background image

19

English

Table 9

Setting

Mode 

No.

FIRST 

CODE No.

SECOND 

CODE No.

Fan speed during 

cooling  

thermostat OFF

LL  

(Extra low)

12 (22)

6

01

Setting

02

Fan speed during 

heating  

thermostat OFF

LL  

(Extra low)

12 (22)

3

01

Setting

02

10-4 SETTING FILTER SIGN

• 

A message to inform the air filter cleaning time will be indi

-

cated on the remote controller.

• 

Set the SECOND CODE No. shown in the Table 10 accord-
ing to the amount of dust or pollution in the room.

• 

The periodical filter cleaning time can be shortened de

-

pending on the environment.

Table 10

Dust level

Hours until 

indication

Mode 

No.

FIRST 

CODE No.

SECOND 

CODE No.

Normal

Approx. 

 

2500 hrs

10 (20)

0

01

More  

contaminated

Approx. 

 

1250 hrs

02

With indication

3

01

No indication*

02

* Use “No indication” setting when cleaning indication is not 

necessary such as the case of periodical clean ing being 
carried out.

11. TEST OPERATION

• 

After cleaning the indoor unit inside, carry out test operation 
according to installation manual attached to the outdoor 
unit.

• 

When the remote controller operation lamp flashes, it 

shows that something is abnormal. 
Check the malfunction codes on the remote controller. 
The relation between the malfunction codes and malfunction de-
tails is described in the operation manual attached to the outdoor 
unit. 
Particularly, if the indication is one of those shown in the 
Table 11, it may be an error in the electrical wiring or the 
power supply is disconnected. Therefore, recheck wiring.

Table 11

Remote controller 

indication

Details

Though the central-

ized control is not 

carried out, the 

indication “ 

 ” 

turns on. 

• 

The terminals (T1 · T2) for FORCED OFF 
on the indoor unit trans mission terminal 
block is short circuited.

“U4” turns on

“UH” turns on

• 

The power supply to the outdoor unit is not 
connected. 

• 

The power supply wiring to the outdoor unit 
is not carried out.

• 

The transmission wiring and the remote 
controller wiring and FORCED OFF wiring 
are connected wrongly.

• 

The transmission wiring is disconnected. 

No indication

• 

The power supply to the indoor unit is not 
connected. 

• 

The power supply wiring to the indoor unit 
is not carried out.

• 

The remote controller wiring and the trans-
mission wiring and FORCED OFF wiring 
are connected wrongly.

• 

The remote controller wiring is discon-
nected.

 CAUTION

After test operation is completed, check the items men-
tioned in 

2. BEFORE INSTALLATION (2) Items to be 

checked at delivery

 on page 4.

If the interior finish work is not completed when the test 
operation is finished, for protection of the air con ditioner, 

ask the customer not operate the air conditioner until the 

interior finish work is completed.

 

If the air conditioner is operated, the inside of the indoor 
units may be polluted by substances generated from the 

coating and adhesives used for the interior finish work 

and cause water splash and leakage.

 To the operator carrying out test operation

After test operation is completed, before delivering the 

air conditioner to the customer, confirm that the control 
box lid, the air filter and suction grille are attached.

 

In addition, explain the power supply status (power sup

-

ply ON/OFF) to the customer.

01_EN_3P184443-13Z.indd   19

2/15/2018   9:15:37

Summary of Contents for FXSQ05TAVJU

Page 1: ...TAVJU FXSQ36TAVJU FXSQ07TAVJU FXSQ18TAVJU FXSQ48TAVJU FXSQ09TAVJU FXSQ24TAVJU FXSQ54TAVJU FXSQ12TAVJU FXSQ30TAVJU INSTALLATION MANUAL CAREFULLY READ THESE INSTRUCTIONS BEFORE INSTALLATION KEEP THIS MA...

Page 2: ...llation ventilate the area immediately Refrigerant gas may produce toxic gas if it comes in contact with fire Exposure to this gas could cause severe injury or death After completing the installation...

Page 3: ...contain any chlorine does not destroy the ozone layer and does not reduce the earth s protection again harmful ultraviolet radiation R410A can contribute to the greenhouse effect if it is released Th...

Page 4: ...Joint insulating material 6 Sealing material 7 Sealing material 8 Clamp Quantity 1 each 1 sheet 2 sheets 8 pcs Shape Thin 4 For liquid piping Thick 5 For gas piping Large Dark gray Medium Dark gray Na...

Page 5: ...ote controller connected to the master unit if the system is in simultaneous multi operation Have you explained failure examples of 3 SELECTION OF INSTALLATION LOCATION Points of the operation explana...

Page 6: ...oom where an elec tronic lighting type inverter or rapid start type fluorescent lamp is installed 2 Use hanging bolts for installation Investigate if the installation place can withstand the weight of...

Page 7: ...e instal lation location and work on the refrigerant piping drain piping remote controller wiring unless a wireless re mote controller is used and wiring between the indoor and outdoor units to the pi...

Page 8: ...heet to pre vent weld spatter and other foreign materials from entering the indoor unit and damaging the resin drain pan If holes or cracks are generated in the resin drain pan water can leak 2 Adjust...

Page 9: ...When making a flare connection coat the flared inner surface only with ether oil or ester oil Refer to Fig 10 Then turn the flare nut 3 to 4 times with your hand and screw in the nut Torque wrench Sp...

Page 10: ...ing beginning at the base Fig 11 Before brazing refrigerant piping have nitrogen flow through the refrigerant piping and substitute air with nitrogen NOTE 1 Refer to Fig 12 Then carry out brazing NOTE...

Page 11: ...not deflect Refer to Fig 13 Make sure to use the attached drain hose 2 and the metal clamp 1 Insert the drain hose 2 into the drain socket up to the point where the socket diameter becomes larger Put...

Page 12: ...rain pump stops and generate abnormal sound Fig 16 CAUTION To avoid the attached drain hose 2 getting excessive force do not bend nor twist it It may cause water leakage As for drain piping connection...

Page 13: ...he connectors may not come off 3 Gradually pour 1 4 gal 1 of water from the air out let on the left side of the drain socket into the drain pan giving caution to avoid splashing water on the electric...

Page 14: ...ed with the unit Insulation material eld supply Air inlet Air outlet Screws for duct anges 3 accessory Screws for duct anges 3 accessory Flange on air outlet side provided with the unit Fig 20 CAUTION...

Page 15: ...m Outdoor unit Branch Selector unit Max 3 280 ft 1 000 m Branch Selector unit Indoor unit Max 3 280 ft 1 000 m Indoor unit Indoor unit Max 3 280 ft 1 000 m NOTE 1 Vinyl cord with sheath or cable Insu...

Page 16: ...fixture if you have difficulty in performing this step Screws 2 points Conduit mounting plate 12 Hook Fig 24 4 3 Connect the wiring into the control box through the wiring intake beside the control b...

Page 17: ...T P Remote controller Remote controller Remote controller L1 L2 option option option L1 L2 L1 L2 No 2 system When carrying out group control or 2 remote controller control Outdoor unit Note There is n...

Page 18: ...t A Wiring specification Sheathed vinyl cord or 2 core cable Wiring size AWG 18 16 0 75 1 25 mm2 Wiring length Max 328 ft 100 m External contact spec Contact that can make and break the min load of DC...

Page 19: ...be OFF and the indoor unit will come to a stop Table 7 Mode No FIRST CODE No Setting content SECOND CODE No 01 02 03 11 21 7 Air volume adjust ment OFF Air volume adjust ment completion Air volume ad...

Page 20: ...e 11 Remote controller indication Details Though the central ized control is not carried out the indication turns on The terminals T1 T2 for FORCED OFF on the indoor unit trans mission terminal block...

Page 21: ...1804 HT 3P184443 13Z EM17A015A 5151 San Felipe Suite 500 Houston TX 77056...

Reviews: