background image

English

9

CAUTION

• The drain piping will be clogged with water and water leakage 

may result if the water is accumulated in the drain piping.

• Conduct drain-up piping work if the gradient is insuffi-

cient.

• Attach a support bracket at 3.3 to 4.9 ft intervals for 

the prevention of piping deflection.

• Be sure to use the drain hose (2) and metal clamp (1).

Insert the drain hose (2) deep into the base of the 
drain socket, and securely fasten the metal clamp (1) 
within the taped part on the insertion front end of the 
hose.

Be sure to fasten the screw of the metal clamp (1) until 
the margin of the screw thread decreases to 3/16 in. or 
less.

NOTE

Be sure to follow the instructions as below.

• Do not connect the drain piping directly to a sewer that 

smells of ammonia.
The ammonia in the sewer may reach through the drain 
piping and corrode the heat exchanger of the indoor unit.

• Do not bend or twist the provided drain hose (2) in order 

not to impose excessive force on the hose. (Doing so 
may result in water leakage.)

• Take the procedure shown in the following illustration to 

perform concentrated drain piping.

• Select the diameter of the concentrated drain piping to 

suit the capacity of equipment connecting to the concen-
trated drain piping (see the equipment design sheet).

(2) Check the smooth draining of the piping on completion of 

the installation of the piping.

[Before electrical work]

CAUTION

• A licensed electrical engineering technician must con-

duct electrical wiring work (including grounding work).

• If no licensed electrical engineering technician is avail-

able, take steps 3 and 4 after the test operation of the air 
conditioner is finished.

1. Remove the control box lid, 

and connect the single-

phase electric wires to terminals L1 and L2 of the ter-
minal block and the ground wiring to the ground ter-
minal

.

Perform wiring according to 

10-1. CONNECTING 

POWER SUPPLY, GROUND, REMOTE CONTROLLER, 
AND TRANSMISSION WIRING

 in 

10. WIRING EXAM-

PLE AND HOW TO SET THE REMOTE CONTROLLER

.

CAUTION

• In order not to impose tension on the wire connections, per-

form clamping securely with the provided clamp (8) specified 
in 3 in 

10-1. CONNECTING POWER SUPPLY, GROUND, 

REMOTE CONTROLLER, AND TRANSMISSION WIRING

.

2. Check that the control box lid is closed before turning the 

air conditioner ON.

3. Provide 

approximately 61 in

3

 of water

 gradually into the 

drain pan through the water inlet on the bottom of the drain 
socket or the outlet. Make sure that the water is not spilled 
onto the drain pump.

4. The drain pump will operate with the power turned ON. 

Check that the pump drains water smoothly. (The drain 
pump will stop automatically in 10 minutes.)

3.3 - 4.9 ft

Support bracket

Downward slope of at least 1/100

(accessory)

(accessory)

Metal clamp (1)

Tape

Drain hose (2)

Concentrated drain piping

The drain piping will be clogged with water 
and water leakage may result if the water is 
accumulated in the drain piping.

Maintain 

a downward slope of at least 

1/100

 so that no air bank will be formed.

18 - 3/8 in.

Ceiling slab

3.3 - 4.9 ft

12 in. max.

28 in. max.

Support bracket

Drain-up piping 
(field supply)

Adjustable 
(18-3/8 in. max.)

Metal clamp (1) (accessory)

Drain hose (2) (accessory)

Drain hose (2) (accessory)

Horizontal or 
upward slope

If there is an air bank, noise may be generated 
as a result of a water backflow when the drain 
pump comes to a stop.

Locate the drain hose horizontally 
or with a little upward gradient.

Summary of Contents for FXMQ07PVJU

Page 1: ...12PVJU FXMQ30PVJU READ THESE INSTRUCTIONS CAREFULLY BEFORE INSTALLATION KEEP THIS MANUAL IN A HANDY PLACE FOR FUTURE REFERENCE LIRE SOIGNEUSEMENT CES INSTRUCTIONS AVANT L INSTALLATION CONSERVER CE MAN...

Page 2: ...efrigerant gas may produce toxic gas if it comes in contact with fire Exposure to this gas could cause severe injury or death After completing the installation work check that the re frigerant gas doe...

Page 3: ...iation R 410A can contribute to the greenhouse effect if it is released Therefore take proper measures to check for the tightness of the refrigerant piping installation Read the chapter Refrigerant Pi...

Page 4: ...can generate electromagnetic waves Control system may malfunction Where the air contains high levels of salt such as that near the ocean and where voltage fluctuates greatly such as that in factories...

Page 5: ...possi ble within the allowable limit Refer to the installation manual of the outdoor unit Items to be checked If not properly done what is likely to occur Check Are the indoor and outdoor unit fixed...

Page 6: ...4 17 3 4 for the control box and inspection hatch 2 for the lower part of the product see axial direction view A 1 Refer to Fig 2 3 3 Inspection hatch 3 for the lower part of the product and the lower...

Page 7: ...INDOOR UNIT INSTALLATION It may be easier to install accessories sold separately before installing the indoor unit Refer to the installation manuals provided to the accessories as well Be sure to use...

Page 8: ...uring of the piping with pinching or taping of the piping in order to prevent the intrusion of dirt dust and moisture into the piping CAUTION Be sure to use the specified type of refrigerant for the r...

Page 9: ...on Furthermore if it contains fluorine the flux will deteriorate refrigerant oil As for the branching of the refrigerant piping or refrigerant refer to the installation manual provided with the outdoo...

Page 10: ...est operation of the air conditioner is finished 1 Remove the control box lid and connect the single phase electric wires to terminals L1 and L2 of the ter minal block and the ground wiring to the gro...

Page 11: ...sputter will not come in contact with the drain pan for the filter If the metal duct pass through a metal lath wire lath or metal plate of a wooden structure separate the duct and wall elec trically B...

Page 12: ...s used Telephone ground wires or lightning rods might cause abnormally high electric potential in the ground during lighting storms 9 2 ELECTRICAL CHARACTERISTICS MCA Min Circuit Amps A MFA Max Fuse A...

Page 13: ...included insulation tube and secure it with the included clamp When use the insulation tube Cut off the insulation tube as need length WARNING Trim and lay the wiring neatly and attach the control bo...

Page 14: ...rupter is imperative for the prevention of electric shocks and fire accidents No 1 system When using 1 remote controller for 1 indoor unit No 2 system For group control or use with 2 remote con trolle...

Page 15: ...3 How to select FORCED OFF and ON OFF OPERATION Turn the power on and then use the remote controller to select operation 10 5 CENTRALIZED CONTROL For centralized control it is necessary to designate...

Page 16: ...the air conditioner go to FIELD SET MODE select MODE NO 21 11 in the case of group set tings set the setting FIRST CODE NO to 7 and set the setting SECOND CODE NO to 03 Return to normal mode after th...

Page 17: ...peration of the air conditioner explain the customer not to operate the air conditioner until the interior finish work is com pleted for the protection of the air conditioner Otherwise substances that...

Page 18: ...1645 Wallace Drive Suite 110 Carrollton TX 75006 info daikinac com www daikinac com 0912 FS 3PN06583 9P EM09A025...

Reviews: