VRV SYSTEM Inverter Air Conditioners

Installation manual

CONTENTS

1. SAFETY PRECAUTIONS...............................................  1
2. BEFORE INSTALLATION ..............................................  2
3. SELECTING INSTALLATION SITE AND AIR FLOW

DIRECTION ..................................................................... 3

4. PREPARATIONS BEFORE INSTALLATION .................  4
5. INDOOR UNIT INSTALLATION .....................................  7
6. REFRIGERANT PIPING WORK ....................................  8
7. DRAIN PIPING WORK ...................................................  9
8. ELECTRIC WIRING WORK .........................................  11
9. INSTALLATION OF CORNER COVER AND AIR 

INTAKE GRILLE............................................................ 13

10. FIELD SETTINGS ........................................................  14
11. TEST OPERATION ......................................................  14

1.

SAFETY PRECAUTIONS

Please read these “SAFETY PRECAUTIONS” carefully before 
installing air conditioning unit and be sure to install it correctly.
After completing installation, conduct a trial operation to check 
for faults and explain to the customer how to operate the air con-
ditioner and take care of it with the aid of the operation manual. 
Ask the customer to store the installation manual along with the 
operation manual for future reference.

This air conditioner comes under the term “appliances not 
accessible to the general public”.

Safety Precaution

This unit is a class A product. In a domestic environment this 
product may cause radio interference in which case the user 
may be required to take adequate measures.

Meaning of WARNING and CAUTION notices

WARNING

........Failure to follow these instructions prop-

erly may result in personal injury or loss 
of life.

CAUTION

.........Failure to observe these instructions 

properly may result in property damage 
or personal injury, which may be serious 
depending on the circumstances.

WARNING

• Ask your dealer or qualified personnel to carry out installation 

work.
Do not attempt to install the air conditioner yourself. Improper 
installation may result in water leakage, electric shocks or 
fire.

• Install the air conditioner in accordance with the instructions 

in this installation manual.
Improper installation may result in water leakage, electric 
shocks or fire.

• Consult your local dealer regarding what to do in case of 

refrigerant leakage. When the air conditioner is to be 
installed in a small room, it is necessary to take proper mea-
sures so that the amount of any leaked refrigerant does not 
exceed the concentration limit in the event of a leakage. 
Otherwise, this may lead to an accident due to oxygen 
depletion.

• Be sure to use only the specified accessories and parts for 

installation work.
Failure to use the specified parts may result in the unit fall-
ing, water leakage, electric shocks or fire. 

• Install the air conditioner on a foundation strong enough to 

withstand the weight of the unit.
A foundation of insufficient strength may result in the equip-
ment falling and causing injury.

• Carry out the specified installation work after taking into 

account strong winds, typhoons or earthquakes.
Failure to do so during installation work may result in the unit 
falling and causing accidents.

• Make sure that a separate power supply circuit is provided 

for this unit and that all electrical work is carried out by qual-
ified personnel according to local laws and regulations and 
this installation manual.
An insufficient power supply capacity or improper electrical 
construction may lead to electric shocks or fire.

• Make sure that all wiring is secured, the specified wires are 

used, and that there is no strain on the terminal connections 
or wires.
Improper connections or securing of wires may result in 
abnormal heat build-up or fire.

• When wiring the power supply and connecting the remote 

controller wiring and transmission wiring, position the wires 
so that the control box lid can be securely fastened.
Improper positioning of the control box lid may result in elec-
tric shocks, fire or the terminals overheating.

• If refrigerant gas leaks during installation, ventilate the area 

immediately.
Toxic gas may be produced if the refrigerant comes into con-
tact with fire.

• After completing installation, check for refrigerant gas leakage.

Toxic gas may be produced if the refrigerant gas leaks into the 
room and comes into contact with a source of fire, such as a 
fan heater, stove or cooker.

• Be sure to switch off the unit before touching any electrical 

parts.

• Do not directly touch the refrigerant leaked from refrigerant 

piping connections. 
Frostbite may be caused.

• Be sure to earth the air conditioner.

Do not earth the unit to a utility pipe, lightning conductor or 
telephone earth lead. Imperfect earthing may result in elec-
tric shocks or fire.
A high surge current from lightning or other sources may 
cause damage to the air conditioner.

• Be sure to install an earth leakage breaker.

Failure to install an earth leakage breaker may result in elec-
tric shocks or fire.

CAUTION

• While following the instructions in this installation manual, 

install drain piping to ensure proper drainage and insulate 
piping to prevent condensation.
Improper drain piping may result in indoor water leakage 
and property damage.

• Install the indoor and outdoor units, power cord and con-

necting wires at least 1 meter away from televisions or 
radios to prevent picture interference and noise.
(Depending on the incoming signal strength, a distance of 
1 meter may not be sufficient to eliminate noise.)

• Remote controller (wireless kit) transmitting distance can be 

shorter than expected in rooms with electronic fluorescent 
lamps (inverter or rapid start types).
Install the indoor unit as far away from fluorescent lamps as 
possible.

01_EN_3P086156-10X.fm  Page 1  Wednesday, April 15, 2009  3:48 PM

Summary of Contents for FXUQ100MAV1

Page 1: ... ESTAS INSTRUCCIONES ANTES DE INSTALAR GUARDE ESTE MANUAL EN UN LUGAR A MANO PARA LEER EN CASO DE TENER ALGUNA DUDA PRIMA DELL INSTALLAZIONE LEGGERE ATTENTAMENTE QUESTE ISTRUZIONI TENERE QUESTO MANUALE A PORTATA DI MANO PER RIFERIMENTI FUTURI ÄΙΑΒΑΣΤΕ ΠΡΟΣΕΚΤΙΚΑ ΑΥΤΕΣ ΤΙΣ ΟÄΗΓΙΕΣ ΠΡΙΝ ΑΠΟ ΤΗΝ ΕΓΚΑΤΑΣΤΑΣΗ ΕΧΕΤΕ ΑΥΤΟ ΤΟ ΕΓΧΕΙΡΙÄΙΟ ΕΥΚΑΙΡΟ ΓΙΑ ΝΑ ΤΟ ΣΥΜΒΟΥΛΕΥΕΣΤΕ ΣΤΟ ΜΕΛΛΟΝ LEES DEZE INSTRUCTIES ZORG...

Page 2: ...20MVE FXSQ25MVE FXSQ32MVE FXSQ40MVE FXSQ50MVE FXSQ63MVE FXSQ80MVE FXSQ100MVE FXSQ125MVE FXKQ25MVE FXKQ32MVE FXKQ40MVE FXKQ63MVE FXAQ20MVE FXAQ25MVE FXAQ32MVE FXAQ40MVE FXAQ50MVE FXAQ63MVE FXUQ71MV1 FXUQ100MV1 FXUQ125MV1 BEVQ71MVE BEVQ100MVE BEVQ125MVE FXMQ125MFV1 FXMQ200MFV1 FXMQ250MFV1 FXAQ20MHV1 FXAQ25MHV1 FXAQ32MHV1 FXAQ40MHV1 FXAQ50MHV1 BEVQ50MVE FXLQ20MHV1 FXLQ25MHV1 FXLQ32MHV1 FXLQ40MHV1 FXL...

Page 3: ...alling and causing injury Carry out the specified installation work after taking into account strong winds typhoons or earthquakes Failure to do so during installation work may result in the unit falling and causing accidents Make sure that a separate power supply circuit is provided for this unit and that all electrical work is carried out by qual ified personnel according to local laws and regul...

Page 4: ...e used Using the wrong refrigerant will prevent the unit from functioning properly Do not dispose of any parts necessary for installation until the installation is complete 2 1 PRECAUTIONS Be sure to read this manual before installing the indoor unit When selecting installation site refer to the paper pattern This unit is suitable for installation in a household commer cial and light industrial en...

Page 5: ... Where unavoidably lower take what measures are neces sary to keep hands out of the air outlet Space is required to attach detach corner covers 3 2 Air flow direction Select the air flow direction that best suits the unit s location 2 way and 3 way air flow must be set from the remote control ler For details see 10 FIELD SETTINGS NOTE Restrictions are placed on piping direction therefore select fl...

Page 6: ...the ceiling to bear the weight of the unit Adjust clear ance from the false ceiling before proceeding further 3 Detach the air intake grille and corner covers from the indoor unit Detach the air intake grille Refer to Fig 4 and 5 Slide the locking knobs 2 on the air intake grille inward direction of arrows and lift upwards Open the air intake grille to a 45 angle and detach from the unit Detach th...

Page 7: ...piping All the above parts are field supplied Use either a M8 M10 size bolt Use a hole in anchor for existing ceilings and a sunken insert sunken anchor or other field supplied parts for new ceilings to reinforce the ceiling to bear the weight of the unit Adjust clearance from the false ceiling before proceeding further 3 Detach the air intake grille and corner covers from the indoor unit Detach t...

Page 8: ...ets C and D are closed so that air flow rate is the same in all four directions Air flow rate can be changed by sliding the shutter Refer to Fig 14 CAUTION Be careful not to touch the heat exchanger fins 2 way air discharge Refer to Fig 15 NOTE Illustrations seen from ceiling Air intake grille Cornercover 4 Hold the indoor unit by the hanger brackets when carrying Flap Top decorative plate Screw f...

Page 9: ... As for the parts to be used for installation work be sure to use the provided accessories and specified parts designated by our company 5 1 Fit the top nuts and washers over the suspension bolts 4 Use the washer fixing plate 5 to keep the washer from fall ing out of place Hang the unit from the hangers on side A and then fit the bottom washers and nuts over the suspen sion bolts on that side Refe...

Page 10: ...pes of refrigerant are not the same CAUTION Use a pipe cutter and flare suitable for the type of refrig erant Apply ester oil or ether oil around the flare section before connecting To prevent dust moisture or other foreign matter from infiltrating the tube either pinch the end or cover it with tape Do not allow anything other than the designated refrig erant to get mixed into the refrigerant circ...

Page 11: ...tems For instance if the chlorine based flux is used it will cause piping corrosion or in particular if the flux contains fluo rine it will damage the refrigerant oil Before brazing local refrigerant piping nitrogen gas shall be blown through the piping to expel air from the piping If you brazing is done without nitrogen gas blowing a large amount of oxide film develops inside the piping and could...

Page 12: ... 30 CAUTION If the upward running drain hose leans at a slant the float switch will malfunction and water will leak 7 2 After piping work is finished check if drainage flows smoothly Open the water inlet lid add approximately 1 liter of water slowly and check drainage flow Refer to Fig 31 1 1 5 m VP20 VP20 Drain piping field supplied Drain hose 1 For VP20 connection accessory 500 Clamp 2 accessory...

Page 13: ... the size of power supply wiring connected to the outdoor unit the capacity of the circuit breaker and switch and wir ing instructions Be sure to ground the air conditioner Do not connect the ground wire to gas and water pipes lightning rods or telephone ground wires Gas pipes might cause explosions or fire if gas leaks Water pipes no grounding effect if hard vinyl piping is used Telephone ground ...

Page 14: ...NSTALLATION MANUAL OF REMOTE CONTROLLER attached to the remote controller 6 Never connect power supply wiring to the terminal block for remote controller wiring A mistake of the sort could damage the entire system 7 Use only specified wiring and tightly connect wiring to termi nals Be careful wiring do not place external stress on termi nals Keep wiring in neat order and so as not to obstruct othe...

Page 15: ...ontrol 9 INSTALLATION OF CORNER COVER AND AIR INTAKE GRILLE Attach the corner covers to the unit and lock in place by screw The screws are taped to the corner covers For upward or rightward running pipes cut the corner covers as shown at Fig 36 before attaching them Refer to Fig 36 Attach the air intake grille Hook the strings to the unit to prevent the grille from drop ping Refer to Fig 37 L N L ...

Page 16: ...y to identify the point of trouble An explanation of malfunction codes and the corresponding trouble is pro vided in CAUTION FOR SERVICING of the outdoor unit If any of the items in Table 9 are displayed there may be a problem with the wiring or power so check the wiring again Table 9 CAUTION If all interior work has not been completed when the test run is done tell the customer not to run the uni...

Page 17: ... 0905 HT 3P086156 10X EM03A117B 00_CV_3P086156 10X fm Page 2 Monday April 13 2009 4 46 PM ...