background image

English

5

CAUTION

• Install the indoor and outdoor units, power supply wiring and 

connecting wires at least 3.3 ft away from televisions or radios 
in order to prevent image interference or noise.
(Depending on the radio waves, a distance of 3.3 ft may not 
be sufficient enough to eliminate the noise.)

• In the case of the installation of a wireless remote controller, the 

transmission distance of the wireless remote controller may be 
shortened if the room has a fluorescent light of electronic light-
ing type (i.e., an inverter or rapid-start fluorescent light).
Keep the distance between the receiver and the fluorescent 
light as far as possible.

(2) Use hanging bolts to install the indoor unit. Check that the 

place of installation withstands the weight of the indoor unit. 
Secure the hanging bolts with proper beams if necessary.

4.

PREPARATIONS BEFORE INSTALLATION

(1) Check the positional relationship between the ceiling open-

ing hole and the hanging bolt of the unit.

• For the maintenance, inspection, and other servicing 

purposes of the control box and drain pump, prepare one 
of the following service spaces.
1. Inspection hatch 1 (17-3/4 × 17-3/4) for the control 

box and a minimum space of 12 in. for the lower part 
of the product. 

(Refer to Fig. 2-2)

2. Inspection hatch 1 (17-3/4 × 17-3/4) for the control 

box and inspection hatch 2 for the lower part of the 
product (see axial direction view A-1). 

(Refer to Fig. 

2-3)

3. Inspection hatch 3 for the lower part of the product 

and the lower part of the control box (see axial direc-
tion view A-2). 

(Refer to Fig. 2-3)

(length: in.)

Ceiling

Floor surface

• The H1 dimension indicates the 

height of the product.

• Determine the H2 dimension by 

maintaining a downward slope of 
at least 1/100 as specified in 
“7. DRAIN PIPING WORK”.

Min. 1

Min. 12

Min. 18

Min. 99

Min. 28 (service space)

(If no ceiling board is provided.)

*H1=12

*H2=Min. 25

[Required installation place]

The dimensions indicate the 
minimum required space of 
installation.

Fig. 2-1

28

24-13/16

(Hanging bolt pitch)

Inspection hatch 1 
(17-3/4×17-3/4)

Inspection hatch

Control box

Control box

Ceiling

B

C

(Hanging bolt pitch)

Bottom of unit

Air inlet

Air outlet

Hanging bolt (× 4)

*H3=Min. 12

Fig. 2-2

Case 1

(length: in.)

28

28

Inspection hatch

Inspection hatch 1 
(17-3/4×17-3/4)

Inspection 
hatch 2

Inspection hatch 3

(Same as the indoor 
unit size +12 or more)

Control box

Control box

Control box

Inspection hatch

(Ceiling opening)

Ceiling

Axial direction view A-1

Axial direction view A-2

Min. D=B+12

Min. 8

B

*H3=Min. 3/4

07 • 09 • 12 type

22

23-1/8

34

Model

B

C

D

40

40-7/8

52

56

56-5/8

68

18 • 24 • 30 type

36 • 48 type

(length: in.)

A

Fig. 2-3

Case 2, 3

(Same as the 
indoor unit 
size or more)

• Determine the H3 

dimension by maintaining a 
downward slope of at least 
1/100 as specified in 
“7. DRAIN PIPING WORK”.

Summary of Contents for FXMQ07PVJU

Page 1: ...12PVJU FXMQ30PVJU READ THESE INSTRUCTIONS CAREFULLY BEFORE INSTALLATION KEEP THIS MANUAL IN A HANDY PLACE FOR FUTURE REFERENCE LIRE SOIGNEUSEMENT CES INSTRUCTIONS AVANT L INSTALLATION CONSERVER CE MAN...

Page 2: ...efrigerant gas may produce toxic gas if it comes in contact with fire Exposure to this gas could cause severe injury or death After completing the installation work check that the re frigerant gas doe...

Page 3: ...iation R 410A can contribute to the greenhouse effect if it is released Therefore take proper measures to check for the tightness of the refrigerant piping installation Read the chapter Refrigerant Pi...

Page 4: ...can generate electromagnetic waves Control system may malfunction Where the air contains high levels of salt such as that near the ocean and where voltage fluctuates greatly such as that in factories...

Page 5: ...possi ble within the allowable limit Refer to the installation manual of the outdoor unit Items to be checked If not properly done what is likely to occur Check Are the indoor and outdoor unit fixed...

Page 6: ...4 17 3 4 for the control box and inspection hatch 2 for the lower part of the product see axial direction view A 1 Refer to Fig 2 3 3 Inspection hatch 3 for the lower part of the product and the lower...

Page 7: ...INDOOR UNIT INSTALLATION It may be easier to install accessories sold separately before installing the indoor unit Refer to the installation manuals provided to the accessories as well Be sure to use...

Page 8: ...uring of the piping with pinching or taping of the piping in order to prevent the intrusion of dirt dust and moisture into the piping CAUTION Be sure to use the specified type of refrigerant for the r...

Page 9: ...on Furthermore if it contains fluorine the flux will deteriorate refrigerant oil As for the branching of the refrigerant piping or refrigerant refer to the installation manual provided with the outdoo...

Page 10: ...est operation of the air conditioner is finished 1 Remove the control box lid and connect the single phase electric wires to terminals L1 and L2 of the ter minal block and the ground wiring to the gro...

Page 11: ...sputter will not come in contact with the drain pan for the filter If the metal duct pass through a metal lath wire lath or metal plate of a wooden structure separate the duct and wall elec trically B...

Page 12: ...s used Telephone ground wires or lightning rods might cause abnormally high electric potential in the ground during lighting storms 9 2 ELECTRICAL CHARACTERISTICS MCA Min Circuit Amps A MFA Max Fuse A...

Page 13: ...included insulation tube and secure it with the included clamp When use the insulation tube Cut off the insulation tube as need length WARNING Trim and lay the wiring neatly and attach the control bo...

Page 14: ...rupter is imperative for the prevention of electric shocks and fire accidents No 1 system When using 1 remote controller for 1 indoor unit No 2 system For group control or use with 2 remote con trolle...

Page 15: ...3 How to select FORCED OFF and ON OFF OPERATION Turn the power on and then use the remote controller to select operation 10 5 CENTRALIZED CONTROL For centralized control it is necessary to designate...

Page 16: ...the air conditioner go to FIELD SET MODE select MODE NO 21 11 in the case of group set tings set the setting FIRST CODE NO to 7 and set the setting SECOND CODE NO to 03 Return to normal mode after th...

Page 17: ...peration of the air conditioner explain the customer not to operate the air conditioner until the interior finish work is com pleted for the protection of the air conditioner Otherwise substances that...

Page 18: ...1645 Wallace Drive Suite 110 Carrollton TX 75006 info daikinac com www daikinac com 0912 FS 3PN06583 9P EM09A025...

Reviews: