background image

6

CAUTION

CAUTION TO BE TAKEN WHEN BRAZING REFRIGER-
ANT PIPING

Do not use flux when brazing refrigerant piping. Therefore, 
use the phosphor copper brazing filter metal (BCuP) which 
does not require flux.
(Flux has extremely harmful infulence on refrigerant piping 
system. For instance, if the chlorine based flux is used, it will 
cause pipe corrosion or, in particular, if the flux contains flu-
orine, it will damage the refrigerant oil.)

• Before brazing local refrigerant piping, nitrogen gas shall be 

blown through the piping to expel air from the piping.
If brazing is done without nitrogen gas blowing, a large 
amount of oxide film develops inside the piping, and could 
cause system malfunction.

• When brazing the refrigerant piping, only begin brazing after 

having carried out nitrogen substitution or while inserting 
nitrogen into the refrigerant piping. Once this is done, con-
nect the indoor unit with a flared or a flanged connection.

• Nitrogen should be set to 2.9 psi with a pressure-reducing 

valve if brazing while inserting nitrogen into the piping. 

NOTE

Use the flare nuts attached with the unit.

• Refer to Table 2 for tightening torque.

Table 2

Not recommendable but in case of emergency

You must use a torque wrench but if you are obliged to install 
the unit without a torque wrench, you may
follow at the installation method mentioned below.

After the work is finished, make sure to check that there 
is no gas leak.

When you keep on tightening the flare nut with a spanner, 
there is a point where the tightening torque suddenly 
increases. From that position, further tighten the flare nut at 
the angle shown below:

Table 3

(in.) 

7. DRAIN PIPING WORK

Rig the drain pipe as shown below and take measures 
against condensate. Improperly rigged piping could lead to 
leaks and eventually wet furniture and belongings.

(1)

Carry out the drain piping

Connect the drain hose 
(1) using the attached 
hose and parts, as 
shown in the right 
drawing.

• If converging multiple drain pipes, install according to the 

procedure shown below.

Select converging drain pipes whose gauge is suitable for the 
operating capacity of the unit.

(2)

After piping work is finished, check drainage flows 
smoothly.
• Add approximately 1 liter of water slowly from the air out-

let and check drainage flow.

(3)

Be sure to insulate all indoor pipes

Pipe 

size

Tightening 

torque

(ft-lbf)

Flare 

dimensions

A (in.)

Flare shape (in.)

 φ

 1/4”

10.5 – 12.7

0.343 – 0.358

 φ

 3/8”

24.1 – 29.4

0.504  – 0.520

 φ

 1/2”

36.5 – 44.5

0.638 – 0.654

 φ

 5/8”

45.6 – 55.6

0.760  – 0.776

Pipe size

Further tightening 

angle

Recommended arm length 

of tool

φ 

1/4”

60 to 90 degrees

Approx. 5 7/8

φ 

3/8”

60 to 90 degrees

Approx. 7 7/8

φ 

1/2”

30 to 60 degrees

Approx. 9 13/16

φ 

5/8”

30 to 60 degrees

Approx. 11 13/16

Summary of Contents for FXLQ12MVJU

Page 1: ...in a handy place for future reference This manual should be left with the equipment owner MODELS Floor standing type and Concealed floor standing type FXLQ12MVJU FXNQ12MVJU FXLQ18MVJU FXNQ18MVJU FXLQ...

Page 2: ...LECTING INSTALLATION SITE 3 4 PREPARATIONS BEFORE INSTALLATION 4 5 INDOOR UNIT INSTALLATION 4 6 REFRIGERANT PIPING WORK 5 7 DRAIN PIPING WORK 6 8 ELECTRIC WIRING WORK 7 9 WIRING EXAMPLE AND HOW TO SET...

Page 3: ...Carry out the specified installation work after taking account of strong winds typhoons or earthquakes Improper installation work may result in the equipment falling and causing accidents Make sure t...

Page 4: ...on of the unit The accessories needed for installation must be retained in your custody until the installation work is completed Do not discard them Decide upon a line of transport Leave the unit insi...

Page 5: ...oise Depending on the radio waves a distance of 3 5 ft may not be enough to eliminate the noise Items to be checked If not properly done what is likely to occur Check Are the indoor and outdoor unit f...

Page 6: ...kin 1 Level the indoor unit with the leveling screws 7 If the floor is too uneven to level the unit place the unit on a flat base and level 2 If the unit is in danger of falling over either fasten to...

Page 7: ...rant to get mixed into the refrigerant circuit such as air etc If any refrigerant gas leaks while working on the unit ventilate the room thoroughly right away The outdoor unit is charged with refriger...

Page 8: ...to install the unit without a torque wrench you may follow at the installation method mentioned below After the work is finished make sure to check that there is no gas leak When you keep on tighteni...

Page 9: ...as leaks Water pipes no grounding effect if hard vinyl piping is used Lightning rods or telephone ground wires might cause abnormally high electric potential in the ground during lightning 8 2 ELECTRI...

Page 10: ...correct screwdriver for tightening the terminal screws If the blade of screwdriver is too small the head of the screw might be damaged and the screw will not be properly tightened If the terminal scr...

Page 11: ...COMPUTERISED CONTROL FORCED OFF AND ON OFF OPERATION 1 Wire specifications and how to perform wiring Connect input from outside to terminals T1 and T2 of the terminal block for remote controller 2 Act...

Page 12: ...corresponding trouble is pro vided in the installation manual of the outdoor unit If any of the items in Table 4 are displayed there may be a problem with the wiring or power so check the wiring again...

Page 13: ...0407 HT 3P086154 3E EM04A011 Daikin US Corporation 375 Park Avenue Suite 3308 New York NY 10152 www daikinac com info daikinac com...

Reviews: