background image

8

English

Table 2

(2) On completion of installation work, 

check that there is no 

gas leakage

.

(3) Refer to the illustration on the right-hand side and be sure to 

perform heat insulation work on the piping joints after gas 
leakage checks. 

(Refer to Fig. 6)

• Use the insulation for fitting (4) and (5) provided to the 

liquid piping and gas piping, respectively, and conduct 
heat insulation work.
(Tighten both edges of the insulation for fitting (4) and (5) 
for each joint with the clamp (8).)

• Make sure that the joint of the insulation for fitting (4) and 

(5) for the joint on the liquid piping and gas piping side 
faces upward.

• Wrap the middle sealing material (7) around the insula-

tion for fitting (4) and (5) for the joint (flare nut part).

CAUTION

• Be sure to perform the heat insulation of the local piping 

up to the piping joint.

If the piping is exposed, dew condensation may result. Fur-
thermore, a burn may be caused if a human body comes in 
contact with the piping.

• Perform nitrogen substituent or apply nitrogen into the 

refrigerant piping (see NOTE 1) in the case of refrigerant 
piping blazing (see NOTE 2). Then perform the flare con-
nection of the indoor unit. 

(Refer to Fig. 7)

CAUTION

• Do not use any antioxidant at the time of piping blazing.

The piping may be clogged with a residual antioxidant and 
parts may malfunction.

NOTE

1. At the time of blazing, set the pressure of nitrogen to 

approximately 2.9 PSI (close to the pressure of a breeze 
coming in contact with the cheek) with a decompression 
valve.

2. Do not use flux at the time of blazing and connecting the 

refrigerant piping. Use a copper phosphorus brazing alloy 
(BCuP-2/BCu 93P-710/795), which does not require flux, 
for blazing.
(Flux has a bad influence on the refrigerant piping. Chlo-
rine-based flux will cause piping corrosion. Furthermore, if 
it contains fluorine, the flux will deteriorate refrigerant oil.)

• As for the branching of the refrigerant piping or refrigerant, 

refer to the installation manual provided with the outdoor unit.

7.

DRAIN PIPING WORK

(1) Conduct drain piping work.

Check that the piping 
ensures proper draining.

• Make sure that the diam-

eter of the piping exclud-
ing the rising part is the 
same as or larger than 
the diameter of the con-
necting pipe (vinyl chloride pipe with an outer diameter 
of 1/4 in. and a nominal inner diameter of 31/32 in.).

• Make sure that the piping is short enough 

with a down-

ward slope of at least 1/100

 and that there is no air 

bank formed. No drain trap is required.

Pipe size

Further tightening angle

Recommended arm length of 

tool

φ 

1/4

60 to 90 degrees

Approx. 5-7/8 in.

φ 

3/8

60 to 90 degrees

Approx. 7-7/8 in.

φ 

1/2

30 to 60 degrees

Approx. 9-13/16 in.

φ 

5/8

30 to 60 degrees

Approx. 11-13/16 in.

Heat insulation procedure for gas piping

Insulation material 
for piping 
(on unit side)

Insulation material 
for piping (field supply)

Make sure that 
the seam faces 
upward.

Clamp (8) 
(accessory)

Gas pipe

Liquid pipe

Flare nut joint

Attached to 
the surface.

Insulation for fitting (5) (accessory)

Middle sealing pad (7) 
(accessory)

Wrap the insulation material 
around the portion from the 
surface of the main unit to the 
upper part of the flare nut joint.

Insulation material 
for piping (field supply)

Wrap the insulation material 
around the portion from the 
surface of the main unit to the 
upper part of the flare nut joint.

Fig. 6

Heat insulation procedure for liquid piping

Insulation material 
for piping 
(on unit side)

Make sure that 
the seam faces 
upward.

Clamp (8) 
(accessory)

Main unit

Flare nut joint

Attached to 
the surface.

Insulation for fitting (4) (accessory)

Middle sealing pad (7) 
(accessory)

Nitrogen

Refrigerant 
piping

Part to be 
brazed 

Taping

Pressurereducing valve

hands 
valve

Nitrogen

Fig. 7

Refrigerant 
piping

Drain socket 

Socket for 
maintenance 
(with rubber cap)

Summary of Contents for FXMQ07PVJU

Page 1: ...12PVJU FXMQ30PVJU READ THESE INSTRUCTIONS CAREFULLY BEFORE INSTALLATION KEEP THIS MANUAL IN A HANDY PLACE FOR FUTURE REFERENCE LIRE SOIGNEUSEMENT CES INSTRUCTIONS AVANT L INSTALLATION CONSERVER CE MAN...

Page 2: ...efrigerant gas may produce toxic gas if it comes in contact with fire Exposure to this gas could cause severe injury or death After completing the installation work check that the re frigerant gas doe...

Page 3: ...iation R 410A can contribute to the greenhouse effect if it is released Therefore take proper measures to check for the tightness of the refrigerant piping installation Read the chapter Refrigerant Pi...

Page 4: ...can generate electromagnetic waves Control system may malfunction Where the air contains high levels of salt such as that near the ocean and where voltage fluctuates greatly such as that in factories...

Page 5: ...possi ble within the allowable limit Refer to the installation manual of the outdoor unit Items to be checked If not properly done what is likely to occur Check Are the indoor and outdoor unit fixed...

Page 6: ...4 17 3 4 for the control box and inspection hatch 2 for the lower part of the product see axial direction view A 1 Refer to Fig 2 3 3 Inspection hatch 3 for the lower part of the product and the lower...

Page 7: ...INDOOR UNIT INSTALLATION It may be easier to install accessories sold separately before installing the indoor unit Refer to the installation manuals provided to the accessories as well Be sure to use...

Page 8: ...uring of the piping with pinching or taping of the piping in order to prevent the intrusion of dirt dust and moisture into the piping CAUTION Be sure to use the specified type of refrigerant for the r...

Page 9: ...on Furthermore if it contains fluorine the flux will deteriorate refrigerant oil As for the branching of the refrigerant piping or refrigerant refer to the installation manual provided with the outdoo...

Page 10: ...est operation of the air conditioner is finished 1 Remove the control box lid and connect the single phase electric wires to terminals L1 and L2 of the ter minal block and the ground wiring to the gro...

Page 11: ...sputter will not come in contact with the drain pan for the filter If the metal duct pass through a metal lath wire lath or metal plate of a wooden structure separate the duct and wall elec trically B...

Page 12: ...s used Telephone ground wires or lightning rods might cause abnormally high electric potential in the ground during lighting storms 9 2 ELECTRICAL CHARACTERISTICS MCA Min Circuit Amps A MFA Max Fuse A...

Page 13: ...included insulation tube and secure it with the included clamp When use the insulation tube Cut off the insulation tube as need length WARNING Trim and lay the wiring neatly and attach the control bo...

Page 14: ...rupter is imperative for the prevention of electric shocks and fire accidents No 1 system When using 1 remote controller for 1 indoor unit No 2 system For group control or use with 2 remote con trolle...

Page 15: ...3 How to select FORCED OFF and ON OFF OPERATION Turn the power on and then use the remote controller to select operation 10 5 CENTRALIZED CONTROL For centralized control it is necessary to designate...

Page 16: ...the air conditioner go to FIELD SET MODE select MODE NO 21 11 in the case of group set tings set the setting FIRST CODE NO to 7 and set the setting SECOND CODE NO to 03 Return to normal mode after th...

Page 17: ...peration of the air conditioner explain the customer not to operate the air conditioner until the interior finish work is com pleted for the protection of the air conditioner Otherwise substances that...

Page 18: ...1645 Wallace Drive Suite 110 Carrollton TX 75006 info daikinac com www daikinac com 0912 FS 3PN06583 9P EM09A025...

Reviews: