Capacity Tables
EDUS391502-F7
18
FXLQ-M / FXNQ-M
8. Capacity Tables
8.1
Cooling Capacity at Te: 43°F (6°C)
TC:
Total capacity: MBH
SHC: Sensible heat capacity: MBH
Notes:
1. These capacity tables can be used when selecting a
VRV
indoor unit. The actual capacity of the
VRV
system depends on factors such
as the selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the
VRV
system satisfies the required heat load.
2.
shows rated condition.
8.2
Heating Capacity
TC:
Total capacity: MBH
Notes:
1. These capacity tables can be used when selecting a
VRV
indoor unit. The actual capacity of the
VRV
system depends on factors such
as the selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the
VRV
system satisfies the required heat load.
2.
shows rated condition.
8.3
Correction Factor for Cooling Capacity at Te: 48°F (9°C)
TC:
Total capacity
SHF: Sensible heat factor
Model
Indoor air temp. °FWB (Te: 43°F (6°C))
61
64
67
70
72
75
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
MBH
MBH
MBH
MBH
MBH
MBH
MBH
MBH
MBH
MBH
MBH
MBH
FXLQ07MVJU
FXNQ07MVJU
5.9 4.9 6.7 5.4 7.5 5.8 7.6 5.6 7.7 5.1 7.9 4.8
FXLQ09MVJU
FXNQ09MVJU
7.5 5.9 8.5 6.5 9.5 7.1 9.7 6.9 9.8 6.4 10.0 6.0
FXLQ12MVJU
FXNQ12MVJU
9.5
7.5
10.7
7.9
12.0
8.3
12.7
8.4
12.9
8.0
13.1
7.6
FXLQ18MVJU
FXNQ18MVJU
14.2
10.7
16.1
11.5
18.0
12.2
19.1
12.6
19.3
12.1
19.7
11.4
FXLQ24MVJU
FXNQ24MVJU
18.9
14.1
21.5
15.1
24.0
15.9
25.5
16.5
25.8
15.8
26.3
14.7
Model
Indoor air temp. °FDB (Tc: 115°F (46°C))
62
65
68
70
72
75
TC
TC
TC
TC
TC
TC
MBH
MBH
MBH
MBH
MBH
MBH
FXLQ07MVJU
FXNQ07MVJU
9.9
9.3
8.8
8.5
8.2
7.7
FXLQ09MVJU
FXNQ09MVJU
12.3
11.5
10.9
10.5
10.1
9.5
FXLQ12MVJU
FXNQ12MVJU
14.9
14.7
14.0
13.5
13.0
12.3
FXLQ18MVJU
FXNQ18MVJU
22.3
22.1
21.0
20.0
19.5
18.4
FXLQ24MVJU
FXNQ24MVJU
29.7
29.5
28.0
27.0
26.0
24.5
Model
Indoor air temp. °FWB (Te: 48°F (9°C))
61
64
67
70
72
75
TC
SHF
TC
SHF
TC
SHF
TC
SHF
TC
SHF
TC
SHF
FXLQ07MVJU
FXNQ07MVJU
0.71
1.16
0.77
1.11
0.79
1.09
0.81
1.07
0.84
1.05
0.87
1.03
FXLQ09MVJU
FXNQ09MVJU
0.71
1.16
0.77
1.11
0.79
1.09
0.81
1.07
0.84
1.05
0.87
1.03
FXLQ12MVJU
FXNQ12MVJU
0.71
1.16
0.77
1.11
0.79
1.09
0.81
1.07
0.84
1.05
0.87
1.03
FXLQ18MVJU
FXNQ18MVJU
0.71
1.16
0.77
1.11
0.79
1.09
0.81
1.07
0.84
1.05
0.87
1.03
FXLQ24MVJU
FXNQ24MVJU
0.71
1.16
0.77
1.10
0.80
1.08
0.81
1.07
0.84
1.05
0.87
1.04
Refer to the correction factor table below when a mini-
split indoor unit is connected to your
VRV
system.
Summary of Contents for FXLQ-M Series
Page 1: ...EDUS391502 F7 FXLQ M FXNQ M Floor Standing Type Concealed Floor Standing Type...
Page 2: ......
Page 11: ...EDUS391502 F7 Dimensions FXLQ M FXNQ M 9 3D045642A Unit in mm FXLQ12MVJU9...
Page 12: ...Dimensions EDUS391502 F7 10 FXLQ M FXNQ M 3D045643A Unit in mm FXLQ18MVJU9 FXLQ24MVJU9...
Page 13: ...EDUS391502 F7 Dimensions FXLQ M FXNQ M 11 3 2 FXNQ 3D090733 Unit in mm FXNQ07MVJU9 FXNQ09MVJU9...
Page 14: ...Dimensions EDUS391502 F7 12 FXLQ M FXNQ M 3D045650A Unit in mm FXNQ12MVJU9...
Page 15: ...EDUS391502 F7 Dimensions FXLQ M FXNQ M 13 3D045651A Unit in mm FXNQ18MVJU9 FXNQ24MVJU9...
Page 22: ...Sound Levels Reference Data EDUS391502 F7 20 FXLQ M FXNQ M FXLQ12MVJU 4D052501...
Page 23: ...EDUS391502 F7 Sound Levels Reference Data FXLQ M FXNQ M 21 FXLQ18MVJU 4D052502...
Page 24: ...Sound Levels Reference Data EDUS391502 F7 22 FXLQ M FXNQ M FXLQ24MVJU 4D052503...
Page 26: ...Sound Levels Reference Data EDUS391502 F7 24 FXLQ M FXNQ M FXNQ12MVJU 4D052504...
Page 27: ...EDUS391502 F7 Sound Levels Reference Data FXLQ M FXNQ M 25 FXNQ18MVJU 4D052505...
Page 28: ...Sound Levels Reference Data EDUS391502 F7 26 FXLQ M FXNQ M FXNQ24MVJU 4D052506...