background image

14

English

10. FIELD SETTINGS

10-1 Make sure the control box lids are closed on 

the indoor and BEV and outdoor units.

Field setting must be made from the remote controller in 
accordance with the installation condition.

• Setting can be made by changing the “Mode No.”, “FIRST 

CODE NO.”, and “SECOND CODE NO.”.

• The “Field Settings” included with the remote control lists 

the order of the settings and method of operation.
Setting is made in all units in a group. To set for individual 
indoor units or to check the setting, use the mode Nos. (with 
“2” in upper digit) in parentheses ( ). 

• Set the remote controller to the field set mode. For 

details, refer to the “HOW TO SET IN THE FIELD”, in 
the remote controller manual. 

10-2 Setting ceiling height

• Select the SECOND CODE NO. that corresponds to the 

ceiling height. Refer to Table 5 and 6. 
(SECOND CODE NO. is set to “01” when the unit is shipped 
from the factory for ceilings 2.7m or lower in 4-way air dis-
charge mode.)

Table 5

Table 6

10-3 Setting for option

• For setting for option, see the installation instructions pro-

vided with the option.

10-4 Setting air discharge direction

• For changing air discharge direction to 2-way or 3-way air dis-

charge, change the SECOND CODE NO. as shown Table 7.
(SECOND CODE NO. is factory set to “01” for a air discharge 
direction of 4-way air discharge.)

Table 7

10-5 Setting air filter sign

• Remote controllers are equiped with liquid crystal display air 

filer signs to display the time to clean air filters.

• Change the SECOND CODE NO. according to Table 8 

depending on the amount of dirt or dust in the room.
(SECOND CODE NO. is factory set to “01” for filter contami-
nation-light)

Table 8

11. TEST OPERATION 

Refer to the installation manual of the outdoor unit.

• The operation lamp of the remote controller will flash when a 

malfunction occurs. Check the malfunction code on the liquid 
crystal display to identify the point of trouble. An explanation 
of malfunction codes and the corresponding trouble is pro-
vided in “CAUTION FOR SERVICING” of the outdoor unit.
If any of the items in Table 9 are displayed, there may be a 
problem with the wiring or power, so check the wiring again.

Table 9

CAUTION

If all interior work has not been completed when the test-run is 
done, tell the customer not to run the unit until all interior work 
has been completed, in order to protect the indoor unit. If the 
unit is run, the indoor unit will be contaminated by substances 
given off by the paints, adhesives, and other materials used in 
the interior work, causing sparks and leaking.

Ceiling height (m)

Setting

4-way air dis-

charge

3-way air dis-

charge

2-way air dis-

charge

Less than 2.7m

Less than 3m

Less than 3.5m

N

More than 2.7m;

3m or less

More than 3m;

3.5m or less

More than 3.5m;

3.8m or less

H

More than 3m;

3.5m or less

More than 3.5m;

3.8m or less

S

Setting

Mode No.

FIRST CODE NO.

SECOND CODE NO.

N

13 (23)

0

01

H

02

S

03

Setting

Mode No.

FIRST CODE NO. SECOND CODE NO.

4-way air 

discharge

13 (23)

1

01

3-way air 

discharge

02

2-way air 

discharge

03

SETTING

Mode No.

SECOND 
CODE NO.

FIELD SET 
MODE

FIRST 
CODE NO.

Setting

Spacing time of 

display air filter 

sign (long life type)

Mode No.

FIRST 
CODE 

NO.

SECOND 

CODE 

NO.

Air filter con-

tamination

-light

Approx. 2500 hrs

10 (20)

0

01

Air filter con-

tamination

-heavy

Approx. 1250 hrs

02

Remote con-

trol display

Content

“U3” is lit up

• The test-run has not been completed.

“U4” is lit up

“UH” is lit up

• The power on the outdoor unit is off.
• The outdoor unit has not been wired for power 

supply.

• The transmission wiring between the outdoor 

unit and the BEV unit has been cut.

“UF” is lit up

• The wiring with the BEV is incorrect.

No display

• The power on the BEV unit is off.
• The BEV unit has not been wired for power supply.
• Incorrect wiring for the remote controller wiring, 

and/or the transmission wiring.

• The remote controller wiring is cut.
• The wiring with the BEV is incorrect.

01_EN_3P086156-10X.fm  Page 14  Wednesday, April 15, 2009  3:48 PM

Summary of Contents for FXUQ100MAV1

Page 1: ... ESTAS INSTRUCCIONES ANTES DE INSTALAR GUARDE ESTE MANUAL EN UN LUGAR A MANO PARA LEER EN CASO DE TENER ALGUNA DUDA PRIMA DELL INSTALLAZIONE LEGGERE ATTENTAMENTE QUESTE ISTRUZIONI TENERE QUESTO MANUALE A PORTATA DI MANO PER RIFERIMENTI FUTURI ÄΙΑΒΑΣΤΕ ΠΡΟΣΕΚΤΙΚΑ ΑΥΤΕΣ ΤΙΣ ΟÄΗΓΙΕΣ ΠΡΙΝ ΑΠΟ ΤΗΝ ΕΓΚΑΤΑΣΤΑΣΗ ΕΧΕΤΕ ΑΥΤΟ ΤΟ ΕΓΧΕΙΡΙÄΙΟ ΕΥΚΑΙΡΟ ΓΙΑ ΝΑ ΤΟ ΣΥΜΒΟΥΛΕΥΕΣΤΕ ΣΤΟ ΜΕΛΛΟΝ LEES DEZE INSTRUCTIES ZORG...

Page 2: ...20MVE FXSQ25MVE FXSQ32MVE FXSQ40MVE FXSQ50MVE FXSQ63MVE FXSQ80MVE FXSQ100MVE FXSQ125MVE FXKQ25MVE FXKQ32MVE FXKQ40MVE FXKQ63MVE FXAQ20MVE FXAQ25MVE FXAQ32MVE FXAQ40MVE FXAQ50MVE FXAQ63MVE FXUQ71MV1 FXUQ100MV1 FXUQ125MV1 BEVQ71MVE BEVQ100MVE BEVQ125MVE FXMQ125MFV1 FXMQ200MFV1 FXMQ250MFV1 FXAQ20MHV1 FXAQ25MHV1 FXAQ32MHV1 FXAQ40MHV1 FXAQ50MHV1 BEVQ50MVE FXLQ20MHV1 FXLQ25MHV1 FXLQ32MHV1 FXLQ40MHV1 FXL...

Page 3: ...alling and causing injury Carry out the specified installation work after taking into account strong winds typhoons or earthquakes Failure to do so during installation work may result in the unit falling and causing accidents Make sure that a separate power supply circuit is provided for this unit and that all electrical work is carried out by qual ified personnel according to local laws and regul...

Page 4: ...e used Using the wrong refrigerant will prevent the unit from functioning properly Do not dispose of any parts necessary for installation until the installation is complete 2 1 PRECAUTIONS Be sure to read this manual before installing the indoor unit When selecting installation site refer to the paper pattern This unit is suitable for installation in a household commer cial and light industrial en...

Page 5: ... Where unavoidably lower take what measures are neces sary to keep hands out of the air outlet Space is required to attach detach corner covers 3 2 Air flow direction Select the air flow direction that best suits the unit s location 2 way and 3 way air flow must be set from the remote control ler For details see 10 FIELD SETTINGS NOTE Restrictions are placed on piping direction therefore select fl...

Page 6: ...the ceiling to bear the weight of the unit Adjust clear ance from the false ceiling before proceeding further 3 Detach the air intake grille and corner covers from the indoor unit Detach the air intake grille Refer to Fig 4 and 5 Slide the locking knobs 2 on the air intake grille inward direction of arrows and lift upwards Open the air intake grille to a 45 angle and detach from the unit Detach th...

Page 7: ...piping All the above parts are field supplied Use either a M8 M10 size bolt Use a hole in anchor for existing ceilings and a sunken insert sunken anchor or other field supplied parts for new ceilings to reinforce the ceiling to bear the weight of the unit Adjust clearance from the false ceiling before proceeding further 3 Detach the air intake grille and corner covers from the indoor unit Detach t...

Page 8: ...ets C and D are closed so that air flow rate is the same in all four directions Air flow rate can be changed by sliding the shutter Refer to Fig 14 CAUTION Be careful not to touch the heat exchanger fins 2 way air discharge Refer to Fig 15 NOTE Illustrations seen from ceiling Air intake grille Cornercover 4 Hold the indoor unit by the hanger brackets when carrying Flap Top decorative plate Screw f...

Page 9: ... As for the parts to be used for installation work be sure to use the provided accessories and specified parts designated by our company 5 1 Fit the top nuts and washers over the suspension bolts 4 Use the washer fixing plate 5 to keep the washer from fall ing out of place Hang the unit from the hangers on side A and then fit the bottom washers and nuts over the suspen sion bolts on that side Refe...

Page 10: ...pes of refrigerant are not the same CAUTION Use a pipe cutter and flare suitable for the type of refrig erant Apply ester oil or ether oil around the flare section before connecting To prevent dust moisture or other foreign matter from infiltrating the tube either pinch the end or cover it with tape Do not allow anything other than the designated refrig erant to get mixed into the refrigerant circ...

Page 11: ...tems For instance if the chlorine based flux is used it will cause piping corrosion or in particular if the flux contains fluo rine it will damage the refrigerant oil Before brazing local refrigerant piping nitrogen gas shall be blown through the piping to expel air from the piping If you brazing is done without nitrogen gas blowing a large amount of oxide film develops inside the piping and could...

Page 12: ... 30 CAUTION If the upward running drain hose leans at a slant the float switch will malfunction and water will leak 7 2 After piping work is finished check if drainage flows smoothly Open the water inlet lid add approximately 1 liter of water slowly and check drainage flow Refer to Fig 31 1 1 5 m VP20 VP20 Drain piping field supplied Drain hose 1 For VP20 connection accessory 500 Clamp 2 accessory...

Page 13: ... the size of power supply wiring connected to the outdoor unit the capacity of the circuit breaker and switch and wir ing instructions Be sure to ground the air conditioner Do not connect the ground wire to gas and water pipes lightning rods or telephone ground wires Gas pipes might cause explosions or fire if gas leaks Water pipes no grounding effect if hard vinyl piping is used Telephone ground ...

Page 14: ...NSTALLATION MANUAL OF REMOTE CONTROLLER attached to the remote controller 6 Never connect power supply wiring to the terminal block for remote controller wiring A mistake of the sort could damage the entire system 7 Use only specified wiring and tightly connect wiring to termi nals Be careful wiring do not place external stress on termi nals Keep wiring in neat order and so as not to obstruct othe...

Page 15: ...ontrol 9 INSTALLATION OF CORNER COVER AND AIR INTAKE GRILLE Attach the corner covers to the unit and lock in place by screw The screws are taped to the corner covers For upward or rightward running pipes cut the corner covers as shown at Fig 36 before attaching them Refer to Fig 36 Attach the air intake grille Hook the strings to the unit to prevent the grille from drop ping Refer to Fig 37 L N L ...

Page 16: ...y to identify the point of trouble An explanation of malfunction codes and the corresponding trouble is pro vided in CAUTION FOR SERVICING of the outdoor unit If any of the items in Table 9 are displayed there may be a problem with the wiring or power so check the wiring again Table 9 CAUTION If all interior work has not been completed when the test run is done tell the customer not to run the uni...

Page 17: ... 0905 HT 3P086156 10X EM03A117B 00_CV_3P086156 10X fm Page 2 Monday April 13 2009 4 46 PM ...

Reviews: