background image

5

(4) Perform the following procedure to mount the remote 

controller (optional accessory) on the unit if desired. 
(FXLQ type only)

• Open the left side lid of control panel and mount the lower 

case of the remote controller.

See the installation manual 
attached to the remote controller 
for instructions on screw fasten-
ing and wiring for the remote con-
troller.

CAUTION

Setting the unit at an angle opposite to the drain piping 
might cause leaks.

6. REFRIGERANT PIPING WORK

For refrigerant piping of outdoor units, see the installation 
manual attached to the outdoor unit.
Execute heat insulation work completely on both sides of 
the gas piping and the liquid piping. Otherwise, a water 
leakage can result sometimes.

(When using a heat pump, the temperature of the gas piping 
can reach up to approximately 250°F, so use insulation which is 
sufficiently resistant.)

Also, in cases where the temperature and humidity of the 
refrigerant piping sections might exceed 86°F or RH80%, 
reinforce the refrigerant insulation. (13/16” or thicker) Con-
densate may form on the surface of the insulating material.
Before refrigerant piping work, check which type of refrig-
erant is used. Proper operation is not possible if the types 
of refrigerant are not the same.

NOTE

Use a pipe cutter and flare suitable for the type of 
refrigerant.

To prevent dust, moisture or other foreign matter 
from infiltrating the tube, either pinch the end or 
cover it with tape.

Do not allow anything other than the designated 
refrigerant to get mixed into the refrigerant circuit, 
such as air, etc. 

If any refrigerant gas leaks while working on the unit, 
ventilate the room thoroughly right away.

• The outdoor unit is charged with refrigerant.
• Use copple alloy seamless pipes.
• To prevent flare nut cracking and gas leaks, be sure to use 

both a spanner and torque wrench together, as shown in the 
drawing, when connecting or disconnecting pipes to / from 
the unit.

• Refer to Table 2 for the dimensions of flare.
• When connecting the flare nut, coat the flare section (both 

inside and outside) with ester oil or ether oil, rotate three or  
four times first, then screw in.

• Refer to the Table 2 for tightening torque.

• After inspecting pipe joints for gas leakage, be sure to insu-

late with the accessory joint insulation for fitting (3) (4) while 
referring to the figure below. 
(Fasten both ends with clamps (6)).

• Wrap only the gas line side with the sealing pad (5). Bend the 

pad over the insulation for fitting (union) from above.

Use “ Table 3 ” as a reference if a torque wrench is not available. 
Once work is complete, make sure there is no gas leaking. As 
the flare nut is tightened with the wrench, the torque will sud-
denly increase. From that position, tighten the nut to the angle 
shown on “ Table 3 ”.

• Make absolutely sure to execute heat insulation works on the 

pipe-connecting section after checking gas leakage by thor-
oughly studying the following figure and using the attached 
heat insulating materials for fitting (3) and (4). (Fasten both 
ends with the clamps (6) (accessory).) 

(Refer to Fig. 1)

CAUTION

Be sure to insulate any field piping all the way to the piping 
connection inside the unit. Any exposed piping may cause 
condensate or burns if touched.

Summary of Contents for FXLQ12MVJU

Page 1: ...in a handy place for future reference This manual should be left with the equipment owner MODELS Floor standing type and Concealed floor standing type FXLQ12MVJU FXNQ12MVJU FXLQ18MVJU FXNQ18MVJU FXLQ...

Page 2: ...LECTING INSTALLATION SITE 3 4 PREPARATIONS BEFORE INSTALLATION 4 5 INDOOR UNIT INSTALLATION 4 6 REFRIGERANT PIPING WORK 5 7 DRAIN PIPING WORK 6 8 ELECTRIC WIRING WORK 7 9 WIRING EXAMPLE AND HOW TO SET...

Page 3: ...Carry out the specified installation work after taking account of strong winds typhoons or earthquakes Improper installation work may result in the equipment falling and causing accidents Make sure t...

Page 4: ...on of the unit The accessories needed for installation must be retained in your custody until the installation work is completed Do not discard them Decide upon a line of transport Leave the unit insi...

Page 5: ...oise Depending on the radio waves a distance of 3 5 ft may not be enough to eliminate the noise Items to be checked If not properly done what is likely to occur Check Are the indoor and outdoor unit f...

Page 6: ...kin 1 Level the indoor unit with the leveling screws 7 If the floor is too uneven to level the unit place the unit on a flat base and level 2 If the unit is in danger of falling over either fasten to...

Page 7: ...rant to get mixed into the refrigerant circuit such as air etc If any refrigerant gas leaks while working on the unit ventilate the room thoroughly right away The outdoor unit is charged with refriger...

Page 8: ...to install the unit without a torque wrench you may follow at the installation method mentioned below After the work is finished make sure to check that there is no gas leak When you keep on tighteni...

Page 9: ...as leaks Water pipes no grounding effect if hard vinyl piping is used Lightning rods or telephone ground wires might cause abnormally high electric potential in the ground during lightning 8 2 ELECTRI...

Page 10: ...correct screwdriver for tightening the terminal screws If the blade of screwdriver is too small the head of the screw might be damaged and the screw will not be properly tightened If the terminal scr...

Page 11: ...COMPUTERISED CONTROL FORCED OFF AND ON OFF OPERATION 1 Wire specifications and how to perform wiring Connect input from outside to terminals T1 and T2 of the terminal block for remote controller 2 Act...

Page 12: ...corresponding trouble is pro vided in the installation manual of the outdoor unit If any of the items in Table 4 are displayed there may be a problem with the wiring or power so check the wiring again...

Page 13: ...0407 HT 3P086154 3E EM04A011 Daikin US Corporation 375 Park Avenue Suite 3308 New York NY 10152 www daikinac com info daikinac com...

Reviews: