background image

English

7

Use “ Table 2 ” as a reference if a torque wrench is not available. 
Once work is complete, make sure there is no gas leaking. As 
the flare nut is tightened with the wrench, the torque will sud-
denly increase. From that position, tighten the nut to the angle 
shown on “ Table 2 ”.

• Make absolutely sure to execute heat insulation works on the 

pipe-connecting section after checking gas leakage by thor-
oughly studying the following figure and using the attached 
heat insulating materials for fitting (6) and (7). (Fasten both 
ends with the clamps (4) (accessory).) 
 

(Refer to Fig. 18)

• Wrap the sealing pad (9) (accessory) only around the insula-

tion for the joints on the gas piping side. 

(Refer to Fig. 19)

CAUTION

Be sure to insulate any field piping all the way to the piping 
connection inside the unit. Any exposed piping may cause 
condensation or burns if touched.

CAUTION

CAUTION TO BE TAKEN WHEN BRAZING REFRIGER-

ANT PIPING

Do not use flux when brazing refrigerant piping. Therefore, use 
the phosphor copper brazing filler metal (BCuP-2: JIS Z 3264/
B-Cu93P-710/795: ISO 3677) which does not require flux.
(Flux has extremely harmful influence on refrigerant piping 
systems. For instance, if the chlorine based flux is used, it will 
cause pipe corrosion or, in particular, if the flux contains fluo-
rine, it will damage the refrigerant oil.)

• Before brazing local refrigerant piping, nitrogen gas shall be 

blown through the piping to expel air from the piping.
If your brazing is done without nitrogen gas blowing, a large 
amount of oxide film develops inside the piping, and could 
cause system malfunction.

• When brazing the refrigerant piping, only begin brazing after 

having carried out nitrogen substitution or while inserting 
nitrogen into the refrigerant piping. Once this is done, con-
nect the indoor unit with a flared or a flanged connection.

• Nitrogen should be set to 0.02 MPa with a pressure-reducing 

valve if brazing while inserting nitrogen into the piping.

NOTE

NOTE

NOTE

NOTE

The flare nuts used must be those included with the main 

body.

• Refer to Table 1 for tightening torque.

Table 1

Not recommendable but in case of emergency

You must use a torque wrench but if you are obliged to 
install the unit without a torque wrench, you may follow the 
installation method mentioned below.

After the work is finished, make sure to check that 
there is no gas leak.

When you keep on tightening the flare nut with a spanner, 
there is a point where the tightening torque suddenly 
increases. From that position, further tighten the flare nut 
the angle shown below:

Table 2

7. DRAIN PIPING WORK

Rig the drain pipe as shown below and take measures against 
condensation. Improperly rigged piping could lead to leaks and 
eventually wet furniture and belongings.

(1)

Carry out the drain piping
• For drain work, rig the pipes so that they drain reliably.
• The drain pipe outlet direction can be chosen from the 

right rear, right, left rear, and left. Refer to “REFRIGER-
ANT PIPING WORK” for right rear and right direction, 
and refer to Fig. 20 for left rear and left direction. 

    

 

 

   

  

    

   

  

 

 

 

  

  

 

 

 

  

     !

" #  $ #

%   

   

   

Fig. 18

Fig. 19

   

 

Pipe 

size

Tightening torque

(N·m)

Flare 

dimensions

A (mm)

Flare

 φ

 6.4 

(1/4”)

15.7±1.5

8.9±0.2

 φ

 9.5 

(3/8”)

36.3±3.6

13.0±0.2

 φ

 12.7 

(1/4”)

54.9±5.4

16.4±0.2

 φ

 15.9

(5/8”)

68.6±6.8

19.5±0.2

Pipe size

Further tightening angle

Recommended arm 

length of tool

φ 

6.4 (1/4”)

60 to 90 degrees

Approx. 150mm

φ 

9.5 (3/8”)

60 to 90 degrees

Approx. 200mm

φ 

12.7 (1/2”)

30 to 60 degrees

Approx. 250mm

φ 

15.9 (5/8”)

30 to 60 degrees

Approx. 300mm

A

45

0

± 2

0

R0.4-0.8

90

0

± 2

0

 

Rear side (metal plate)

removable part

Left-facing drain piping

Left dressing board

removable part

Rear left-facing

drain piping

Fig. 20

01_EN_3P172532-7B.fm  Page 7  Wednesday, October 14, 2015  6:17 PM

Summary of Contents for FXHQ100MAVE

Page 1: ...ES DE LA INSTALACI N CONSERVE ESTE MANUAL PARA POSIBLES CONSULTAS FUTURAS PRIMA DELL INSTALLAZIONE LEGGERE ATTENTAMENTE LE PRESENTI ISTRUZIONI CONSERVARE IL PRESENTE MANUALE IN UN LUOGO FACILMENTE ACC...

Page 2: ...0MVE FXSQ25MVE FXSQ32MVE FXSQ40MVE FXSQ50MVE FXSQ63MVE FXSQ80MVE FXSQ100MVE FXSQ125MVE FXKQ25MVE FXKQ32MVE FXKQ40MVE FXKQ63MVE FXAQ20MVE FXAQ25MVE FXAQ32MVE FXAQ40MVE FXAQ50MVE FXAQ63MVE FXUQ71MV1 FXU...

Page 3: ...a foundation that can withstand its mass Insufficient strength may result in the air conditioner falling down and causing injury In addition it may lead to vibration of indoor units and cause unpleas...

Page 4: ...the paper pattern For the installation of an outdoor unit refer to the installation manual attached to the outdoor unit Do not install or operate the unit in rooms mentioned below Laden with mineral o...

Page 5: ...alled on ceilings up to 3 5 m in height However if the ceiling is higher than 2 7m the remote control will have to be set locally Refer to 11 FIELD SETTING on page 12 3 Use suspension bolts for instal...

Page 6: ...e suction grille opened Holding the knob on the back of suction grille pull to the front direction to remove Refer to Fig 4 2 Detach the dressing boards left and right Remove the side panel fixing scr...

Page 7: ...is tilted to the left or to the left and back Place it level or tilt it slightly to the left or the back Within 1 CAUTION Setting the unit at an angle opposite to the drain piping might cause leaks 6...

Page 8: ...indoor unit The refrigerant is pre charged in the outdoor unit When connecting the pipings to the air conditioner make sure to use a spanner and a torque wrench as shown in Fig 16 For the dimension of...

Page 9: ...t piping Once this is done con nect the indoor unit with a flared or a flanged connection Nitrogen should be set to 0 02 MPa with a pressure reducing valve if brazing while inserting nitrogen into the...

Page 10: ...according to the procedure shown below Select converging drain pipes whose gauge is suitable for the operating capacity of the unit 2 Confirm that smooth drainage is achieved after the pip ing work A...

Page 11: ...WIRINGS Method of wiring power supply units and connecting remote controller wiring Refer to Fig 26 Power supply wiring Hold the electric parts box lid and loosen the anchoring screws 2 pc then remove...

Page 12: ...is used it may damage the screw head and a proper tightening cannot be carried out If a terminal is over tightened it may be damaged Refer to the table shown below for tightening torque of terminals...

Page 13: ...r to Fig 30 and 8 3 9 4 FOR REMOTE CONTROL FORCED OFF AND ON OFF OPERATION 1 Wire specifications and how to perform wiring Connect input from outside to terminals T1 and T2 of the terminal block for r...

Page 14: ...in the field set mode select mode No 12 then set the first code switch No to 1 Then set second code position No to 01 for FORCED OFF and 02 for ON OFF OPERATION FORCED OFF at factory set 12 TEST OPER...

Page 15: ...1511 HT 3P172532 7B EM02A086D 00_CV_3P172532 7B fm Page 2 Monday August 31 2015 5 20 PM...

Reviews: