9-2 ELECTRICAL CHARACTERISTICS
Table 4
Units
Power
supply
Fan motor
Model
Hz Volts
Voltage
range
MCA MOP
kW
FLA
FXSQ05TAVJU
60
208V-
230V
Max. 253V
Min. 187V
0.8
15
0.078 0.6
FXSQ07TAVJU
0.8
15
0.078 0.6
FXSQ09TAVJU
0.8
15
0.078 0.6
FXSQ12TAVJU
0.8
15
0.078 0.7
FXSQ15TAVJU
1.4
15
0.130 1.2
FXSQ18TAVJU
1.6
15
0.230 1.3
FXSQ24TAVJU
1.8
15
0.230 1.4
FXSQ30TAVJU
1.8
15
0.230 1.5
FXSQ36TAVJU
2.5
15
0.300 2.0
FXSQ48TAVJU
2.8
15
0.300 2.0
FXSQ54TAVJU
3.3
15
0.350 2.6
MCA: Min. Circuit Amps (A) ; MOP: Max. Overcurrent Protective Device (A)
kW: Fan Motor Rated Output (kW) ; FLA: Full Load Amps (A)
9-3 SPECIFICATION FOR FIELD SUPPLY FUSES
AND WIRING
Table 5
Model
Power supply wiring
Remote controller wiring
Transmission wiring
MOP
Size
Wiring
Size
FXSQ05TAVJU
15A
Wiring size
and length
must comply
with local
codes.
2-conductor,
stranded
nonshielded
copper cable
PVC/vinyl
jacket
(NOTE 2)
AWG18-16
(0.75-
1.25 mm
2
)
FXSQ07TAVJU
FXSQ09TAVJU
FXSQ12TAVJU
FXSQ15TAVJU
FXSQ18TAVJU
FXSQ24TAVJU
FXSQ30TAVJU
FXSQ36TAVJU
FXSQ48TAVJU
FXSQ54TAVJU
The lengths of remote controller wiring and transmission
wiring are as follows:
(1) Remote controller wiring (indoor unit - remote controller)
..............................................................
Max. 1,640 ft. (500 m)
(2)
Transmission wirings ... Total wiring length 6,560 ft. (2,000 m)
•
Outdoor unit - Indoor unit ........
Max. 3,280 ft. (1,000 m)
•
Outdoor unit - Branch Selector unit ...
Max. 3,280 ft. (1,000 m)
•
Branch Selector unit - Indoor unit .....
Max. 3,280 ft. (1,000 m)
•
Indoor unit - Indoor unit ..........
Max. 3,280 ft. (1,000 m)
NOTE
1.
Vinyl cord with sheath or cable (Insulated thickness :
1/16 in. (1 mm) or more)
9-4 WIRING CONNECTION METHOD
CAUTION FOR WIRING
•
For connection to the terminal block, use ring type crimp
style terminals with insulation sleeve or insulate the wirings
properly.
Insulation sleeve
Ring type crimp
style terminals
Wiring
Fig. 21
•
Connect the terminal as shown in Fig. 22.
•
Do not carry out soldering finish when stranded wires are
used. (Otherwise, the loosening of wires may result in
abnormal heat radiation.)
Use wires the same in size
(if the air conditioner is
in simultaneous multi operation)
Fig. 22
(Abnormal heating may occur if the wirings are not tight-
ened securely.)
•
Use the required wirings, connect them securely and fix
these wirings securely so that external force may not apply
to the terminals.
•
Use a proper screw driver for tightening the terminal
screws.
If an improper screw driver is used, it may damage the
screw head and a proper tightening cannot be car ried out.
•
If a terminal is over tightened, it may be damaged.
Refer to the table shown below for tightening torque of
terminals.
Table 6
Tightening torque
[lbf·ft. (N·m)]
Terminal for remote controller and
transmission wirings
0.65 ± 0.07
(0.88 ± 0.08)
Terminal for power supply
0.965 ± 0.095
(1.31 ± 0.13)
Ground terminal
•
Do not carry out soldering finish when stranded wirings
are used.