background image

English

15

Make sure the control box lids are closed on the indoor and 
outdoor units.
Field setting must be made from the remote controller in 
accordance with the installation condition.

• Setting can be made by changing the “MODE NO.”, “FIRST 

CODE NO.”, and “SECOND CODE NO.”.

• For setting and operation, refer to the “FIELD SETTING” in 

the installation manual of the remote controller.

• Set the remote controller to the “FIELD SET MODE”. For 

details, refer to the “HOW TO SET IN THE FIELD”, in the 
remote controller manual. 

• When in the “FIELD SET MODE”, select “MODE NO.

12” , then set the “FIRST CODE NO.” to “1”. Then set 
“SECOND CODE NO.” to “01” for FORCED OFF and “02” 
for ON/OFF OPERATION. (FORCED OFF at factory set)

With Wireless Remote Controller Used

Set the wireless remote controller address before using the 
wireless remote controller.
For the setting method of the address, refer to the operation 
manual provided with the wireless remote controller.

NOTE

• A “MODE NO.” is set on a group basis. To make a mode set-

ting on a room unit basis or check the setting made, however, 
set the corresponding mode number in the parentheses.

1. Settings for Optional Accessories

• In the case of connecting optional accessories, refer to 

the operation manuals provided with the optional acces-
sories and make necessary settings.

2. External Static Pressure Settings

Make settings in either method (a) or method (b) as 
explained below. (FXMQ48PVJU cannot be selected 
method (a). Please select method (b).)
(a) Use the airflow auto adjustment function to make settings.

Airflow auto adjustment: The volume of blow-off air is 
automatically adjusted to the rated quantity.
(1) Check that power supply wiring to the air conditioner 

is completed along with duct installation. If a closing 
damper is installed in the air-conditioning system, 
make sure that the closing damper is opened. Fur-
thermore, check that the air filter as a field supply is 
attached to the air passage on the suction side.

(2) If there are a number of air outlets and inlets, adjust the 

throttles so that the airflow rate of each air outlet and 
inlet will coincide with the designed airflow rate. At that 
time, operate the air conditioner in “fan operation mode”. 
To change the airflow rate, press and set the airflow 
adjustment button of the remote controller to HH, H, or L.

(3) Make settings for airflow automatic adjustment. After 

setting the air conditioner to “fan operation mode”, 
stop the air conditioner, go to “FIELD SET MODE”, 
select “MODE NO. 21” (11 in the case of group set-
tings), set the setting “FIRST CODE NO.” to 7, and set 
the setting “SECOND CODE NO.” to 03. 
Return to normal mode after these settings, and press 
the ON/OFF OPERATION button. Then the operation 
lamp will be lit and the air conditioner will go into fan 
operation for airflow automatic adjustment. Do not 
adjust the throttles of the air outlets or inlets during 
automatic adjustment of the air conditioner. After the 
air conditioner runs approximately one to eight min-
utes, the air conditioner will finish airflow adjustment 
automatically, the operation lamp will be turned OFF, 
and the air conditioner will come to a stop.

Table 3

(4) After the air conditioner stops operating, check with 

“MODE NO. 21” on an indoor unit basis that 02 is set 
for the “SECOND CODE NO.” in Table 3. If the air 
conditioner does not stop operating automatically or 
the “SECOND CODE NO.” is not 02, repeat steps 
from (3). If the outdoor unit is not turned ON, U4 or 
UH as explained in Table 7 will be displayed. This dis-
play is not problematic, because this function is set 
for the indoor unit. Continue setting the function. 
After setting this function, be sure to turn ON the out-
door unit before the test operation of the outdoor unit. 
If any other error is displayed, refer to Table 7 and the 
operation manual provided with the outdoor unit and 
check the defective point.

CAUTION

• If there is any change after airflow adjustment in the ventila-

tion paths (e.g., the duct and air outlet), be sure to make air-
flow auto adjustment again.

• Consult your Daikin representative if there is any change in 

the ventilation paths (e.g., the duct and air outlet) after the test 
operation of the outdoor unit is finished or the air conditioner 
is moved to another place.

(b) Select External Static Pressure with Remote Controller

Check that 01 (OFF) is set for the “SECOND CODE NO.” 
in “MODE NO. 21” for airflow adjustment on an indoor 
unit basis in Table 3. The “SECOND CODE NO.” is set to 
01 (OFF) at factory set. Change the “SECOND CODE 
NO.” as shown in Table 4 according to the external static 
pressure of the duct to be connected.
(1) The “SECOND CODE NO.” is set to 07 (an external 

static pressure of 0.4 inWG) at factory set. (FXMQ18 
· 24 · 30 · 36 · 48PVJU)
The “SECOND CODE NO.” is set to 02 (an external 
static pressure of 0.2 inWG) at factory set. (FXMQ07 
· 09  · 12PVJU)

SETTING

MODE NO.

SECOND 
CODE NO.

FIELD SET 
MODE

FIRST 
CODE NO.

MODE NO.

FIRST CODE NO.

Setting contents

11 (

21

)

7

Airflow 

adjustment

SECOND CODE NO.

01

02

03

OFF

Completion of 

airflow adjustment

Start of airflow 

adjustment

Summary of Contents for FXMQ07PVJU

Page 1: ...12PVJU FXMQ30PVJU READ THESE INSTRUCTIONS CAREFULLY BEFORE INSTALLATION KEEP THIS MANUAL IN A HANDY PLACE FOR FUTURE REFERENCE LIRE SOIGNEUSEMENT CES INSTRUCTIONS AVANT L INSTALLATION CONSERVER CE MAN...

Page 2: ...efrigerant gas may produce toxic gas if it comes in contact with fire Exposure to this gas could cause severe injury or death After completing the installation work check that the re frigerant gas doe...

Page 3: ...iation R 410A can contribute to the greenhouse effect if it is released Therefore take proper measures to check for the tightness of the refrigerant piping installation Read the chapter Refrigerant Pi...

Page 4: ...can generate electromagnetic waves Control system may malfunction Where the air contains high levels of salt such as that near the ocean and where voltage fluctuates greatly such as that in factories...

Page 5: ...possi ble within the allowable limit Refer to the installation manual of the outdoor unit Items to be checked If not properly done what is likely to occur Check Are the indoor and outdoor unit fixed...

Page 6: ...4 17 3 4 for the control box and inspection hatch 2 for the lower part of the product see axial direction view A 1 Refer to Fig 2 3 3 Inspection hatch 3 for the lower part of the product and the lower...

Page 7: ...INDOOR UNIT INSTALLATION It may be easier to install accessories sold separately before installing the indoor unit Refer to the installation manuals provided to the accessories as well Be sure to use...

Page 8: ...uring of the piping with pinching or taping of the piping in order to prevent the intrusion of dirt dust and moisture into the piping CAUTION Be sure to use the specified type of refrigerant for the r...

Page 9: ...on Furthermore if it contains fluorine the flux will deteriorate refrigerant oil As for the branching of the refrigerant piping or refrigerant refer to the installation manual provided with the outdoo...

Page 10: ...est operation of the air conditioner is finished 1 Remove the control box lid and connect the single phase electric wires to terminals L1 and L2 of the ter minal block and the ground wiring to the gro...

Page 11: ...sputter will not come in contact with the drain pan for the filter If the metal duct pass through a metal lath wire lath or metal plate of a wooden structure separate the duct and wall elec trically B...

Page 12: ...s used Telephone ground wires or lightning rods might cause abnormally high electric potential in the ground during lighting storms 9 2 ELECTRICAL CHARACTERISTICS MCA Min Circuit Amps A MFA Max Fuse A...

Page 13: ...included insulation tube and secure it with the included clamp When use the insulation tube Cut off the insulation tube as need length WARNING Trim and lay the wiring neatly and attach the control bo...

Page 14: ...rupter is imperative for the prevention of electric shocks and fire accidents No 1 system When using 1 remote controller for 1 indoor unit No 2 system For group control or use with 2 remote con trolle...

Page 15: ...3 How to select FORCED OFF and ON OFF OPERATION Turn the power on and then use the remote controller to select operation 10 5 CENTRALIZED CONTROL For centralized control it is necessary to designate...

Page 16: ...the air conditioner go to FIELD SET MODE select MODE NO 21 11 in the case of group set tings set the setting FIRST CODE NO to 7 and set the setting SECOND CODE NO to 03 Return to normal mode after th...

Page 17: ...peration of the air conditioner explain the customer not to operate the air conditioner until the interior finish work is com pleted for the protection of the air conditioner Otherwise substances that...

Page 18: ...1645 Wallace Drive Suite 110 Carrollton TX 75006 info daikinac com www daikinac com 0912 FS 3PN06583 9P EM09A025...

Reviews: