FXZQ15~50A2VEB
VRV System air conditioners
4P341102-1B – 2013.06

Installation and operation manual

2

For the following items, take special care during 
construction and check after installation is finished

Notes to the installer

Read this manual carefully to ensure correct installation. Be sure
to instruct the customer how to properly operate the system and
show him/her the enclosed operation manual.

Explain to the customer what system is installed on the site. Be
sure to fill out the appropriate installation specifications in the
chapter "What to do before operation" of the outdoor unit
operation manual.

Selecting installation site

When the conditions in the ceiling are exceeding 30°C and a relative
humidity of 80%, or when fresh air is inducted into the ceiling, an
additional insulation is required (minimum 10 mm thickness,
polyethylene foam).
For this unit you can select different air flow directions. It is necessary
to purchase an optional blocking pad kit to discharge the air in 3 or
4 (closed corners) directions.

Install the unit so that air vents, lights, or machines near the unit do
not interfere with the air flow.

1

Select an installation site where the following conditions are
fulfilled and that meets your customer's approval.

Where optimum air distribution can be ensured.

Where nothing blocks air passage.

Where condensate water can be properly drained.

Where the false ceiling is not noticeably on an incline.

Where sufficient clearance for maintenance and service can be
ensured.

Where there is no risk of flammable gas leaking.

The equipment is not intended for use in a potentially explosive
atmosphere.

Where piping between indoor and outdoor units is possible within the
allowable limit. (Refer to the installation manual of the outdoor unit.)

Keep indoor unit, outdoor unit, inter unit wiring and remote
controller wiring at least 1 meter away from televisions and
radios. This is to prevent image interference and noise in those
electrical appliances. (Noise may be generated depending on the
conditions under which the electric wave is generated, even if
1 meter is kept.)

When installing the wireless remote controller kit, the distance
between wireless remote controller and indoor unit might be
shorter if there are fluorescent lights who are electrically started
in the room. The indoor unit must be installed as far as possible
away from fluorescent lights.

2

Ceiling height
This indoor unit may be installed on ceilings up to 3.5 m in
height. However, it becomes necessary to make field settings
using the remote controller when installing the unit at a height
over 2.7 m.
To avoid accidental touching, it is recommended to install the
unit higher than 2.5 m.
Refer to 

"Field setting" on page 8

 and to the decoration panel

installation manual.

3

Air flow directions
Select the air flow directions best suited to the room and point of
installation. (For air discharge in 3 directions, it is necessary to
make field settings by means of the remote controller and to
close the air outlet(s). Refer to the installation manual of the
optional blocking pad kit and to 

"Field setting" on page 8

(See

figure 1)

 (

: air flow direction)

4

Use suspension bolts for installation. Check whether the ceiling
is strong enough to support the weight of the indoor unit. If there
is a risk, reinforce the ceiling before installing the unit.
(The installation pitch is marked on the paper pattern for
installation. Refer to it to check for points requiring reinforcing.)
Space required for installation see 

figure 2

 (

: air flow

direction)

Tick 

 

when 

checked

Is the indoor unit fixed firmly?

The unit may drop, vibrate or make noise.

Is the gas leak test finished?

It may result in insufficient cooling or heating.

Is the unit fully insulated?

Condensate water may drip.

Does drainage flow smoothly?

Condensate water may drip.

Does the power supply voltage correspond to that shown on the 
name plate?

The unit may malfunction or components may burn out.

Are wiring and piping correct?

The unit may malfunction or components may burn out.

Is the unit safely grounded?

Dangerous at electric leakage.

Is the wiring size according to specifications?

The unit may malfunction or components may burn out.

Is nothing blocking the air outlet or inlet of either the indoor or 
outdoor units?

It may result in insufficient cooling or heating.

Are refrigerant piping length and additional refrigerant charge 
noted down?

The refrigerant charge in the system might not be clear.

a

Indoor unit

b

Lighting
The figure describes about a ceiling lighting, but a recessed 
ceiling light is not restricted.

c

Air fan

A

If the air outlet is closed, space marked (A) should be 500 mm at 
least. In addition, if both the right and left corner of this air outlet 
are closed, space marked (A) should be 200 mm at least.

B

1500 mm from any static volume

•PP

•PP

•PP

(

A

)

•PP

(B)

•

1500 mm

a

c

b

a

1

All-round air discharge

2

Air discharge in 4 directions

3

Air discharge in 3 directions

NOTE

Air flow directions as shown in 

figure 1

 merely

serve as examples of possible air flow directions.

1

Air discharge

2

Air inlet

NOTE

Leave 200 mm or more space where marked with *, on
sides where the air outlet is closed.

Summary of Contents for FXZQ15A2VEB

Page 1: ...INSTALLATION AND OPERATION MANUAL FXZQ15A2VEB FXZQ20A2VEB FXZQ25A2VEB FXZQ32A2VEB FXZQ40A2VEB FXZQ50A2VEB System air conditioners ...

Page 2: ...75 a 700 700 a 575 8 7 3 2 1 4 1 1 2 3 2 1 2 2 3 2 4 5 1 5 6 575 a a 575 a 8 7 3 2 1 4 2 3 4 1 2 1 4 2 1 3 4 5 2 1 5 6 1 H2 1 PP 9 10 7 6 8 4 4 PP H2 PP PP PP 4 4 PP H1 H2 PP 2 1 5 4 3 11 2 2 1 8 8 2 4 7 1 9 10 5 5 2 7 4 3 L N 1 3 1 2 4 5 7 11 3 2 6 8 9 10 ...

Page 3: ...lineato nel A e giudicato positivamente da B secondo il Certificato C 07 Σημείωση όπως καθορίζεται στο A και κρίνεται θετικά από το B σύμφωνα με το Πιστοποιητικό C 08 Nota tal como estabelecido em A e com o parecer positivo de B de acordo com o Certificado C 09 Примечание как указано в A и в соответствии с положительным решением B согласно Свидетельству C 10 Bemærk som anført i A og positivt vurde...

Page 4: ...n kitchens Plastic parts may deteriorate Where corrosive gas like sulphurous gas exists Copper tubing and brazed spots may corrode Where volatile flammable gas like thinner or gasoline is used Where machines generating electromagnetic waves exist Control system may malfunction Where the air contains high levels of salt such as air near the ocean and where voltage fluctuates a lot e g in factories ...

Page 5: ...ht However it becomes necessary to make field settings using the remote controller when installing the unit at a height over 2 7 m To avoid accidental touching it is recommended to install the unit higher than 2 5 m Refer to Field setting on page 8 and to the decoration panel installation manual 3 Air flow directions Select the air flow directions best suited to the room and point of installation ...

Page 6: ...nger bracket Securing the hanger bracket See figure 5 2 Fix the paper pattern for installation For new ceilings only The paper pattern for installation corresponds with the measurements of the ceiling opening Consult the builder for details The centre of the ceiling opening is indicated on the paper pattern for installation The centre of the unit is indicated on the unit casing After removing the ...

Page 7: ...as being exposed to a fire Make sure there is no refrigerant gas leak A toxic gas may be released by the refrigerant gas leaking indoor and being exposed to flames from an area heater cooking stove etc Finally insulate as shown in the figure below use the supplied accessory parts Piping insulation procedure Installation shall be done by a licensed refrigeration technician the choice of materials a...

Page 8: ...ently set on a slope fit the hose with drain raising piping field supply How to perform piping See figure 6 Connect the drain hose to the drain raising pipes and insulate them Connect the drain hose to the drain outlet on the indoor unit and tighten it with the clamp Precautions Install the drain raising pipes at a height of less than H2 Install the drain raising pipes at a right angle to the indo...

Page 9: ...e remote controller refer to the Installation manual of the remote controller All wiring must be performed by an authorized electrician A main switch or other means for disconnection having a contact separation in all poles must be incorporated in the fixed wiring in accordance with relevant local and national legislation Note that the operation will restart automatically if the main power supply ...

Page 10: ...s in the casing wiring holes with putty or insulation material field supply thus to prevent small animals or dirt from entering the unit from outside and causing short circuits in the control box 2 Keep total current of crossover wiring between indoor units less than 12 A Branch the line outside the terminal block of the unit in accordance with electrical equipment standards when using two power w...

Page 11: ...between 2 filter cleaning display indications Long life filter Light 2 500 hrs Heavy 1 250 hrs 2 Thermostat sensor selection Use both the unit sensor or remotesensorif installed AND the remote controller sensor See note 5 6 Use unit sensor only or remote sensor if installed See note 5 6 Use remote controller sensor only See note 5 6 3 Setting for display of time between 2 filter cleaning display i...

Page 12: ...re obtaining access to terminal devices all power supply circuits must be interrupted To clean the air conditioner be sure to stop operation and turn the power switch off Otherwise an electric shock and injury may result Do not wash the air conditioner with water Doing so may result in an electric shock Be careful with scaffoldings Caution must be exercised when working in high places After a long...

Page 13: ...ang only on the hinges Press both wires hinges inward as shown in the figure 23A B Open the suction grille 45 degrees and lift it upward as shown in the figure 23B 3 Remove the air filter actions 2 to 4 in the illustration Refer to procedure step 2 in How to clean the air filter on page 9 4 Clean the suction grille Wash with a soft bristle brush and neutral detergent or water and dry thoroughly Se...

Page 14: ...35A Connector power supply for adaptor X81A Connector sensor kit Connector for optional parts F2U Fuse Q1DI Earth leak detector Notes 1 Terminal block Connector Field wiring 2 In case of using a central remote controller connect it to the unit in accordance with the supplied installation manual 3 X2A X8A X24A X33A X35A X36A and X38A are connected when the optional accessories are being used In cas...

Page 15: ...F1 F2 Control box LN P1 P2 P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T1 T2 P1 P2 P1 P2 1 4 2 3 5 IN D OUT D F1 F2 F1 F2 Control box LN P1 P2 P1 P2 F1 F2 T1 T2 P1 P2 P1 P2 F1 F2 T1 T2 LN P1 P2 P1 P2 F1 F2 T1 T2 LN LN P1 P2 P1 P2 F1 F2 T1 T2 N L N L N L N L N L N L 1 4 2 3 24 2 3 4 5 6 1 26 25 20 21 22 23 A B A B A B A B 1 4 4 4 4 2 3 2 3 5 5 12 13 14 15 16 17 18 19 ...

Page 16: ...4P341102 1B 2013 06 Copyright 2013 Daikin ...

Reviews: