12

English

(2) 

After piping is finished, check if the drain flows 

smoothly.

[When the electric wiring work is finished]

• 

Gradually pour 1/4 gal. (1  ) of water from the inspec-
tion hatch at the bottom of the drain socket on the 
left side of the drain socket into the drain pan giving 
caution to avoid splashing water on the electric com-

ponents such as drain pump and confirm drainage by 

operating the indoor unit under cooling mode accord-
ing to 

10. FIELD SETTING

(Refer to Fig. 18)

Control box

Drain socket

Filling port

Drain pan

Drain socket 

(with rubber cap)

Plastic container 

for pouring water

Drain pump 

position

Terminal block 

for wiring between 

the indoor and 

outdoor units

Control box lid 

Air outlet

Inspection 

window

Screw

[Method of adding water]

Fig. 18

[When the electric wiring work is not finished]

• 

The electric wiring works (including grounding) must 

be carried out by a qualified electrician.

• 

If a qualified person is not present, after the electric 
wiring work is finished, check the drainage accord ing 
to the method specified in 

[When the electric wiring 

work is finished]

.

1. 

Open the control box lid and connect the single 

phase 208/230 V power supply to the terminal (L1, 
L2) on the terminal block (X1M). 
Connect the ground wiring to the ground terminal.

2. 

Make sure the control box lid is closed before turn

-

ing on the power supply.

• 

Throughout the whole process, carry out the 
work giving caution to the wiring around the con-

trol box so that the connectors may not come off.

3. 

Gradually pour 1/4 gal. (1  ) of water from the air out-
let on the left side of the drain socket into the drain 
pan giving caution to avoid splashing water on the 
electric components such as drain pump.  

(Refer to Fig. 18)

4. 

When the power supply is turned on, the drain pump 
will operate. Drainage can be checked at the trans-
parent part of the drain socket.
(The drain pump will automatically stop after 10 
minutes.)

The drainage of water can be confirmed with water 

level change in the drain pan through the access 
window.

• 

Do not connect the drain piping directly to the 
sewage that gives off ammonia odor. 
The ammonia in the sewage may go through the 

drain piping and corrode the heat exchanger of 

the indoor unit.

• 

Do not apply external force to the float switch. (It 

may result in malfunction)

• 

Do not touch the drain pump. 
Touching the drain pump may cause electric 
shocks.

5. 

Turn off the power supply after checking drainage, 
and remove the power supply wiring.

6. 

Attach the control box lid as before.

(3)  Sweating may occur and result in water leakage. 

Therefore, make sure to insulate the following 2 

locations (drain piping that laid indoors and drain 

sockets).

• 

Use the provided sealing material (Large) (6), and 
perform the thermal insulation of the metal clamp (1) 
and drain hose (2) after checking the drainage of water. 

(Refer to Fig. 19)

Start wrapping from where the 

metal clamp (1) is tightened.

Wrap the sealing material (Large) (6) 

so that the metal clamp (1) end side 

may be doubled.

Metal clamp (1)

(accessory)

Drain hose (2)

(accessory)

Sealing material (Large) (6) 

(accessory)

Sealing material - Large 
(6) (accessory)

No clearance is 
allowed.

Fig. 19

01_EN_3P184443-13Z.indd   12

2/15/2018   9:15:29

Summary of Contents for FXSQ05TAVJU

Page 1: ...TAVJU FXSQ36TAVJU FXSQ07TAVJU FXSQ18TAVJU FXSQ48TAVJU FXSQ09TAVJU FXSQ24TAVJU FXSQ54TAVJU FXSQ12TAVJU FXSQ30TAVJU INSTALLATION MANUAL CAREFULLY READ THESE INSTRUCTIONS BEFORE INSTALLATION KEEP THIS MA...

Page 2: ...llation ventilate the area immediately Refrigerant gas may produce toxic gas if it comes in contact with fire Exposure to this gas could cause severe injury or death After completing the installation...

Page 3: ...contain any chlorine does not destroy the ozone layer and does not reduce the earth s protection again harmful ultraviolet radiation R410A can contribute to the greenhouse effect if it is released Th...

Page 4: ...Joint insulating material 6 Sealing material 7 Sealing material 8 Clamp Quantity 1 each 1 sheet 2 sheets 8 pcs Shape Thin 4 For liquid piping Thick 5 For gas piping Large Dark gray Medium Dark gray Na...

Page 5: ...ote controller connected to the master unit if the system is in simultaneous multi operation Have you explained failure examples of 3 SELECTION OF INSTALLATION LOCATION Points of the operation explana...

Page 6: ...oom where an elec tronic lighting type inverter or rapid start type fluorescent lamp is installed 2 Use hanging bolts for installation Investigate if the installation place can withstand the weight of...

Page 7: ...e instal lation location and work on the refrigerant piping drain piping remote controller wiring unless a wireless re mote controller is used and wiring between the indoor and outdoor units to the pi...

Page 8: ...heet to pre vent weld spatter and other foreign materials from entering the indoor unit and damaging the resin drain pan If holes or cracks are generated in the resin drain pan water can leak 2 Adjust...

Page 9: ...When making a flare connection coat the flared inner surface only with ether oil or ester oil Refer to Fig 10 Then turn the flare nut 3 to 4 times with your hand and screw in the nut Torque wrench Sp...

Page 10: ...ing beginning at the base Fig 11 Before brazing refrigerant piping have nitrogen flow through the refrigerant piping and substitute air with nitrogen NOTE 1 Refer to Fig 12 Then carry out brazing NOTE...

Page 11: ...not deflect Refer to Fig 13 Make sure to use the attached drain hose 2 and the metal clamp 1 Insert the drain hose 2 into the drain socket up to the point where the socket diameter becomes larger Put...

Page 12: ...rain pump stops and generate abnormal sound Fig 16 CAUTION To avoid the attached drain hose 2 getting excessive force do not bend nor twist it It may cause water leakage As for drain piping connection...

Page 13: ...he connectors may not come off 3 Gradually pour 1 4 gal 1 of water from the air out let on the left side of the drain socket into the drain pan giving caution to avoid splashing water on the electric...

Page 14: ...ed with the unit Insulation material eld supply Air inlet Air outlet Screws for duct anges 3 accessory Screws for duct anges 3 accessory Flange on air outlet side provided with the unit Fig 20 CAUTION...

Page 15: ...m Outdoor unit Branch Selector unit Max 3 280 ft 1 000 m Branch Selector unit Indoor unit Max 3 280 ft 1 000 m Indoor unit Indoor unit Max 3 280 ft 1 000 m NOTE 1 Vinyl cord with sheath or cable Insu...

Page 16: ...fixture if you have difficulty in performing this step Screws 2 points Conduit mounting plate 12 Hook Fig 24 4 3 Connect the wiring into the control box through the wiring intake beside the control b...

Page 17: ...T P Remote controller Remote controller Remote controller L1 L2 option option option L1 L2 L1 L2 No 2 system When carrying out group control or 2 remote controller control Outdoor unit Note There is n...

Page 18: ...t A Wiring specification Sheathed vinyl cord or 2 core cable Wiring size AWG 18 16 0 75 1 25 mm2 Wiring length Max 328 ft 100 m External contact spec Contact that can make and break the min load of DC...

Page 19: ...be OFF and the indoor unit will come to a stop Table 7 Mode No FIRST CODE No Setting content SECOND CODE No 01 02 03 11 21 7 Air volume adjust ment OFF Air volume adjust ment completion Air volume ad...

Page 20: ...e 11 Remote controller indication Details Though the central ized control is not carried out the indication turns on The terminals T1 T2 for FORCED OFF on the indoor unit trans mission terminal block...