background image

8

English

6.  REFRIGERANT PIPING WORK

• 

For the outdoor unit refrigerant piping, refer to the installa-
tion manual attached to the outdoor unit.

• 

Carry out insulation of both gas and liquid refrigerant piping 
securely. If not insulated, it may cause water leakage. For 
gas piping, use insulation material of which heat resistant 
temperature is not less than 250°F (120°C). 
For use under high humidity, strengthen the insulation ma-
terial for refrigerant piping. If not strengthened, the surface 
of insulation material may sweat.

• 

Before installation work, make sure that the refrigerant is 
R410A. (Unless the refrigerant is R410A, the nor mal opera-

tion cannot be expected.)

 CAUTION

This air conditioner is a dedicated model for refriger-

ant R410A. Make sure to meet the require ments shown 

below and carry out installation work.

•  Use dedicated piping cutters and flaring tools for 

R410A.

•  When making a flare connection, coat the flared in

-

ner surface only with ether oil or ester oil.

•  Use only the flare nuts attached to the air condition

-

er. If other flare nuts are used, it may cause refriger

-

ant leakage.

• 

To prevent contamination or moisture from getting 

into the piping, take measures such as pinch ing or 

taping the pipings.

Do not mix substance other than the specified refrig

-

erant such as air into the refrigeration circuit. 

If the refrigerant leaks during the work, ventilate the 

room.

• 

The refrigerant is pre-charged in the outdoor unit.

• 

When connecting the pipings to the air conditioner, 
make sure to use a spanner and a torque wrench as 
shown in 

Fig. 9

.

• 

For the dimension of flared part and the tightening 

torque, refer to the Table 2.

• 

When making a flare connection, coat the flared inner 

surface only with ether oil or ester oil.  

(Refer to Fig. 10)

 

Then, turn the flare nut 3 to 4 times with your hand and 

screw in the nut.

 

Torque wrench

Spanner

Flare nut

Union joint

Fig. 9

Coat the flared inner surface 

only with ether oil or ester oil

Fig. 10

Table 2

Piping 

size 

[in. (mm)]

Tightening 

torque 

[lbf·ft. (N·m)]

Dimension for 

processing flare 

A [in. (mm)]

Flare shape 

[in. (mm)]

f

 1/4 

(6.4)

10.4–12.7 

(15.7±1.5)

0.342–0.358

(8.9±0.2)

90°±2°

A

45°±2°

R0.016-0.031

(0.4-0.8)

f

 3/8 

(9.5)

24.1–29.4

(36.3±3.6)

0.504–0.520

(13.0±0.2)

f

 1/2 

(12.7)

36.5–44.5

(54.9±5.4)

0.638–0.654

(16.4±0.2)

f

 5/8 

(15.9)

45.6–55.6

(68.6±6.8)

0.760–0.776

(19.5±0.2)

 CAUTION

Do not have oil adhere to the screw fixing part of resin 

parts.

If oil adheres, it may weaken the strength of screwed part.

Do not tighten flare nuts too tight.

If a flare nut cracks, the refrigerant may leak.

• 

If there is no torque wrench, use Table 3 as a rule of 
thumb. 

When tightening a flare nut with a spanner harder and 

harder, there is a point where the tightening torque sud-
denly increases. 
From that position, tighten the nut additionally at the 
angle shown in Table 3. 

After the work is finished, check securely that there is no 

gas leak. 
If the nut is not tightened as instructed, it may cause 
slow refrigerant leak and result in malfunction (such as 
does not cool or heat).

Table 3

Piping size 

[in. (mm)]

Tightening 

angle

Recommended arm length of 

tool used

f

 1/4 (6.4)

60°–90°

Approx. 6 in. (150 mm)

f

 3/8 (9.5)

60°–90°

Approx. 8 in. (200 mm)

f

 1/2 (12.7)

30°–60°

Approx. 10 in. (250 mm)

f

 5/8 (15.9)

30°–60°

Approx. 12 in. (300 mm)

 CAUTION

Insulation of field piping must be carried out up to the 

connection inside the casing.

If the piping is exposed to the atmosphere, it may cause 

sweating, burn due to touching the piping, electric shocks 

or a fire due to the wiring touching the piping.

01_EN_3P184443-13Z.indd   8

2/15/2018   9:15:27

Summary of Contents for FXSQ05TAVJU

Page 1: ...TAVJU FXSQ36TAVJU FXSQ07TAVJU FXSQ18TAVJU FXSQ48TAVJU FXSQ09TAVJU FXSQ24TAVJU FXSQ54TAVJU FXSQ12TAVJU FXSQ30TAVJU INSTALLATION MANUAL CAREFULLY READ THESE INSTRUCTIONS BEFORE INSTALLATION KEEP THIS MA...

Page 2: ...llation ventilate the area immediately Refrigerant gas may produce toxic gas if it comes in contact with fire Exposure to this gas could cause severe injury or death After completing the installation...

Page 3: ...contain any chlorine does not destroy the ozone layer and does not reduce the earth s protection again harmful ultraviolet radiation R410A can contribute to the greenhouse effect if it is released Th...

Page 4: ...Joint insulating material 6 Sealing material 7 Sealing material 8 Clamp Quantity 1 each 1 sheet 2 sheets 8 pcs Shape Thin 4 For liquid piping Thick 5 For gas piping Large Dark gray Medium Dark gray Na...

Page 5: ...ote controller connected to the master unit if the system is in simultaneous multi operation Have you explained failure examples of 3 SELECTION OF INSTALLATION LOCATION Points of the operation explana...

Page 6: ...oom where an elec tronic lighting type inverter or rapid start type fluorescent lamp is installed 2 Use hanging bolts for installation Investigate if the installation place can withstand the weight of...

Page 7: ...e instal lation location and work on the refrigerant piping drain piping remote controller wiring unless a wireless re mote controller is used and wiring between the indoor and outdoor units to the pi...

Page 8: ...heet to pre vent weld spatter and other foreign materials from entering the indoor unit and damaging the resin drain pan If holes or cracks are generated in the resin drain pan water can leak 2 Adjust...

Page 9: ...When making a flare connection coat the flared inner surface only with ether oil or ester oil Refer to Fig 10 Then turn the flare nut 3 to 4 times with your hand and screw in the nut Torque wrench Sp...

Page 10: ...ing beginning at the base Fig 11 Before brazing refrigerant piping have nitrogen flow through the refrigerant piping and substitute air with nitrogen NOTE 1 Refer to Fig 12 Then carry out brazing NOTE...

Page 11: ...not deflect Refer to Fig 13 Make sure to use the attached drain hose 2 and the metal clamp 1 Insert the drain hose 2 into the drain socket up to the point where the socket diameter becomes larger Put...

Page 12: ...rain pump stops and generate abnormal sound Fig 16 CAUTION To avoid the attached drain hose 2 getting excessive force do not bend nor twist it It may cause water leakage As for drain piping connection...

Page 13: ...he connectors may not come off 3 Gradually pour 1 4 gal 1 of water from the air out let on the left side of the drain socket into the drain pan giving caution to avoid splashing water on the electric...

Page 14: ...ed with the unit Insulation material eld supply Air inlet Air outlet Screws for duct anges 3 accessory Screws for duct anges 3 accessory Flange on air outlet side provided with the unit Fig 20 CAUTION...

Page 15: ...m Outdoor unit Branch Selector unit Max 3 280 ft 1 000 m Branch Selector unit Indoor unit Max 3 280 ft 1 000 m Indoor unit Indoor unit Max 3 280 ft 1 000 m NOTE 1 Vinyl cord with sheath or cable Insu...

Page 16: ...fixture if you have difficulty in performing this step Screws 2 points Conduit mounting plate 12 Hook Fig 24 4 3 Connect the wiring into the control box through the wiring intake beside the control b...

Page 17: ...T P Remote controller Remote controller Remote controller L1 L2 option option option L1 L2 L1 L2 No 2 system When carrying out group control or 2 remote controller control Outdoor unit Note There is n...

Page 18: ...t A Wiring specification Sheathed vinyl cord or 2 core cable Wiring size AWG 18 16 0 75 1 25 mm2 Wiring length Max 328 ft 100 m External contact spec Contact that can make and break the min load of DC...

Page 19: ...be OFF and the indoor unit will come to a stop Table 7 Mode No FIRST CODE No Setting content SECOND CODE No 01 02 03 11 21 7 Air volume adjust ment OFF Air volume adjust ment completion Air volume ad...

Page 20: ...e 11 Remote controller indication Details Though the central ized control is not carried out the indication turns on The terminals T1 T2 for FORCED OFF on the indoor unit trans mission terminal block...

Page 21: ...1804 HT 3P184443 13Z EM17A015A 5151 San Felipe Suite 500 Houston TX 77056...

Reviews: