background image

7

CAUTION

• Drain piping connections

Do not connect the drain piping directly to sewage pipes that 
smell of ammonia. The ammonia in the sewage might enter 
the indoor unit through the drain pipes and corrode the heat 
exchanger.

• Keep in mind that it will become the cause of getting drain 

pipe blocked if water collects on drain pipe.

8. ELECTRIC WIRING WORK 

8-1

GENERAL INSTRUCTIONS 

• All field supplied parts and materials, electric works must 

conform to local codes.

• Use copper wire only. 
• Follow the “WIRING DIAGRAM” attached to the unit to wire 

the outdoor unit, indoor units and the remote controllers. 
For details on hooking up the remote controller, refer to the 
“INSTALLATION MANUAL OF REMOTE CONTROLLER.” 

• All wiring must be performed by an authorized electrician.
• This system consists of multiple indoor units. Mark each 

indoor unit as unit A, unit B . . . , and be sure the terminal block 
wiring to the outdoor unit and BS unit is properly matched. If 
wiring and piping between the outdoor unit and indoor unit are 
mismatched, the system may cause a malfunction.

• A circuit breaker capable of shutting down the power supply 

to the entire system must be installed.

• Be sure to ground the air conditioner.
• Do not connect the ground wire to gas pipes, water pipes, 

lightning rods, or telephone ground wires.
• Gas pipes: might cause explosions or fire if gas leaks.
• Water pipes: no grounding effect if hard vinyl piping is 

used.

• Lightning rods or telephone ground wires: might cause 

abnormally high electric potential in the ground during 
lightning.

8-2

ELECTRICAL CHARACTERISTICS

MCA: Min. Circuit Amps (A); MFA: Max. Fuse Amps (A) 
W: Fan Motor Rated Output (W); FLA: Full Load Amps (A)

8-3

SPECIFICATIONS FOR FIELD SUPPLIED 
FUSES AND WIRE 

NOTE

1.

Allowable length of transmission wiring between indoor / 
outdoor units and between the indoor unit and the remote 
controller is as follows. 

(1) Outdoor unit – Indoor unit: 

Max. 3280 ft. (Total wiring length: 6560 ft.) 

(2) Indoor unit – Remote controller: 

Max. 1640 ft.

2.

Insulated thickness: 1/16” or more.

9. WIRING EXAMPLE AND HOW TO SET 

THE REMOTE CONTROLLER

9-1

HOW TO CONNECT WIRINGS 

• Remove the electric parts box lid and connect the wirings.

NOTE

• For wiring to the electric parts box, also see “Wiring Diagram” 

label on the back of the electric parts box lid.

• Do not confuse remote controller wiring and transmission 

wiring when connecting to the terminal block.

• Fasten the wiring with accessory clamp (6).
• If mounting a remote con-

troller on the unit, wire as 
shown in the figure on the 
right.

Units

Power 
supply

Fan motor

Model

Hz Volts

Voltage 

range

MCA MFA

W

FLA

FXLQ12MVJU,
FXNQ12MVJU

60

208-

230

Max. 253
Min.  187

0.5

15

25

0.4

FXLQ18 · 24MVJU,
FXNQ18 · 24MVJU

0.6

15

35

0.5

Model

Power supply wiring

Remote controller wiring

Transmission wiring

Field 

fuses 

Size

Wire

Size

FXLQ12 · 18 · 

24 MVJU

15A

Size must com-
ply with local 
codes.

Sheathed 
wire
(2 wire) 

AWG

18-16

FXNQ12 · 18 · 

24 MVJU

Summary of Contents for FXLQ12MVJU

Page 1: ...in a handy place for future reference This manual should be left with the equipment owner MODELS Floor standing type and Concealed floor standing type FXLQ12MVJU FXNQ12MVJU FXLQ18MVJU FXNQ18MVJU FXLQ...

Page 2: ...LECTING INSTALLATION SITE 3 4 PREPARATIONS BEFORE INSTALLATION 4 5 INDOOR UNIT INSTALLATION 4 6 REFRIGERANT PIPING WORK 5 7 DRAIN PIPING WORK 6 8 ELECTRIC WIRING WORK 7 9 WIRING EXAMPLE AND HOW TO SET...

Page 3: ...Carry out the specified installation work after taking account of strong winds typhoons or earthquakes Improper installation work may result in the equipment falling and causing accidents Make sure t...

Page 4: ...on of the unit The accessories needed for installation must be retained in your custody until the installation work is completed Do not discard them Decide upon a line of transport Leave the unit insi...

Page 5: ...oise Depending on the radio waves a distance of 3 5 ft may not be enough to eliminate the noise Items to be checked If not properly done what is likely to occur Check Are the indoor and outdoor unit f...

Page 6: ...kin 1 Level the indoor unit with the leveling screws 7 If the floor is too uneven to level the unit place the unit on a flat base and level 2 If the unit is in danger of falling over either fasten to...

Page 7: ...rant to get mixed into the refrigerant circuit such as air etc If any refrigerant gas leaks while working on the unit ventilate the room thoroughly right away The outdoor unit is charged with refriger...

Page 8: ...to install the unit without a torque wrench you may follow at the installation method mentioned below After the work is finished make sure to check that there is no gas leak When you keep on tighteni...

Page 9: ...as leaks Water pipes no grounding effect if hard vinyl piping is used Lightning rods or telephone ground wires might cause abnormally high electric potential in the ground during lightning 8 2 ELECTRI...

Page 10: ...correct screwdriver for tightening the terminal screws If the blade of screwdriver is too small the head of the screw might be damaged and the screw will not be properly tightened If the terminal scr...

Page 11: ...COMPUTERISED CONTROL FORCED OFF AND ON OFF OPERATION 1 Wire specifications and how to perform wiring Connect input from outside to terminals T1 and T2 of the terminal block for remote controller 2 Act...

Page 12: ...corresponding trouble is pro vided in the installation manual of the outdoor unit If any of the items in Table 4 are displayed there may be a problem with the wiring or power so check the wiring again...

Page 13: ...0407 HT 3P086154 3E EM04A011 Daikin US Corporation 375 Park Avenue Suite 3308 New York NY 10152 www daikinac com info daikinac com...

Reviews: