Installation and operation manual

7

FXZQ15~50A2VEB

VRV System air conditioners

4P341102-1B – 2013.06

Electrical characteristics

MCA: Min. circuit Amps (A)
MFA: Max. Fuse Amps (A)
KW: Fan Motor Rated Output (kW)
FLA: Full Load Amps (A)

Specifications for field supplied fuses and wire

Wiring example and how to set the remote 
controller

How to connect wiring 

(See figure 9)

Power supply wiring
Remove the control box lid (1) and connect the wires to the
power supply terminal block inside (L, N) and connect the
ground wire to the grounding terminal. While doing this, pull the
wires inside through the hole in the casing and clamp the wires
along with other wires using a clamp as indicated in the figure.

Unit transmission wiring and remote controller wiring
Remove the control box lid (1) and pull the wires inside through
the hole in the casing and connect to the terminal block for unit
transmission wiring (F1, F2) and remote controller wiring
(P1, P2). Securely fix the wiring using a clamp as indicated in
the figure.

After connection
Attach the small sealing (supplied with the unit) around the
cables to prevent infiltrating of water from the outside into the
unit. If two or more cables are used, divide the small sealing into
the required number of pieces and wrap them around all the
cables.

Attach the control box lid.

Precautions

1

Observe the notes mentioned below when wiring to the power
supply terminal block.
- Use a round crimp-style terminal for insulation sleeve for 

connection to the terminal block for wiring the units. When 
none are available, follow the instructions below.

- Do not connect wires of different gauge to the same power 

supply terminal. (Looseness in the connection may cause 
overheating.)

- When clamping wiring, use the clamps (delivered with the 

unit) to prevent outside pressure being exerted on the wiring 
connections. Tie up firmly. When doing the wiring, make sure 
the wiring is neat and does not cause the control box to stick 
up. Close the cover firmly.

- When connecting wires of the same gauge, connect them 

according to the figure.

Use the specified electric wire. Connect the wire securely to the
terminal. Lock the wire down without applying excessive force to
the terminal. Use torques according to the table below.

- When attaching the control box lid, make sure not to pinch 

any wires.

- After all wiring connections are done, fill in any gaps in the 

casing wiring holes with putty or insulation material (field 
supply) thus to prevent small animals or dirt from entering the 
unit from outside and causing short circuits in the control box.

2

Keep total current of crossover wiring between indoor units less
than 12 A. Branch the line outside the terminal block of the unit
in accordance with electrical equipment standards, when using
two power wiring of a gauge greater than 2 mm

2

 (Ø1.6).

The branch must be sheathed in order to provide an equal or
greater degree of insulation as power supply wiring itself.

3

Do not connect wires of different gauge to the same grounding
terminal. Looseness in the connection may deteriorate the
protection.

4

Remote controller wiring and unit transmission wiring should be
located at least 50 mm away from power supply wiring. Not
following this guideline may result in malfunction due to
electrical noise.

5

For the remote controller wiring, refer to the "Installation manual
of the remote controller" supplied with the remote controller.

6

Never connect the power supply wiring to the terminal block for
transmission wiring. This mistake could damage the entire system.

7

Use only specified wires and tightly connect wires to the
terminals. Be careful that wires do not place external stress on
the terminals. Keep wiring in neat order so that they do not
obstruct other equipment such as popping open the service
cover. Make sure the cover closes tight. Incomplete connections
could result in overheating, and in the worse case, electric shock
or fire. 

Model

Hz

Volts

Voltage range

FXZQ15~50

50

220-240

min. 198-max. 264

power supply

Fan motor

Model

MCA

MFA

KW

FLA

FXZQ15~25

0.3

16 A

0.043

0.2

FXZQ32

0.4

16 A

0.045

0.3

FXZQ40

0.4

16 A

0.059

0.3

FXZQ50

0.6

16 A

0.092

0.5

NOTE

For details, refer to "Electrical data".

Power supply wiring

Model

Field fuses

Wire

Size

FXZQ15~50

16 A

H05VV-U3G

Local codes

Transmission wiring

Model

Wire

Size

FXZQ15~50

Sheathed wire (2)

0.75-1.25 mm

2

NOTE

For details, refer to 

"Wiring example" on page 8

.

Allowable length of transmission wiring between
indoor and outdoor units, and between the indoor
unit and the remote controller is as follows:

Outdoor unit - indoor unit: max. 1000 m 
(total wiring length: 2000 m)

Indoor unit - remote controller: max 500 m

Tightening torque (N

m)

Terminal block for unit transmission and 
remote controller

0.79~0.97

Terminal block for power supply

1.18~1.44

NOTE

The customer has the ability to select the remote
controller thermistor.

1

2

3

1

Round crimp-style terminal

2

Attach insulation sleeve

3

Wiring

Summary of Contents for FXZQ15A2VEB

Page 1: ...INSTALLATION AND OPERATION MANUAL FXZQ15A2VEB FXZQ20A2VEB FXZQ25A2VEB FXZQ32A2VEB FXZQ40A2VEB FXZQ50A2VEB System air conditioners ...

Page 2: ...75 a 700 700 a 575 8 7 3 2 1 4 1 1 2 3 2 1 2 2 3 2 4 5 1 5 6 575 a a 575 a 8 7 3 2 1 4 2 3 4 1 2 1 4 2 1 3 4 5 2 1 5 6 1 H2 1 PP 9 10 7 6 8 4 4 PP H2 PP PP PP 4 4 PP H1 H2 PP 2 1 5 4 3 11 2 2 1 8 8 2 4 7 1 9 10 5 5 2 7 4 3 L N 1 3 1 2 4 5 7 11 3 2 6 8 9 10 ...

Page 3: ...lineato nel A e giudicato positivamente da B secondo il Certificato C 07 Σημείωση όπως καθορίζεται στο A και κρίνεται θετικά από το B σύμφωνα με το Πιστοποιητικό C 08 Nota tal como estabelecido em A e com o parecer positivo de B de acordo com o Certificado C 09 Примечание как указано в A и в соответствии с положительным решением B согласно Свидетельству C 10 Bemærk som anført i A og positivt vurde...

Page 4: ...n kitchens Plastic parts may deteriorate Where corrosive gas like sulphurous gas exists Copper tubing and brazed spots may corrode Where volatile flammable gas like thinner or gasoline is used Where machines generating electromagnetic waves exist Control system may malfunction Where the air contains high levels of salt such as air near the ocean and where voltage fluctuates a lot e g in factories ...

Page 5: ...ht However it becomes necessary to make field settings using the remote controller when installing the unit at a height over 2 7 m To avoid accidental touching it is recommended to install the unit higher than 2 5 m Refer to Field setting on page 8 and to the decoration panel installation manual 3 Air flow directions Select the air flow directions best suited to the room and point of installation ...

Page 6: ...nger bracket Securing the hanger bracket See figure 5 2 Fix the paper pattern for installation For new ceilings only The paper pattern for installation corresponds with the measurements of the ceiling opening Consult the builder for details The centre of the ceiling opening is indicated on the paper pattern for installation The centre of the unit is indicated on the unit casing After removing the ...

Page 7: ...as being exposed to a fire Make sure there is no refrigerant gas leak A toxic gas may be released by the refrigerant gas leaking indoor and being exposed to flames from an area heater cooking stove etc Finally insulate as shown in the figure below use the supplied accessory parts Piping insulation procedure Installation shall be done by a licensed refrigeration technician the choice of materials a...

Page 8: ...ently set on a slope fit the hose with drain raising piping field supply How to perform piping See figure 6 Connect the drain hose to the drain raising pipes and insulate them Connect the drain hose to the drain outlet on the indoor unit and tighten it with the clamp Precautions Install the drain raising pipes at a height of less than H2 Install the drain raising pipes at a right angle to the indo...

Page 9: ...e remote controller refer to the Installation manual of the remote controller All wiring must be performed by an authorized electrician A main switch or other means for disconnection having a contact separation in all poles must be incorporated in the fixed wiring in accordance with relevant local and national legislation Note that the operation will restart automatically if the main power supply ...

Page 10: ...s in the casing wiring holes with putty or insulation material field supply thus to prevent small animals or dirt from entering the unit from outside and causing short circuits in the control box 2 Keep total current of crossover wiring between indoor units less than 12 A Branch the line outside the terminal block of the unit in accordance with electrical equipment standards when using two power w...

Page 11: ...between 2 filter cleaning display indications Long life filter Light 2 500 hrs Heavy 1 250 hrs 2 Thermostat sensor selection Use both the unit sensor or remotesensorif installed AND the remote controller sensor See note 5 6 Use unit sensor only or remote sensor if installed See note 5 6 Use remote controller sensor only See note 5 6 3 Setting for display of time between 2 filter cleaning display i...

Page 12: ...re obtaining access to terminal devices all power supply circuits must be interrupted To clean the air conditioner be sure to stop operation and turn the power switch off Otherwise an electric shock and injury may result Do not wash the air conditioner with water Doing so may result in an electric shock Be careful with scaffoldings Caution must be exercised when working in high places After a long...

Page 13: ...ang only on the hinges Press both wires hinges inward as shown in the figure 23A B Open the suction grille 45 degrees and lift it upward as shown in the figure 23B 3 Remove the air filter actions 2 to 4 in the illustration Refer to procedure step 2 in How to clean the air filter on page 9 4 Clean the suction grille Wash with a soft bristle brush and neutral detergent or water and dry thoroughly Se...

Page 14: ...35A Connector power supply for adaptor X81A Connector sensor kit Connector for optional parts F2U Fuse Q1DI Earth leak detector Notes 1 Terminal block Connector Field wiring 2 In case of using a central remote controller connect it to the unit in accordance with the supplied installation manual 3 X2A X8A X24A X33A X35A X36A and X38A are connected when the optional accessories are being used In cas...

Page 15: ...F1 F2 Control box LN P1 P2 P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 P1 P2 P1 P2 1 4 2 3 5 IN D OUT D F1 F2 F1 F2 Control box LN P1 P2 P1 P2 F1 F2 T1 T2 P1 P2 P1 P2 F1 F2 T1 T2 LN P1 P2 P1 P2 F1 F2 T1 T2 LN LN P1 P2 P1 P2 F1 F2 T1 T2 N L N L N L N L N L N L 1 4 2 3 24 2 3 4 5 6 1 26 25 20 21 22 23 A B A B A B A B 1 4 4 4 4 2 3 2 3 5 5 12 13 14 15 16 17 18 19 ...

Page 16: ...4P341102 1B 2013 06 Copyright 2013 Daikin ...

Reviews: