10. INSTALLATION OF THE SUCTION 

GRILLE AND THE AIR FILTER

Install side panel and suction grille properly in the order oppo-
site to detachment.

11. FIELD SETTING

Make sure the electric parts box lids are closed on the 
indoor and outdoor units.
Field setting must be made from the remote controller in 
accordance with the installation condition.

• Setting can be made by changing the “Mode No.”, “FIRST 

CODE NO.”, and “SECOND CODE NO.”.

• For setting and operation, refer to the “FIELD SETTING” in 

the installation manual of the remote controller.

11-1 Setting ceiling height

• Select the SECOND CODE NO. that corresponds to the ceil-

ing height. (Refer to Table 4). 
(SECOND CODE NO. is factory set to “01” for a ceiling 
height of 2.7m or less.)

Table 4

11-2 Setting air filter sign

• Remote controllers are equipped with liquid crystal display 

air filer signs to display the time to clean air filters.

• Change the SECOND CODE NO. according to Table 5 

depending on the amount of dirt or dust in the room.
(SECOND CODE NO. is factory set to “01” for filter contam-
ination-light.)

Table 5

When using wireless remote controllers

• When using wireless remote controllers, wireless remote 

controller address setting is necessary. Refer to the installa-
tion manual attached to the wireless remote controller for 
setting instructions.

• Set the remote controller to the field set mode. For 

details, refer to the “HOW TO SET IN THE FIELD”, in the 
remote controller manual. 

• When in the field set mode, select mode No. 12, then set 

the first code (switch) No. to “1”. Then set second code 
(position) No. to “01” for FORCED OFF and “02” for ON/
OFF OPERATION. (FORCED OFF at factory set)

12. TEST OPERATION 

Refer to the installation manual of the outdoor unit.

• The operation lamp of the remote controller will flash when 

an malfunction occurs. Check the malfunction code on the 
liquid crystal display to identify the point of trouble. An expla-
nation of malfunction codes and the corresponding trouble is 
provided in “CAUTION FOR SERVICING” of the outdoor 
unit.
If any of the items in Table 6 are displayed, there may be a 
problem with the wiring or power, so check the wiring again.

Table 6

Ceiling height (m)

Mode No.

FIRST CODE 

NO.

SECOND CODE 

NO.

2.7 or less

13 (23)

0

01

2.7- 3.5

02

Setting

Spacing time of 

display air 

filter sign 

(long life type)

Mode 

No.

FIRST 
CODE 

NO.

SECOND 

CODE 

NO.

Air filter 

contamination-light

Approx. 2500 hrs

10 (20)

0

01

Air filter 

contamination-heavy

Approx. 1250 hrs

02

SETTING

Mode 
No.

SECOND
CORD NO.

FIRST 
CORD NO.

FIELD SET 
MODE

Remote control display

Content

“Concentrated Manage-
ment” is lit up

• There is a short circuit at the FORCED 

OFF terminals (T1, T2)

“U4” is lit up

“UH” is lit up

• The power on the outdoor unit is off.
• The outdoor unit has not been wired for 

power supply.

• Incorrect wiring for the transmission 

wiring and / or FORCED OFF wiring.

No display

• The power on the indoor unit is off.
• The indoor unit has not been wired for 

power supply.

• Incorrect wiring for the remote control-

ler wiring, the transmission wiring and / 
or the FORCED OFF wiring.

01_EN_3P172532-7B.fm  Page 12  Wednesday, October 14, 2015  6:17 PM

Summary of Contents for FXHQ100MAVE

Page 1: ...ES DE LA INSTALACI N CONSERVE ESTE MANUAL PARA POSIBLES CONSULTAS FUTURAS PRIMA DELL INSTALLAZIONE LEGGERE ATTENTAMENTE LE PRESENTI ISTRUZIONI CONSERVARE IL PRESENTE MANUALE IN UN LUOGO FACILMENTE ACC...

Page 2: ...0MVE FXSQ25MVE FXSQ32MVE FXSQ40MVE FXSQ50MVE FXSQ63MVE FXSQ80MVE FXSQ100MVE FXSQ125MVE FXKQ25MVE FXKQ32MVE FXKQ40MVE FXKQ63MVE FXAQ20MVE FXAQ25MVE FXAQ32MVE FXAQ40MVE FXAQ50MVE FXAQ63MVE FXUQ71MV1 FXU...

Page 3: ...a foundation that can withstand its mass Insufficient strength may result in the air conditioner falling down and causing injury In addition it may lead to vibration of indoor units and cause unpleas...

Page 4: ...the paper pattern For the installation of an outdoor unit refer to the installation manual attached to the outdoor unit Do not install or operate the unit in rooms mentioned below Laden with mineral o...

Page 5: ...alled on ceilings up to 3 5 m in height However if the ceiling is higher than 2 7m the remote control will have to be set locally Refer to 11 FIELD SETTING on page 12 3 Use suspension bolts for instal...

Page 6: ...e suction grille opened Holding the knob on the back of suction grille pull to the front direction to remove Refer to Fig 4 2 Detach the dressing boards left and right Remove the side panel fixing scr...

Page 7: ...is tilted to the left or to the left and back Place it level or tilt it slightly to the left or the back Within 1 CAUTION Setting the unit at an angle opposite to the drain piping might cause leaks 6...

Page 8: ...indoor unit The refrigerant is pre charged in the outdoor unit When connecting the pipings to the air conditioner make sure to use a spanner and a torque wrench as shown in Fig 16 For the dimension of...

Page 9: ...t piping Once this is done con nect the indoor unit with a flared or a flanged connection Nitrogen should be set to 0 02 MPa with a pressure reducing valve if brazing while inserting nitrogen into the...

Page 10: ...according to the procedure shown below Select converging drain pipes whose gauge is suitable for the operating capacity of the unit 2 Confirm that smooth drainage is achieved after the pip ing work A...

Page 11: ...WIRINGS Method of wiring power supply units and connecting remote controller wiring Refer to Fig 26 Power supply wiring Hold the electric parts box lid and loosen the anchoring screws 2 pc then remove...

Page 12: ...is used it may damage the screw head and a proper tightening cannot be carried out If a terminal is over tightened it may be damaged Refer to the table shown below for tightening torque of terminals...

Page 13: ...r to Fig 30 and 8 3 9 4 FOR REMOTE CONTROL FORCED OFF AND ON OFF OPERATION 1 Wire specifications and how to perform wiring Connect input from outside to terminals T1 and T2 of the terminal block for r...

Page 14: ...in the field set mode select mode No 12 then set the first code switch No to 1 Then set second code position No to 01 for FORCED OFF and 02 for ON OFF OPERATION FORCED OFF at factory set 12 TEST OPER...

Page 15: ...1511 HT 3P172532 7B EM02A086D 00_CV_3P172532 7B fm Page 2 Monday August 31 2015 5 20 PM...

Reviews: