Appendix
EDUS391502-F7
11
FXLQ-M / FXNQ-M
3P086154-3R
11
3P086154-3R
English
Terminal for remote
controller wiring (P1, P2)
No polarity
Remote
controller 2
(Sub)
Remote
controller 1
(Main)
Terminal block
(X2M)
F2
F1
P2
P1
T2
T1
< Caution >
r
When using the group control and the 2 remote control-
lers control at the same time, connect the remote con-
troller 2 (Sub) to the indoor unit at the end of the cross-
over wiring (the largest No.).
Indoor unit 1
Indoor unit 2
Indoor unit
largest No.
Remote
controller 2
(Sub)
Crossover
wiring (Remote
controller)
Remote
controller 1
(Main)
FOR CENTRALIZED CONTROL
r
When centralized equipment (such as centralized control-
ler) is used for control, it is required to set the group No. on
the remote controller.
For details, refer to the manuals attached to the centralized
equipment.
r
Connect the centralized equipment to the indoor unit con-
nected to the remote controller.
9-5 FOR REMOTE CONTROL (FORCE OFF OR ON /
OFF OPERATION)
(1)
9KTKPIOGVJQFCPFURGEKƂECVKQP
r
4GOQVGEQPVTQNKUCXCKNCDNGD[EQPPGEVKPIVJGGZVGTPCN
input to the terminal T1 and T2 on the terminal block for
remote controller and transmission wiring (X2M).
F2
T1
T2
FORCED
OFF
Input A
Wiring
URGEKƂECVKQP
2-conductor,
stranded non-
shielded copper
cable/PVC or
vinyl jacket.
Gauge
AWG18-16
Wiring length
/CZHV
(100 m)
'ZVGTPCN
contact spec
Contact that can
make and break
the min. load of
15 V DC , 1 mA
(2) Actuation
r
Input A of FORCED OFF and ON/OFF OPERATION
will be as the table shown below.
Input A = ON
Input A = OFF
In case of FORCED
OFF
Remote controller
prohibited
Remote controller
permitted
In case of ON/OFF
OPERATION
Operation
Stop
(3) How to choose FORCED OFF or ON/OFF OPERA-
TION
r
For choosing FORCED OFF or ON/OFF OPERATION,
setting by remote controller is required.
(Refer to
(+'.&5'66+0)
.)
FIELD SETTING
<<Refer to also the installation manual attached to the
outdoor unit.>>
CAUTION
$GHQTGECTT[KPIQWVƂGNFUGVVKPIEJGEMVJGKVGOUOGPVKQPGFKP
Clause 2:
a. Items to be checked after completion of work
QPRCIG|%JGEMKHCNNVJGKPUVCNNCVKQPCPFRKRKPIYQTMUHQT
the air conditioner are completed.
r
%JGEMKHVJGEQPVTQNDQZEQXGTUQHVJGCKTEQPFKVKQPGTCTG
closed.
< FIELD SETTING >
#HVGTVWTPQPVJGRQYGTUWRRN[ECTT[QWVƂGNFUGVVKPI
from the remote controller according to the installation
state.>>
r
Carry out setting at 3 places, MODE NO., FIRST CODE
NO. and SECOND CODE NO.
The settings shown by
in the table indicate those
when shipped from the factory.
r
The method of setting procedure and operation is shown in
the installation manual attached to the remote controller.
(Note) Though setting of MODE NO. is carried out as a
group, if you intend to carry out individual setting by
GCEJKPFQQTWPKVQTEQPƂTOCVKQPCHVGTUGVVKPIECTT[
out setting with the MODE NO. shown in the paren-
thesis ( ).
r
In case of remote control, for changeover of input to
FORCED OFF or to ON/OFF OPERATION.
=?'PVGTKPVQVJGƂGNFUGVVKPIOQFGYKVJVJGTGOQVGEQPVTQNNGT
[2] Select MODE NO.
12
.
[3] Set the FIRST CODE NO. to
1
.
[4-1] For FORCE OFF, set the SECOND CODE NO. to
.
[4-2] For ON/OFF OPERATION, set the SECOND CODE
NO. to
.
(It is set to FORCE OFF when shipped from the factory.)
r
Ask your customer to keep the manual attached to the
remote controller together with the operation manual.
r
Do not carry out settings other than those shown in the
table.
Summary of Contents for FXLQ-M Series
Page 1: ...EDUS391502 F7 FXLQ M FXNQ M Floor Standing Type Concealed Floor Standing Type...
Page 2: ......
Page 11: ...EDUS391502 F7 Dimensions FXLQ M FXNQ M 9 3D045642A Unit in mm FXLQ12MVJU9...
Page 12: ...Dimensions EDUS391502 F7 10 FXLQ M FXNQ M 3D045643A Unit in mm FXLQ18MVJU9 FXLQ24MVJU9...
Page 13: ...EDUS391502 F7 Dimensions FXLQ M FXNQ M 11 3 2 FXNQ 3D090733 Unit in mm FXNQ07MVJU9 FXNQ09MVJU9...
Page 14: ...Dimensions EDUS391502 F7 12 FXLQ M FXNQ M 3D045650A Unit in mm FXNQ12MVJU9...
Page 15: ...EDUS391502 F7 Dimensions FXLQ M FXNQ M 13 3D045651A Unit in mm FXNQ18MVJU9 FXNQ24MVJU9...
Page 22: ...Sound Levels Reference Data EDUS391502 F7 20 FXLQ M FXNQ M FXLQ12MVJU 4D052501...
Page 23: ...EDUS391502 F7 Sound Levels Reference Data FXLQ M FXNQ M 21 FXLQ18MVJU 4D052502...
Page 24: ...Sound Levels Reference Data EDUS391502 F7 22 FXLQ M FXNQ M FXLQ24MVJU 4D052503...
Page 26: ...Sound Levels Reference Data EDUS391502 F7 24 FXLQ M FXNQ M FXNQ12MVJU 4D052504...
Page 27: ...EDUS391502 F7 Sound Levels Reference Data FXLQ M FXNQ M 25 FXNQ18MVJU 4D052505...
Page 28: ...Sound Levels Reference Data EDUS391502 F7 26 FXLQ M FXNQ M FXNQ24MVJU 4D052506...
Page 31: ...EDUS391502 F7 Appendix FXLQ M FXNQ M i Appendix 1 Installation Manual 1...
Page 44: ......
Page 45: ......
Page 46: ......
Page 47: ......