Installation and operation manual

9

FXLQ20~6 FXNQ20~63P7VEB

VRV System air conditioners

4PW59127-1

W

IRING

 

EXAMPLES

Fit the power supply wiring of each unit with a switch and fuse as
shown in 

figure 1

.

Complete system example (3 systems)

When using 1 remote controller for 1 indoor unit. (Normal operation)

(See figure 2)

For group control or use with 2 remote controllers 

(See figure 4)

When including BS unit 

(See figure 3)

PRECAUTIONS

A single switch can be used to supply power to units on the
same system. However, branch switches and branch circuit
breakers must be selected carefully.

For a group control remote controller, choose the remote
controller that suits the indoor unit which has the most functions.

Do not ground the equipment on gas pipes, water pipes,
lightning rods or crossground with telephones. Improper
grounding could result in electric shock.

F

IELD

 

SETTING

Field setting must be made on the remote controller in function of the
installation condition.

Setting can be made by changing the "Mode number", "First
code No." and "Second code No.".

For setting and operation, refer to the "Field settings" in the
installation manual of the remote controller.

Control by 2 Remote Controllers (Controlling 1 indoor 
unit by 2 remote controllers)

When using 2 remote controllers, one must be set to "MAIN" and the
other to "SUB". Refer to the installatoin manual of the remote
controller.

Computerised control (forced off and on/off operation)

1

Wire specifications and how to perform wiring

-

Connect input from outside to terminals T1 and T2 of the 
terminal board (remote controller to transmission wiring).

2

Actuation

-

The following table explains "forced off" and "on/off 
operations" in response to input A.

3

How to select forced off and on/off operation

-

Turn the power on and then use the remote controller to 
select operation.

-

Set the remote controller to the field set mode. For details, 
refer to the chapter "How to set in the field", in the remote 
controller manual.

-

When in the field set mode, select mode No. 12, then set the 
first code No. to "1". Then set second code (position) No. to 
"01" for forced off and to "02" for on/off operation. (forced off 
at factory set.)

Centralized control

For centralized control, it is necessary to designate the group No. For
details, refer to the manual of each optional controller for centralized
control.

1

Power supply

6

BS unit (only for heat 
recovery system)

2

Main switch

3

Outdoor unit

7

Power supply wiring

4

Indoor unit

8

Transmission wiring

5

Remote controller

9

Switch

10

Fuse

1

Outdoor unit

2

Indoor unit

3

Remote controller (optional accessories)

4

Most downstream indoor unit

5

For use with 2 remote controllers

6

BS unit

Wire specification

Sheathed vinyl cord or cable (2 wire)

Gauge

0.75-1.25 mm

2

Length

Maximum 100 m

External terminal

Contact that can ensure the minimum 
applicable load of 15 V DC, 10 mA

Forced off

on/off operation

Input "on" stops operation 

input off 

 on: turns on the unit 

(impossible by remote controllers)

Input "off" enables control 

input on 

 off: turns off the unit by 

remote controller

F2

T1

T2

FORCED
OFF

Input A

Summary of Contents for FXLQ20P7VEB

Page 1: ...NSTALLATION AND OPERATION MANUAL FXLQ20P7VEB FXLQ25P7VEB FXLQ32P7VEB FXLQ40P7VEB FXLQ50P7VEB FXLQ63P7VEB FXNQ20P7VEB FXNQ25P7VEB FXNQ32P7VEB FXNQ40P7VEB FXNQ50P7VEB FXNQ63P7VEB System air conditioners...

Page 2: ...UT D F1 F2 F1 F2 Control box L N L N P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 3 1 4 2 L N L N L N L N 2 1 2 3 7 9 8 10 4 5 6 NOTES L N IN D OUT D...

Page 3: ...parecer positivo de B de acordo com o Certificado C 09 A B C 10 Bem rk som anf rt i A og positivt vurderet af B i henhold til Certifikat C 11 Information enligt A och godk nts av B enligt Certifikatet...

Page 4: ...by suffocation Precautions Do not install or operate the unit in rooms mentioned below Places with mineral oil or filled with oil vapour or spray like in kitchens Plastic parts may deteriorate Where...

Page 5: ...s A product In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures Keep indoor unit outdoor unit power supply wiring and t...

Page 6: ...ir outlet direction can be chosen by rotating the discharge grill NOTE Make sure no short circuit of air is caused when placing the unit directly under a windowsill 100 100 1000 20 A B C C A 1750 B 17...

Page 7: ...alling over either fasten to the wall using the holes provided or fasten to the floor with a field supplied floor fastener Wallmounted installation 1 Positioning of holes for fastening to the wall Uni...

Page 8: ...ning torque Overtightening may damage the flare and cause leaks When connecting the flare nut coat the flare inner surface with ether oil or ester oil and initially tighten 3 or 4 turns by hand before...

Page 9: ...from mixing into the system Vacuum pump Use a 2 stage vacuum pump with a non return valve Make sure the pump oil does not flow oppositely into the system while the pump is not working Use a vacuum pum...

Page 10: ...he table below When attaching the control box lid make sure not to pinch any wires and make sure that the wiring does not come in contact with the piping and sharp edges After all wiring connections a...

Page 11: ...16 0 025 0 5 50 0 6 16 0 035 0 5 63 0 6 16 0 035 0 5 MCA Minimum Circuit Amps A MFA Maximum Fuse Amps A FLA Full Load Amps A NOTE For details refer to Electrical data in the technical data book Power...

Page 12: ...ration 1 Wire specifications and how to perform wiring Connect input from outside to terminals T1 and T2 of the terminal board remote controller to transmission wiring 2 Actuation The following table...

Page 13: ...en finished Error code Meaning There is a short circuit at the forced off terminals T1 T2 U4 or UH The power on the outdoor unit is off The outdoor unit has not been wired for power supply Incorrect t...

Page 14: ...air filter make sure to attach it Turn on the main power supply switch The control panel display lights up when the power is turned on To protect the unit turn on the main power switch at least 6 hour...

Page 15: ...SSORY X18A CONNECTOR WIRING ADAPTOR FOR ELECTRICAL APPENDICES WIRED REMOTE CONTROLLER R1T THERMISTOR AIR SS1 SELECTOR SWITCH MAIN SUB TERMINAL BLOCK BLK BLACK PNK PINK CONNECTOR BLU BLUE RED RED TERMI...

Page 16: ...4PW59127 1 Copyright Daikin...

Reviews: