Capacity Tables

EDUS391502-F7

18

FXLQ-M / FXNQ-M

8. Capacity Tables

8.1

Cooling Capacity at Te: 43°F (6°C)

TC:

Total capacity: MBH

SHC: Sensible heat capacity: MBH

Notes:

  1. These capacity tables can be used when selecting a 

VRV

 indoor unit. The actual capacity of the 

VRV

 system depends on factors such 

as the selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the 

VRV

 

system satisfies the required heat load.

2. 

 shows rated condition.

8.2

Heating Capacity

TC:

Total capacity: MBH

Notes:

  1. These capacity tables can be used when selecting a 

VRV

 indoor unit. The actual capacity of the 

VRV

 system depends on factors such 

as the selected model of outdoor units, outdoor air temperature and piping length. Please confirm that the corrected capacity of the 

VRV

 

system satisfies the required heat load.

2. 

 shows rated condition.

8.3

Correction Factor for Cooling Capacity at Te: 48°F (9°C)

TC:

 Total capacity

SHF:  Sensible heat factor

Model

Indoor air temp.  °FWB (Te: 43°F (6°C))

61

64

67

70

72

75

TC

SHC

TC

SHC

TC

SHC

TC

SHC

TC

SHC

TC

SHC

MBH

MBH

MBH

MBH

MBH

MBH

MBH

MBH

MBH

MBH

MBH

MBH

FXLQ07MVJU

FXNQ07MVJU

5.9 4.9 6.7 5.4 7.5 5.8 7.6 5.6 7.7 5.1 7.9 4.8 

FXLQ09MVJU

FXNQ09MVJU

7.5 5.9 8.5 6.5 9.5 7.1 9.7 6.9 9.8 6.4 10.0 6.0 

FXLQ12MVJU

FXNQ12MVJU

9.5

7.5

10.7

7.9

12.0

8.3

12.7

8.4

12.9

8.0

13.1

7.6

FXLQ18MVJU

FXNQ18MVJU

14.2

10.7

16.1

11.5

18.0

12.2

19.1

12.6

19.3

12.1

19.7

11.4

FXLQ24MVJU

FXNQ24MVJU

18.9

14.1

21.5

15.1

24.0

15.9

25.5

16.5

25.8

15.8

26.3

14.7

Model

Indoor air temp.  °FDB (Tc: 115°F (46°C))

62

65

68

70

72

75

TC

TC

TC

TC

TC

TC

MBH

MBH

MBH

MBH

MBH

MBH

FXLQ07MVJU

FXNQ07MVJU

9.9

9.3

8.8

8.5

8.2

7.7

FXLQ09MVJU

FXNQ09MVJU

12.3

11.5

10.9

10.5

10.1

9.5

FXLQ12MVJU

FXNQ12MVJU

14.9

14.7

14.0

13.5

13.0

12.3

FXLQ18MVJU

FXNQ18MVJU

22.3

22.1

21.0

20.0

19.5

18.4

FXLQ24MVJU

FXNQ24MVJU

29.7

29.5

28.0

27.0

26.0

24.5

Model

Indoor air temp.  °FWB (Te: 48°F (9°C))

61

64

67

70

72

75

TC

SHF

TC

SHF

TC

SHF

TC

SHF

TC

SHF

TC

SHF

FXLQ07MVJU

FXNQ07MVJU

0.71

1.16

0.77

1.11

0.79

1.09

0.81

1.07

0.84

1.05

0.87

1.03

FXLQ09MVJU

FXNQ09MVJU

0.71

1.16

0.77

1.11

0.79

1.09

0.81

1.07

0.84

1.05

0.87

1.03

FXLQ12MVJU

FXNQ12MVJU

0.71

1.16

0.77

1.11

0.79

1.09

0.81

1.07

0.84

1.05

0.87

1.03

FXLQ18MVJU

FXNQ18MVJU

0.71

1.16

0.77

1.11

0.79

1.09

0.81

1.07

0.84

1.05

0.87

1.03

FXLQ24MVJU

FXNQ24MVJU

0.71

1.16

0.77

1.10

0.80

1.08

0.81

1.07

0.84

1.05

0.87

1.04

Refer to the correction factor table below when a mini-
split indoor unit is connected to your 

VRV

 system.

Summary of Contents for FXLQ-M Series

Page 1: ...EDUS391502 F7 FXLQ M FXNQ M Floor Standing Type Concealed Floor Standing Type...

Page 2: ......

Page 3: ...agrams 15 6 Electric Characteristics 16 7 Safety Devices Setting 17 8 Capacity Tables 18 8 1 Cooling Capacity at Te 43 F 6 C 18 8 2 Heating Capacity 18 8 3 Correction Factor for Cooling Capacity at Te...

Page 4: ...ge from 0 6 to 2 Ton Stylish modern casing finished in ivory white Ideal for installation beneath a window thanks to its low height One of our slimmest indoor units less than 9 fits any interior desig...

Page 5: ...range from 0 6 to 2 Ton Ideal for installation beneath a window thanks to its low height One of our slimmest indoor units less than 9 fits any interior design only the suction and discharge grilles a...

Page 6: ...irect drive Direct drive Direct drive Temperature control Microprocessor thermostat for cooling and heating Microprocessor thermostat for cooling and heating Microprocessor thermostat for cooling and...

Page 7: ...04 0 282 Fan Model 2D14B20 2D14B20 Type Sirocco fan Sirocco fan Motor output W 35 35 Airflow rate H L cfm m min 490 380 14 11 560 420 16 12 Drive Direct drive Direct drive Temperature control Micropro...

Page 8: ...rive Direct drive Direct drive Temperature control Microprocessor thermostat for cooling and heating Microprocessor thermostat for cooling and heating Microprocessor thermostat for cooling and heating...

Page 9: ...2 3 04 0 282 Fan Model 2D14B20 2D14B20 Type Sirocco fan Sirocco fan Motor output W 35 35 Airflow rate H L cfm m min 490 380 14 11 560 420 16 12 Drive Direct drive Direct drive Temperature control Micr...

Page 10: ...Dimensions EDUS391502 F7 8 FXLQ M FXNQ M 3 Dimensions 3 1 FXLQ 3D090732A Unit in mm FXLQ07MVJU9 FXLQ09MVJU9...

Page 11: ...EDUS391502 F7 Dimensions FXLQ M FXNQ M 9 3D045642A Unit in mm FXLQ12MVJU9...

Page 12: ...Dimensions EDUS391502 F7 10 FXLQ M FXNQ M 3D045643A Unit in mm FXLQ18MVJU9 FXLQ24MVJU9...

Page 13: ...EDUS391502 F7 Dimensions FXLQ M FXNQ M 11 3 2 FXNQ 3D090733 Unit in mm FXNQ07MVJU9 FXNQ09MVJU9...

Page 14: ...Dimensions EDUS391502 F7 12 FXLQ M FXNQ M 3D045650A Unit in mm FXNQ12MVJU9...

Page 15: ...EDUS391502 F7 Dimensions FXLQ M FXNQ M 13 3D045651A Unit in mm FXNQ18MVJU9 FXNQ24MVJU9...

Page 16: ...s Liquid 1 2 12 7 1 4 6 4 FXLQ24MVJU FXNQ24MVJU 5 8 15 9 3 8 9 5 C 4D034245L FXLQ07MVJU9 FXLQ09MVJU9 FXLQ12MVJU9 FXLQ18MVJU9 FXLQ24MVJU9 FXNQ07MVJU9 FXNQ09MVJU9 FXNQ12MVJU9 FXNQ18MVJU9 FXNQ24MVJU9 FXL...

Page 17: ...EDUS391502 F7 Wiring Diagrams FXLQ M FXNQ M 15 5 Wiring Diagrams FXLQ07MVJU FXLQ09MVJU FXLQ12MVJU FXLQ18MVJU FXLQ24MVJU FXNQ07MVJU FXNQ09MVJU FXNQ12MVJU FXNQ18MVJU FXNQ24MVJU 3D045644C...

Page 18: ...lectric Characteristics EDUS391502 F7 16 FXLQ M FXNQ M 6 Electric Characteristics FXLQ07MVJU FXLQ09MVJU FXLQ12MVJU FXLQ18MVJU FXLQ24MVJU FXNQ07MVJU FXNQ09MVJU FXNQ12MVJU FXNQ18MVJU FXNQ24MVJU 4D047090...

Page 19: ...12MVJU FXNQ12MVJU FXLQ18MVJU FXNQ18MVJU FXLQ24MVJU FXNQ24MVJU Printed circuit board fuse 250V 5A 250V 5A 250V 5A 250V 5A 250V 5A Fan motor thermal protector F C OFF 275 18 135 10 ON 248 120 or less OF...

Page 20: ...07MVJU 5 9 4 9 6 7 5 4 7 5 5 8 7 6 5 6 7 7 5 1 7 9 4 8 FXLQ09MVJU FXNQ09MVJU 7 5 5 9 8 5 6 5 9 5 7 1 9 7 6 9 9 8 6 4 10 0 6 0 FXLQ12MVJU FXNQ12MVJU 9 5 7 5 10 7 7 9 12 0 8 3 12 7 8 4 12 9 8 0 13 1 7 6...

Page 21: ...EDUS391502 F7 Sound Levels Reference Data FXLQ M FXNQ M 19 9 Sound Levels Reference Data 9 1 FXLQ FXLQ07MVJU FXLQ09MVJU 4D094283...

Page 22: ...Sound Levels Reference Data EDUS391502 F7 20 FXLQ M FXNQ M FXLQ12MVJU 4D052501...

Page 23: ...EDUS391502 F7 Sound Levels Reference Data FXLQ M FXNQ M 21 FXLQ18MVJU 4D052502...

Page 24: ...Sound Levels Reference Data EDUS391502 F7 22 FXLQ M FXNQ M FXLQ24MVJU 4D052503...

Page 25: ...EDUS391502 F7 Sound Levels Reference Data FXLQ M FXNQ M 23 9 2 FXNQ FXNQ07MVJU FXNQ09MVJU 4D094284...

Page 26: ...Sound Levels Reference Data EDUS391502 F7 24 FXLQ M FXNQ M FXNQ12MVJU 4D052504...

Page 27: ...EDUS391502 F7 Sound Levels Reference Data FXLQ M FXNQ M 25 FXNQ18MVJU 4D052505...

Page 28: ...Sound Levels Reference Data EDUS391502 F7 26 FXLQ M FXNQ M FXNQ24MVJU 4D052506...

Page 29: ...VJU FXLQ12MVJU FXLQ18MVJU FXLQ24MVJU Unit in mm 10 2 FXNQ FXNQ07MVJU FXNQ09MVJU FXNQ12MVJU FXNQ18MVJU FXNQ24MVJU Unit in mm 4D045645A FXLQ07 09MVJU MODEL FXLQ12MVJU 19 11 16 500 22 1 2 570 FXLQ18 24MV...

Page 30: ...U FXNQ07MVJU FXLQ09MVJU FXNQ09MVJU FXLQ12MVJU FXNQ12MVJU FXLQ18MVJU FXNQ18MVJU FXLQ24MVJU FXNQ24MVJU 1 Remote controller Wired type BRC1E73 2 Set back time clock BRC15A71 3 Remote sensor KRCS01 1B 4 C...

Page 31: ...EDUS391502 F7 Appendix FXLQ M FXNQ M i Appendix 1 Installation Manual 1...

Page 32: ...heck that the refrigerant gas does not leak throughout the system r Q PQV KPUVCNN WPKV KP CP CTGC YJGTG COOCDNG OCVG rials are present due to risk of explosions that can cause serious injury or death...

Page 33: ...d the chapter Refrigerant Piping Work and follow the procedures r 5KPEG 4 KU C DNGPF VJG TGSWKTGF CFFKVKQPCN TGHTKI erant must be charged in its liquid state If the refriger ant is charged in a state...

Page 34: ...f installed as a household appliance it could cause electro magnetic interference WARNING r Entrust installation to the place of purchase or an autho rized serviceman Improper installation could lead...

Page 35: ...m air distribution can be ensured r 6JGTG KU PQ TKUM QH COOCDNG ICU NGCMCIG r Piping between indoor and outdoor units is possible within the allowable limit Refer to the installation manu al of the ou...

Page 36: ...e sure to use VJG RTQXKFGF CEEGUUQTKGU CPF URGEK GF RCTVU FGUKIPCVGF D Daikin 1 Level the indoor unit with the leveling screws 7 If VJG QQT KU VQQ WPGXGP VQ NGXGN VJG WPKV RNCEG VJG WPKV QP C CV DCUG...

Page 37: ...If any refrigerant gas leaks while working on the unit venti late the room thoroughly right away r The outdoor unit is charged with refrigerant r Use copper alloy seamless pipes r 6Q RTGXGPV CTG PWV E...

Page 38: ...ing size in mm Tightening torque lbf ft N m Dimension for RTQEGUUKPI CTG A in mm Flare shape I 1 4 6 4 10 4 12 7 15 7 1 5 0 342 0 358 8 9 0 2 R0 016 0 031 90 2 A 4 5 2 I 3 8 9 5 24 1 29 4 36 3 3 6 0 5...

Page 39: ...gas or water pipings lightning conductor or telephone ground wiring r Gas piping IPKVKQP QT GZRNQUKQP OC QEEWT KH the gas leaks r Water piping Hard vinyl tubes are not effective ground r Lightning co...

Page 40: ...GEVU QT QVJGT small creatures Otherwise a short circuit may occur inside VJG EQPVTQN DQZ r When clamping the wirings be sure no tension is applied to the wire connections by using the included clamps...

Page 41: ...s activated L1 L2 L1 L2 L1 L2 Control box Outdoor unit No 2 System Indoor unit A Indoor unit B Indoor unit C Most downstream indoor unit For use with 2 remote controllers IN D OUT D F1 F2 F1 F2 F1 F2...

Page 42: ...hibited Remote controller permitted In case of ON OFF OPERATION Operation Stop 3 How to choose FORCED OFF or ON OFF OPERA TION r For choosing FORCED OFF or ON OFF OPERATION setting by remote controlle...

Page 43: ...ransmission wiring and the remote controller wiring and FORCED OFF wiring are connected incorrectly r The transmission wiring is disconnected No indication r The power supply to the indoor unit is not...

Page 44: ......

Page 45: ......

Page 46: ......

Page 47: ......

Page 48: ...or explosion Use only those parts and accessories supplied or specified by Daikin Ask a qualified installer or contractor to install those parts and accessories Use of unauthorised parts and accessor...

Reviews: