FXLQ20~6 FXNQ20~63P7VEB
VRV System air conditioners
4PW59127-1

Installation and operation manual

2

Accessories

Check if the following accessories are included with your unit.

Optional accessories

There are two types of remote controllers: wired and wireless.

Select a remote controller according to customer request and
install in an appropriate place.

Refer to catalogues and technical literature for selecting a
suitable remote controller.

For the following items, take special care during 
construction and check after installation is finished

Notes to the installer

Read this manual carefully to ensure correct installation. Be
sure to instruct the customer how to properly operate the system
and show him/her the enclosed operation manual.

Explain to the customer what system is installed on the site. Be
sure to fill out the appropriate installation specifications in the
chapter "What to do before operation" of the outdoor unit
operation manual.

This unit can be installed on the floor or be mounted to a wall.

I

MPORTANT

 

INFORMATION

 

REGARDING

 

THE

 

REFRIGERANT

 

USED

This product contains fluorinated greenhouse gases covered by the
Kyoto Protocol.

Refrigerant type:

R410A

GWP

(1)

 value:

1975

(1)

 GWP = global warming potential

Periodical inspections for refrigerant leaks may be required
depending on European or local legislation. Please contact your local
dealer for more information.

S

ELECTING

 

INSTALLATION

 

SITE

1

Select an installation site where the following conditions are
fulfilled and that meets your customer's approval.

-

The installation location is frost-free.

-

Where optimum air distribution can be ensured.

-

Where nothing blocks air passage.

-

Where condensate water can be properly drained.

-

Where the floor or wall is strong enough to bear the indoor 
unit weight.

-

Where sufficient clearance for maintenance and service can 
be ensured.

-

Where piping between indoor and outdoor units is possible 
within the allowable limit. (Refer to the installation manual of 
the outdoor unit.)

-

This is a class A product. In a domestic environment this 
product may cause radio interference in which case the user 
may be required to take adequate measures.

-

Keep indoor unit, outdoor unit, power supply wiring and 
transmission wiring at least 1 meter away from televisions 
and radios. This is to prevent image interference and noise in 
those electrical appliances. (Noise may be generated 
depending on the conditions under which the electric wave is 
generated, even if 1 meter is kept.)

-

When installing the wireless remote controller kit, the 
communication distance between wireless remote controller 
and indoor unit might be shorter if there are fluorescent lights 
who are electrically started in the room. The indoor unit must 
be installed as far as possible away from fluorescent lights.

-

Do not place objects that are susceptible to moisture directly 
beneath the indoor or outdoor units. Under certain 
conditions, condensation on the main unit or refrigerant 
pipes, air filter dirt or drain blockage may cause dripping, 
resulting in fouling or failure of the object concerned.

1

Metal clamp

6

Insulation for liquid pipe

2

Drain hose

7

Clamp

3

Leveling screw

8

Installation and operation 
manual

4

Sealing pad

5

Insulation for gas pipe

Tick 

 

when 

checked

Is the indoor unit fixed firmly?

The unit may drop, vibrate or make noise.

Is the gas leak test finished?

It may result in insufficient cooling or heating.

Is the unit fully insulated and checked for air leaks?

Condensate water may drip.

Does drainage flow smoothly?

Condensate water may drip.

Does the power supply voltage correspond to that shown on the 
name plate?

The unit may malfunction or components may burn out.

Are wiring and piping correct?

The unit may malfunction or components may burn out.

Is the unit safely grounded?

Dangerous at electric leakage.

Is the wiring size according to specifications?

The unit may malfunction or components may burn out.

Is nothing blocking the air outlet or inlet of either the indoor or 
outdoor units?

It may result in insufficient cooling or heating.

Are refrigerant piping length and additional refrigerant charge 
noted down?

The refrigerant charge in the system might not be clear.

1x

1x

4x

1x

1x

1x

1

2

3

5

6

1x

8

8x

7

4

Summary of Contents for FXLQ20P7VEB

Page 1: ...NSTALLATION AND OPERATION MANUAL FXLQ20P7VEB FXLQ25P7VEB FXLQ32P7VEB FXLQ40P7VEB FXLQ50P7VEB FXLQ63P7VEB FXNQ20P7VEB FXNQ25P7VEB FXNQ32P7VEB FXNQ40P7VEB FXNQ50P7VEB FXNQ63P7VEB System air conditioners...

Page 2: ...UT D F1 F2 F1 F2 Control box L N L N P1 P2 P1 P2 P1 P2 P1 P2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 3 1 4 2 L N L N L N L N 2 1 2 3 7 9 8 10 4 5 6 NOTES L N IN D OUT D...

Page 3: ...parecer positivo de B de acordo com o Certificado C 09 A B C 10 Bem rk som anf rt i A og positivt vurderet af B i henhold til Certifikat C 11 Information enligt A och godk nts av B enligt Certifikatet...

Page 4: ...by suffocation Precautions Do not install or operate the unit in rooms mentioned below Places with mineral oil or filled with oil vapour or spray like in kitchens Plastic parts may deteriorate Where...

Page 5: ...s A product In a domestic environment this product may cause radio interference in which case the user may be required to take adequate measures Keep indoor unit outdoor unit power supply wiring and t...

Page 6: ...ir outlet direction can be chosen by rotating the discharge grill NOTE Make sure no short circuit of air is caused when placing the unit directly under a windowsill 100 100 1000 20 A B C C A 1750 B 17...

Page 7: ...alling over either fasten to the wall using the holes provided or fasten to the floor with a field supplied floor fastener Wallmounted installation 1 Positioning of holes for fastening to the wall Uni...

Page 8: ...ning torque Overtightening may damage the flare and cause leaks When connecting the flare nut coat the flare inner surface with ether oil or ester oil and initially tighten 3 or 4 turns by hand before...

Page 9: ...from mixing into the system Vacuum pump Use a 2 stage vacuum pump with a non return valve Make sure the pump oil does not flow oppositely into the system while the pump is not working Use a vacuum pum...

Page 10: ...he table below When attaching the control box lid make sure not to pinch any wires and make sure that the wiring does not come in contact with the piping and sharp edges After all wiring connections a...

Page 11: ...16 0 025 0 5 50 0 6 16 0 035 0 5 63 0 6 16 0 035 0 5 MCA Minimum Circuit Amps A MFA Maximum Fuse Amps A FLA Full Load Amps A NOTE For details refer to Electrical data in the technical data book Power...

Page 12: ...ration 1 Wire specifications and how to perform wiring Connect input from outside to terminals T1 and T2 of the terminal board remote controller to transmission wiring 2 Actuation The following table...

Page 13: ...en finished Error code Meaning There is a short circuit at the forced off terminals T1 T2 U4 or UH The power on the outdoor unit is off The outdoor unit has not been wired for power supply Incorrect t...

Page 14: ...air filter make sure to attach it Turn on the main power supply switch The control panel display lights up when the power is turned on To protect the unit turn on the main power switch at least 6 hour...

Page 15: ...SSORY X18A CONNECTOR WIRING ADAPTOR FOR ELECTRICAL APPENDICES WIRED REMOTE CONTROLLER R1T THERMISTOR AIR SS1 SELECTOR SWITCH MAIN SUB TERMINAL BLOCK BLK BLACK PNK PINK CONNECTOR BLU BLUE RED RED TERMI...

Page 16: ...4PW59127 1 Copyright Daikin...

Reviews: