Installation and operation manual
7
FXZQ15~50A2VEB
VRV System air conditioners
4P341102-1B – 2013.06
Electrical characteristics
MCA: Min. circuit Amps (A)
MFA: Max. Fuse Amps (A)
KW: Fan Motor Rated Output (kW)
FLA: Full Load Amps (A)
Specifications for field supplied fuses and wire
Wiring example and how to set the remote
controller
How to connect wiring
Power supply wiring
Remove the control box lid (1) and connect the wires to the
power supply terminal block inside (L, N) and connect the
ground wire to the grounding terminal. While doing this, pull the
wires inside through the hole in the casing and clamp the wires
along with other wires using a clamp as indicated in the figure.
Unit transmission wiring and remote controller wiring
Remove the control box lid (1) and pull the wires inside through
the hole in the casing and connect to the terminal block for unit
transmission wiring (F1, F2) and remote controller wiring
(P1, P2). Securely fix the wiring using a clamp as indicated in
the figure.
After connection
Attach the small sealing (supplied with the unit) around the
cables to prevent infiltrating of water from the outside into the
unit. If two or more cables are used, divide the small sealing into
the required number of pieces and wrap them around all the
cables.
Attach the control box lid.
Precautions
1
Observe the notes mentioned below when wiring to the power
supply terminal block.
- Use a round crimp-style terminal for insulation sleeve for
connection to the terminal block for wiring the units. When
none are available, follow the instructions below.
- Do not connect wires of different gauge to the same power
supply terminal. (Looseness in the connection may cause
overheating.)
- When clamping wiring, use the clamps (delivered with the
unit) to prevent outside pressure being exerted on the wiring
connections. Tie up firmly. When doing the wiring, make sure
the wiring is neat and does not cause the control box to stick
up. Close the cover firmly.
- When connecting wires of the same gauge, connect them
according to the figure.
Use the specified electric wire. Connect the wire securely to the
terminal. Lock the wire down without applying excessive force to
the terminal. Use torques according to the table below.
- When attaching the control box lid, make sure not to pinch
any wires.
- After all wiring connections are done, fill in any gaps in the
casing wiring holes with putty or insulation material (field
supply) thus to prevent small animals or dirt from entering the
unit from outside and causing short circuits in the control box.
2
Keep total current of crossover wiring between indoor units less
than 12 A. Branch the line outside the terminal block of the unit
in accordance with electrical equipment standards, when using
two power wiring of a gauge greater than 2 mm
2
(Ø1.6).
The branch must be sheathed in order to provide an equal or
greater degree of insulation as power supply wiring itself.
3
Do not connect wires of different gauge to the same grounding
terminal. Looseness in the connection may deteriorate the
protection.
4
Remote controller wiring and unit transmission wiring should be
located at least 50 mm away from power supply wiring. Not
following this guideline may result in malfunction due to
electrical noise.
5
For the remote controller wiring, refer to the "Installation manual
of the remote controller" supplied with the remote controller.
6
Never connect the power supply wiring to the terminal block for
transmission wiring. This mistake could damage the entire system.
7
Use only specified wires and tightly connect wires to the
terminals. Be careful that wires do not place external stress on
the terminals. Keep wiring in neat order so that they do not
obstruct other equipment such as popping open the service
cover. Make sure the cover closes tight. Incomplete connections
could result in overheating, and in the worse case, electric shock
or fire.
Model
Hz
Volts
Voltage range
FXZQ15~50
50
220-240
min. 198-max. 264
power supply
Fan motor
Model
MCA
MFA
KW
FLA
FXZQ15~25
0.3
16 A
0.043
0.2
FXZQ32
0.4
16 A
0.045
0.3
FXZQ40
0.4
16 A
0.059
0.3
FXZQ50
0.6
16 A
0.092
0.5
NOTE
For details, refer to "Electrical data".
Power supply wiring
Model
Field fuses
Wire
Size
FXZQ15~50
16 A
H05VV-U3G
Local codes
Transmission wiring
Model
Wire
Size
FXZQ15~50
Sheathed wire (2)
0.75-1.25 mm
2
NOTE
For details, refer to
Allowable length of transmission wiring between
indoor and outdoor units, and between the indoor
unit and the remote controller is as follows:
•
Outdoor unit - indoor unit: max. 1000 m
(total wiring length: 2000 m)
•
Indoor unit - remote controller: max 500 m
Tightening torque (N
•
m)
Terminal block for unit transmission and
remote controller
0.79~0.97
Terminal block for power supply
1.18~1.44
NOTE
The customer has the ability to select the remote
controller thermistor.
1
2
3
1
Round crimp-style terminal
2
Attach insulation sleeve
3
Wiring