EDUS391777-F17
Installation Manual
FXSQ-TAVJU
18
3P184443-13Z
18
English
10-1 Settings for external static pressure
r
Make settings in either method (a) or method (b).
(a) Make settings with Air volume automatic adjust-
ment function.
“Air volume automatic adjustment” function: The air volume
is adjusted to the rated air volume automatically.
CAUTION
r
$GUWTGVQEJGEMVJCVVJGGZVGTPCNUVCVKERTGUUWTGKUYKVJKP
VJGURGEKƂECVKQPTCPIGDGHQTGOCMKPIUGVVKPIU6JGGZVGTPCN
static pressure will not be automatically adjusted and air
XQNWOGKPUWHƂEKGPE[QTYCVGTNGCMCIGOC[TGUWNVKHVJG
GZVGTPCNUVCVKERTGUUWTGKUQWVUKFGVJGTCPIG4GHGTVQVJG
VGEJPKECNFQEWOGPVHQTVJGUGVVKPITCPIGQHGZVGTPCNUVCVKE
pressure.)
(1)
Check that the electrical wiring and duct work have been
completed.
(If the closing damper is set midway, be sure to check that
the damper is opened. Furthermore, check that the air
RCUUCIGQPVJGUWEVKQPUKFGKURTQXKFGFYKVJCPCKTƂNVGT
ƂGNFUWRRN[
(2)
If air conditioner has more than one air outlet and air
inlet, be sure to make adjustments so that the air volume
ratio of each air outlet and the corresponding air inlet will
conform to the designed air volume ratio.
In that case, set the operating mode to “Fan”. (In the case
of changing the air volume, press the fan speed button on
the remote controller and change the current selection to
“High”, “Medium”, or “Low”.)
(3)
Make settings to adjust the air volume automatically.
After setting the operating mode to “Fan”, set the air
EQPFKVKQPGTVQƂGNFUGVVKPIOQFGYKVJVJGQRGTCVKQPQHVJG
air conditioner stopped. Select Mode No. [21] (11 in the
case of batch settings), select FIRST CODE No. “7”, and
set the SECOND CODE No. to “03”.
Return to the “Basic screen” (“Normal mode” if a wireless
remote controller is used), and press the ON/OFF button.
The operation lamp is lit, and the indoor unit will go into
fan operation for air volume automatic adjustments (at
which time, do not adjust the opening of the air outlet
or inlet). The air volume adjustments will automatically
VGTOKPCVGCRRTQZKOCVGN[VQOKPWVGUCHVGTVJGKPFQQT
unit comes into operation, and the operation lamp will be
OFF and the indoor unit will come to a stop.
Table 7
Mode No.
FIRST
CODE
No.
Setting
content
SECOND CODE No.
01
02
03
11 (21)
7
Air volume
adjust-
ment
OFF
Air volume
adjust-
ment
completion
Air volume
adjust-
ment start
(4)
After the air conditioner comes to a stop, be sure to
check with Mode No. [21] per indoor unit that the above
SECOND CODE No. is “02”. If the operation of the air
conditioner does not stop automatically or the SECOND
CODE No. is not set to “02”, repeat the setting procedure
from (3).
CAUTION
r
+HCKTƃQYRCVJYC[EJCPIGUUWEJCUFWEVCPFCKTQWVNGV
changes, are made after air volume adjustments, be sure to
make “Air volume automatic adjustment” again.
r
+HCKTƃQYRCVJYC[EJCPIGUUWEJCUFWEVCPFCKTQWVNGV
changes, are made after
11. TEST OPERATION
or air
conditioner relocation, contact your dealer.
(b) Select external static pressure with the remote controller.
Check with Mode No. [21] per indoor unit that the SECOND
CODE No. for the above “Air volume adjustment” is set to
“01” (OFF). (The SECOND CODE No. is factory set to “01”
(OFF).)
Change the SECOND CODE No. by referring to the table
DGNQYCEEQTFKPIVQVJGGZVGTPCNUVCVKERTGUUWTGQHVJGFWEV
to be connected.
Table 8
In case of 05-48 type
'ZVGTPCNUVCVKERTGUUWTG
Mode No.
FIRST
CODE No.
SECOND
CODE No.
0.12 inWG (30 Pa) (*1)
13(23)
6
03
0.16 inWG (40 Pa) (*1)
04
0.20 inWG (50 Pa)
05
0.24 inWG (60 Pa)
06
0.28 inWG (70 Pa)
07
0.32 inWG (80 Pa)
08
0.36 inWG (90 Pa)
09
0.40 inWG (100 Pa)
10
0.44 inWG (110 Pa)
11
0.48 inWG (120 Pa)
12
0.52 inWG (130 Pa)
13
0.56 inWG (140 Pa)
14
0.60 inWG (150 Pa)
15
(*1) The FXSQ18-48 type cannot be set to 0.12 inWG (30
Pa) or 0.16 inWG (40 Pa).
In case of 54 type
'ZVGTPCNUVCVKERTGUUWTG
Mode No.
FIRST
CODE No.
SECOND
CODE No.
0.20 inWG (50 Pa)
13(23)
6
05
0.24 inWG (60 Pa)
06
0.28 inWG (70 Pa)
07
0.32 inWG (80 Pa)
08
0.36 inWG (90 Pa)
09
0.40 inWG (100 Pa)
10
0.44 inWG (110 Pa)
11
0.48 inWG (120 Pa)
12
0.52 inWG (130 Pa)
13
0.56 inWG (140 Pa)
14
10-2 SETTING WHEN AN OPTIONAL ACCESSORY
IS ATTACHED
r
For setting when attaching an optional accessory, refer to
the installation manual attached to the optional accessory.
10-3 SETTING FAN SPEED DURING THERMOSTAT
OFF
r
Set the fan speed according to the using environment after
consultation with your customer.
r
9JGPVJGHCPURGGFKUEJCPIGFGZRNCKPVJGUGVHCPURGGF
to your customer.
Summary of Contents for FXSQ05TAVJU
Page 1: ...EDUS391777 F17 FXSQ TAVJU MSP Concealed Ducted Unit...
Page 2: ......
Page 12: ...Dimensions EDUS391777 F17 10 FXSQ TAVJU FXSQ15TAVJU 3D110731A...
Page 13: ...EDUS391777 F17 Dimensions FXSQ TAVJU 11 FXSQ18TAVJU 3D110732A...
Page 14: ...Dimensions EDUS391777 F17 12 FXSQ TAVJU FXSQ24TAVJU FXSQ30TAVJU 3D110733B...
Page 15: ...EDUS391777 F17 Dimensions FXSQ TAVJU 13 FXSQ36TAVJU FXSQ48TAVJU 3D110734B...
Page 16: ...Dimensions EDUS391777 F17 14 FXSQ TAVJU FXSQ54TAVJU 3D110735B...
Page 24: ...Fan Performance EDUS391777 F17 22 FXSQ TAVJU FXSQ09TAVJU 3D112417...
Page 25: ...EDUS391777 F17 Fan Performance FXSQ TAVJU 23 FXSQ12TAVJU 3D112418...
Page 26: ...Fan Performance EDUS391777 F17 24 FXSQ TAVJU FXSQ15TAVJU 3D112419...
Page 27: ...EDUS391777 F17 Fan Performance FXSQ TAVJU 25 FXSQ18TAVJU 3D112420...
Page 28: ...Fan Performance EDUS391777 F17 26 FXSQ TAVJU FXSQ24TAVJU 3D112421...
Page 29: ...EDUS391777 F17 Fan Performance FXSQ TAVJU 27 FXSQ30TAVJU 3D112422...
Page 30: ...Fan Performance EDUS391777 F17 28 FXSQ TAVJU FXSQ36TAVJU 3D112423...
Page 31: ...EDUS391777 F17 Fan Performance FXSQ TAVJU 29 FXSQ48TAVJU 3D112424...
Page 32: ...Fan Performance EDUS391777 F17 30 FXSQ TAVJU FXSQ54TAVJU 3D112425...
Page 34: ...Airflow Auto Adjustment Characteristics EDUS391777 F17 32 FXSQ TAVJU FXSQ09TAVJU 3D112454...
Page 35: ...EDUS391777 F17 Airflow Auto Adjustment Characteristics FXSQ TAVJU 33 FXSQ12TAVJU 3D112455...
Page 36: ...Airflow Auto Adjustment Characteristics EDUS391777 F17 34 FXSQ TAVJU FXSQ15TAVJU 3D112456...
Page 37: ...EDUS391777 F17 Airflow Auto Adjustment Characteristics FXSQ TAVJU 35 FXSQ18TAVJU 3D112457...
Page 38: ...Airflow Auto Adjustment Characteristics EDUS391777 F17 36 FXSQ TAVJU FXSQ24TAVJU 3D112458...
Page 39: ...EDUS391777 F17 Airflow Auto Adjustment Characteristics FXSQ TAVJU 37 FXSQ30TAVJU 3D112459...
Page 40: ...Airflow Auto Adjustment Characteristics EDUS391777 F17 38 FXSQ TAVJU FXSQ36TAVJU 3D112460...
Page 41: ...EDUS391777 F17 Airflow Auto Adjustment Characteristics FXSQ TAVJU 39 FXSQ48TAVJU 3D112461...
Page 42: ...Airflow Auto Adjustment Characteristics EDUS391777 F17 40 FXSQ TAVJU FXSQ54TAVJU 3D112462...
Page 44: ...Sound Levels Reference Data EDUS391777 F17 42 FXSQ TAVJU FXSQ12TAVJU 4D110413...
Page 45: ...EDUS391777 F17 Sound Levels Reference Data FXSQ TAVJU 43 FXSQ15TAVJU 4D110414...
Page 46: ...Sound Levels Reference Data EDUS391777 F17 44 FXSQ TAVJU FXSQ18TAVJU 4D110415...
Page 47: ...EDUS391777 F17 Sound Levels Reference Data FXSQ TAVJU 45 FXSQ24TAVJU 4D110416...
Page 48: ...Sound Levels Reference Data EDUS391777 F17 46 FXSQ TAVJU FXSQ30TAVJU 4D110417...
Page 49: ...EDUS391777 F17 Sound Levels Reference Data FXSQ TAVJU 47 FXSQ36TAVJU 4D110418...
Page 50: ...Sound Levels Reference Data EDUS391777 F17 48 FXSQ TAVJU FXSQ48TAVJU 4D110419...
Page 51: ...EDUS391777 F17 Sound Levels Reference Data FXSQ TAVJU 49 FXSQ54TAVJU 4D110420...
Page 75: ......