background image

9

English

• 

After leak test, referring to 

Fig. 11

, insulate both the 

gas and liquid piping connection with the attached joint 
insulating material (4) and (5) to prevent the pipings from 

getting exposed.

 

Then, tighten both the ends of insulating material with 
the clamp (8).

• 

Wrap the sealing material (Medium) (7) around the joint 

insulating material (4) and (5) (flare nut section), both the 

gas and liquid piping.

• 

Make sure to bring the seam of joint insulating material 
(4) and (5) to the top.

Joint insulating 

material (4)

(accessory)

Gas piping

Liquid piping

Liquid piping insulating method

Indoor unit

Indoor unit

Clamp (8)
(accessory)

Sealing 

material (7) 

Medium
(accessory)

Clamp (8) 
(accessory)

Piping 

insulating 

material

(field supply)

Gas piping insulating method

Joint insulating 

material (5) 

(accessory)

Piping insulating 

material (main unit)

Bring the 

seam 

to the top.

Flare nut 

connection

Piping 

insulating 

material 

(field supply)

Do not leave 

clearance.

Flare nut 

connection

Bring the 

seam 

to the top.

Do not leave 

clearance.

Piping insulating 

material (main unit)

Sealing material

(7) Medium
(accessory)

Wind around the 

piping until top of the 

flare nut connection, 

beginning at the base.

Do not expose the 

piping in order to 

prevent the vapor 

condensation.

Tighten the portion 

where overlapped by 

the piping insulating 

material.

Tighten the portion 

where overlapped by 

the piping insulating 

material.

Do not expose the 

piping in order to 

prevent the vapor 

condensation.

Wind around the 

piping, beginning 

at the base.

Fig. 11

• 

Before brazing refrigerant piping, have nitrogen flow 

through the refrigerant piping and substitute air with 
nitrogen (NOTE 1) 

(Refer to Fig. 12)

. Then, carry out 

brazing (NOTE 2). 

After all the brazing works are finished, carry out flare 

connection with the indoor unit. 

(Refer to Fig. 11)

Pressure reducing valve

Nitrogen

Taping

Stop valve

Brazing place

Nitrogen

Refrigerant piping

Fig. 12

NOTE 

1. 

The proper pressure for having nitrogen flow through 
the piping is approximately 2.9 psi (0.02 MPa) , a pres

-

sure that makes one feel like slight breeze and can be 
obtained through a pressure reducing valve.

2. 

Do not use flux when brazing refrigerant piping.

 

Use phosphor copper brazing filler metal (BCuP-2, 
B-Cu93P-710/795) that does not require flux.

 

(If chlorinated flux is used, the piping will be corroded 
and, in addition if fluorine is contained, the refrig erant 

oil will be deteriorated and the refrigerant circuit will be 
affected badly.)

3. 

When carrying out air tight test of refrigerant piping 
and the indoor unit after the installation of indoor unit is 

finished, confirm the connecting outdoor unit installation 

manual for test pressure. 
Refer to also the outdoor unit installation manual or tech-
nical document for refrigerant piping.

4. 

In case of refrigerant shortage due to forgetting addition-
al refrigerant charge etc., it will result in malfunc tion such 
as does not cool or does not heat. 
Refer to the outdoor unit installation manual or technical 
document for refrigerant piping.

 CAUTION

Do not use antioxidant when brazing piping.

It may result in malfunction of components and clogging of 
piping due to residue.

01_EN_3P184443-13Z.indd   9

2/15/2018   9:15:27

Summary of Contents for FXSQ05TAVJU

Page 1: ...TAVJU FXSQ36TAVJU FXSQ07TAVJU FXSQ18TAVJU FXSQ48TAVJU FXSQ09TAVJU FXSQ24TAVJU FXSQ54TAVJU FXSQ12TAVJU FXSQ30TAVJU INSTALLATION MANUAL CAREFULLY READ THESE INSTRUCTIONS BEFORE INSTALLATION KEEP THIS MA...

Page 2: ...llation ventilate the area immediately Refrigerant gas may produce toxic gas if it comes in contact with fire Exposure to this gas could cause severe injury or death After completing the installation...

Page 3: ...contain any chlorine does not destroy the ozone layer and does not reduce the earth s protection again harmful ultraviolet radiation R410A can contribute to the greenhouse effect if it is released Th...

Page 4: ...Joint insulating material 6 Sealing material 7 Sealing material 8 Clamp Quantity 1 each 1 sheet 2 sheets 8 pcs Shape Thin 4 For liquid piping Thick 5 For gas piping Large Dark gray Medium Dark gray Na...

Page 5: ...ote controller connected to the master unit if the system is in simultaneous multi operation Have you explained failure examples of 3 SELECTION OF INSTALLATION LOCATION Points of the operation explana...

Page 6: ...oom where an elec tronic lighting type inverter or rapid start type fluorescent lamp is installed 2 Use hanging bolts for installation Investigate if the installation place can withstand the weight of...

Page 7: ...e instal lation location and work on the refrigerant piping drain piping remote controller wiring unless a wireless re mote controller is used and wiring between the indoor and outdoor units to the pi...

Page 8: ...heet to pre vent weld spatter and other foreign materials from entering the indoor unit and damaging the resin drain pan If holes or cracks are generated in the resin drain pan water can leak 2 Adjust...

Page 9: ...When making a flare connection coat the flared inner surface only with ether oil or ester oil Refer to Fig 10 Then turn the flare nut 3 to 4 times with your hand and screw in the nut Torque wrench Sp...

Page 10: ...ing beginning at the base Fig 11 Before brazing refrigerant piping have nitrogen flow through the refrigerant piping and substitute air with nitrogen NOTE 1 Refer to Fig 12 Then carry out brazing NOTE...

Page 11: ...not deflect Refer to Fig 13 Make sure to use the attached drain hose 2 and the metal clamp 1 Insert the drain hose 2 into the drain socket up to the point where the socket diameter becomes larger Put...

Page 12: ...rain pump stops and generate abnormal sound Fig 16 CAUTION To avoid the attached drain hose 2 getting excessive force do not bend nor twist it It may cause water leakage As for drain piping connection...

Page 13: ...he connectors may not come off 3 Gradually pour 1 4 gal 1 of water from the air out let on the left side of the drain socket into the drain pan giving caution to avoid splashing water on the electric...

Page 14: ...ed with the unit Insulation material eld supply Air inlet Air outlet Screws for duct anges 3 accessory Screws for duct anges 3 accessory Flange on air outlet side provided with the unit Fig 20 CAUTION...

Page 15: ...m Outdoor unit Branch Selector unit Max 3 280 ft 1 000 m Branch Selector unit Indoor unit Max 3 280 ft 1 000 m Indoor unit Indoor unit Max 3 280 ft 1 000 m NOTE 1 Vinyl cord with sheath or cable Insu...

Page 16: ...fixture if you have difficulty in performing this step Screws 2 points Conduit mounting plate 12 Hook Fig 24 4 3 Connect the wiring into the control box through the wiring intake beside the control b...

Page 17: ...T P Remote controller Remote controller Remote controller L1 L2 option option option L1 L2 L1 L2 No 2 system When carrying out group control or 2 remote controller control Outdoor unit Note There is n...

Page 18: ...t A Wiring specification Sheathed vinyl cord or 2 core cable Wiring size AWG 18 16 0 75 1 25 mm2 Wiring length Max 328 ft 100 m External contact spec Contact that can make and break the min load of DC...

Page 19: ...be OFF and the indoor unit will come to a stop Table 7 Mode No FIRST CODE No Setting content SECOND CODE No 01 02 03 11 21 7 Air volume adjust ment OFF Air volume adjust ment completion Air volume ad...

Page 20: ...e 11 Remote controller indication Details Though the central ized control is not carried out the indication turns on The terminals T1 T2 for FORCED OFF on the indoor unit trans mission terminal block...

Page 21: ...1804 HT 3P184443 13Z EM17A015A 5151 San Felipe Suite 500 Houston TX 77056...

Reviews: