt vurde...

Page 4: ...n kitchens Plastic parts may deteriorate Where corrosive gas like sulphurous gas exists Copper tubing and brazed spots may corrode Where volatile flammable gas like thinner or gasoline is used Where machines generating electromagnetic waves exist Control system may malfunction Where the air contains high levels of salt such as air near the ocean and where voltage fluctuates a lot e g in factories ...

Page 5: ...ht However it becomes necessary to make field settings using the remote controller when installing the unit at a height over 2 7 m To avoid accidental touching it is recommended to install the unit higher than 2 5 m Refer to Field setting on page 8 and to the decoration panel installation manual 3 Air flow directions Select the air flow directions best suited to the room and point of installation ...

Page 6: ...nger bracket Securing the hanger bracket See figure 5 2 Fix the paper pattern for installation For new ceilings only The paper pattern for installation corresponds with the measurements of the ceiling opening Consult the builder for details The centre of the ceiling opening is indicated on the paper pattern for installation The centre of the unit is indicated on the unit casing After removing the ...

Page 7: ...as being exposed to a fire Make sure there is no refrigerant gas leak A toxic gas may be released by the refrigerant gas leaking indoor and being exposed to flames from an area heater cooking stove etc Finally insulate as shown in the figure below use the supplied accessory parts Piping insulation procedure Installation shall be done by a licensed refrigeration technician the choice of materials a...

Page 8: ...ently set on a slope fit the hose with drain raising piping field supply How to perform piping See figure 6 Connect the drain hose to the drain raising pipes and insulate them Connect the drain hose to the drain outlet on the indoor unit and tighten it with the clamp Precautions Install the drain raising pipes at a height of less than H2 Install the drain raising pipes at a right angle to the indo...

Page 9: ...e remote controller refer to the Installation manual of the remote controller All wiring must be performed by an authorized electrician A main switch or other means for disconnection having a contact separation in all poles must be incorporated in the fixed wiring in accordance with relevant local and national legislation Note that the operation will restart automatically if the main power supply ...

Page 10: ...s in the casing wiring holes with putty or insulation material field supply thus to prevent small animals or dirt from entering the unit from outside and causing short circuits in the control box 2 Keep total current of crossover wiring between indoor units less than 12 A Branch the line outside the terminal block of the unit in accordance with electrical equipment standards when using two power w...

Page 11: ...between 2 filter cleaning display indications Long life filter Light 2 500 hrs Heavy 1 250 hrs 2 Thermostat sensor selection Use both the unit sensor or remotesensorif installed AND the remote controller sensor See note 5 6 Use unit sensor only or remote sensor if installed See note 5 6 Use remote controller sensor only See note 5 6 3 Setting for display of time between 2 filter cleaning display i...

Page 12: ...re obtaining access to terminal devices all power supply circuits must be interrupted To clean the air conditioner be sure to stop operation and turn the power switch off Otherwise an electric shock and injury may result Do not wash the air conditioner with water Doing so may result in an electric shock Be careful with scaffoldings Caution must be exercised when working in high places After a long...

Page 13: ...ang only on the hinges Press both wires hinges inward as shown in the figure 23A B Open the suction grille 45 degrees and lift it upward as shown in the figure 23B 3 Remove the air filter actions 2 to 4 in the illustration Refer to procedure step 2 in How to clean the air filter on page 9 4 Clean the suction grille Wash with a soft bristle brush and neutral detergent or water and dry thoroughly Se...

Page 14: ...35A Connector power supply for adaptor X81A Connector sensor kit Connector for optional parts F2U Fuse Q1DI Earth leak detector Notes 1 Terminal block Connector Field wiring 2 In case of using a central remote controller connect it to the unit in accordance with the supplied installation manual 3 X2A X8A X24A X33A X35A X36A and X38A are connected when the optional accessories are being used In cas...

Page 15: ...F1 F2 Control box LN P1 P2 P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 P1 P2 P1 P2 1 4 2 3 5 IN D OUT D F1 F2 F1 F2 Control box LN P1 P2 P1 P2 F1 F2 T1 T2 P1 P2 P1 P2 F1 F2 T1 T2 LN P1 P2 P1 P2 F1 F2 T1 T2 LN LN P1 P2 P1 P2 F1 F2 T1 T2 N L N L N L N L N L N L 1 4 2 3 24 2 3 4 5 6 1 26 25 20 21 22 23 A B A B A B A B 1 4 4 4 4 2 3 2 3 5 5 12 13 14 15 16 17 18 19 ...

Page 16: ...4P341102 1B 2013 06 Copyright 2013 Daikin ...

Reviews: