• Multiple number of indoor units are connected to one outdoor 

unit. Name each indoor unit as A-unit, B-unit ….. and the like. 
When these indoor units are wired to the outdoor unit and the 
BS unit, always wire the indoor unit to the terminal indicated 
with the same symbol on the terminal block. If the wiring and 
the piping are connected to the different indoor units and 
operated, it will result in malfunction.

• Make sure to earth the air conditioner. 

Earthing resistance should be according to applicable legislation.

• Do not connect the earth wiring to gas or water pipings, light-

ning conductor or telephone earth wiring.

• Gas piping ........... Ignition or explosion may occur if the 

gas leaks.

• Water piping.......... Hard vinyl tubes are not effective earths.
• Lightning conductor or telephone earth wiring ...............

Electric potential may rise abnormally if struck by a light-
ning bolt.

• For electric wiring work, refer to also the "WIRING DIA-

GRAM" attached to the control box lid.

• Carry out wiring between the outdoor units, indoor units and 

the remote controllers according to the wiring diagram.

• Carry out installation and wiring of the remote controller accord-

ing to the "installation manual" attached to the remote controller.

• Do not touch the Printed Circuit Board assembly. It may 

cause malfunction.

8-2

ELECTRICAL CHARACTERISTICS

MCA: Min. Circuit Amps (A);

MFA: Max. Fuse Amps (A) 

kW: Fan Motor Rated Output (kW);FLA: Full Load Amps (A)

8-3

SPECIFICATIONS FOR FIELD SUPPLIED 
FUSES AND WIRE 

Allowable length of transmission wiring between indoor/outdoor 
units and between the indoor unit and the remote controller is as 
follows. 

(1) Outdoor unit – Indoor unit: 

Max. 1000 m (Total wiring length: 2000 m) 

(2) Indoor unit – Remote controller: 

Max. 500 m

NOTE

NOTE

NOTE

NOTE

1.

Shows only in case of protected piping. Use H07RN-F in 
case of no protection.

2.

Vinyl cord with sheath or cable (Insulated thickness : 1mm 
or more)

9. WIRING EXAMPLE AND HOW TO SET 

THE REMOTE CONTROLLER

9-1

HOW TO CONNECT WIRINGS 

Method of wiring power supply, units and connecting 

remote controller wiring

〉 

(Refer to Fig. 26)

Power supply wiring

Hold the electric parts box lid and loosen the anchoring 
screws (2 pc.), then remove the electric parts box lid. Align 
the phase and connect the wire to the power terminal block 
(6P) inside the electric parts box. After connecting, use the 
included clamps (4) to bind the wire, together with the ground 
wire, to the anchor. 

(Refer to Fig. 27)

Remote controller wiring and transmission wiring

Hold the electric parts box lid and loosen the anchoring 
screws (2 pc.), then remove the electric parts box lid. Con-
nect the wires to the power terminal block (6P) inside the 
electric parts box. After connecting, use the included clamps 
(4) to bind the remote controller wire, together with the trans-
mission wire, to the anchor. 

(Refer to Fig. 27)

Units

Power supply

Fan motor

Model

Hz

Volts

Voltage 

range

MCA

MFA

kW

FLA

FXHQ32M(A)VE

50

220-240

Max. 264
Min.  198

0.8

15

0.062 0.6

FXHQ63M(A)VE

0.8

15

0.062 0.6

FXHQ100M(A)VE

0.9

15

0.130 0.7

FXHQ32M(A)VE

60

220

Max. 242
Min.  198

0.9

15

0.062 0.7

FXHQ63M(A)VE

0.9

15

0.062 0.7

FXHQ100M(A)VE

1.3

15

0.130 1.0

Model

Power supply wiring

Remote controller 

wiring

Transmission wiring

Field 

fuses  Wire

Size

Wire

Size

FXHQ32M(A)VE

15A

H05VV-

U3G

NOTE 1)

Wiring size and 

length must 
comply with 

local codes.

Sheathed wire

(2 wire)

NOTE 2)

0.75 - 

1.25 
mm

2

FXHQ63M(A)VE

FXHQ100M(A)VE

Earth
terminal

Refer to Fig. 27

Rear 
penetration lid

Earth wiring (*)
(Field wiring)

Power supply 
wiring (*)
(Field wiring)

Electric 
parts box

Terminal block
for remote 
controller (6P)

Power supply terminal block (2P)

Electric parts
box lid fixation 
screw (2 P)

Fig. 26

Electric parts box lid

Electric wiring 
diagram plate

Remote controller wiring 
and transmission wiring (*)
(Field wiring)

How to connect power supply 
terminal block (2P)

power supply 
cord

power supply

L

N

Fastener

Clamp (4) (accessory)

Clamp (4) 
(accessory)

Earth wiring

After securing the 
cramp material 
to the bracket, 
cut off any extra 
material.

Remote controller wiring and 
transmission wiring

Fastener

Power supply 
wiring

Fig. 27

01_EN_3P172532-7B.fm  Page 9  Wednesday, October 14, 2015  6:17 PM

Summary of Contents for FXHQ100MAVE

Page 1: ...ES DE LA INSTALACI N CONSERVE ESTE MANUAL PARA POSIBLES CONSULTAS FUTURAS PRIMA DELL INSTALLAZIONE LEGGERE ATTENTAMENTE LE PRESENTI ISTRUZIONI CONSERVARE IL PRESENTE MANUALE IN UN LUOGO FACILMENTE ACC...

Page 2: ...0MVE FXSQ25MVE FXSQ32MVE FXSQ40MVE FXSQ50MVE FXSQ63MVE FXSQ80MVE FXSQ100MVE FXSQ125MVE FXKQ25MVE FXKQ32MVE FXKQ40MVE FXKQ63MVE FXAQ20MVE FXAQ25MVE FXAQ32MVE FXAQ40MVE FXAQ50MVE FXAQ63MVE FXUQ71MV1 FXU...

Page 3: ...a foundation that can withstand its mass Insufficient strength may result in the air conditioner falling down and causing injury In addition it may lead to vibration of indoor units and cause unpleas...

Page 4: ...the paper pattern For the installation of an outdoor unit refer to the installation manual attached to the outdoor unit Do not install or operate the unit in rooms mentioned below Laden with mineral o...

Page 5: ...alled on ceilings up to 3 5 m in height However if the ceiling is higher than 2 7m the remote control will have to be set locally Refer to 11 FIELD SETTING on page 12 3 Use suspension bolts for instal...

Page 6: ...e suction grille opened Holding the knob on the back of suction grille pull to the front direction to remove Refer to Fig 4 2 Detach the dressing boards left and right Remove the side panel fixing scr...

Page 7: ...is tilted to the left or to the left and back Place it level or tilt it slightly to the left or the back Within 1 CAUTION Setting the unit at an angle opposite to the drain piping might cause leaks 6...

Page 8: ...indoor unit The refrigerant is pre charged in the outdoor unit When connecting the pipings to the air conditioner make sure to use a spanner and a torque wrench as shown in Fig 16 For the dimension of...

Page 9: ...t piping Once this is done con nect the indoor unit with a flared or a flanged connection Nitrogen should be set to 0 02 MPa with a pressure reducing valve if brazing while inserting nitrogen into the...

Page 10: ...according to the procedure shown below Select converging drain pipes whose gauge is suitable for the operating capacity of the unit 2 Confirm that smooth drainage is achieved after the pip ing work A...

Page 11: ...WIRINGS Method of wiring power supply units and connecting remote controller wiring Refer to Fig 26 Power supply wiring Hold the electric parts box lid and loosen the anchoring screws 2 pc then remove...

Page 12: ...is used it may damage the screw head and a proper tightening cannot be carried out If a terminal is over tightened it may be damaged Refer to the table shown below for tightening torque of terminals...

Page 13: ...r to Fig 30 and 8 3 9 4 FOR REMOTE CONTROL FORCED OFF AND ON OFF OPERATION 1 Wire specifications and how to perform wiring Connect input from outside to terminals T1 and T2 of the terminal block for r...

Page 14: ...in the field set mode select mode No 12 then set the first code switch No to 1 Then set second code position No to 01 for FORCED OFF and 02 for ON OFF OPERATION FORCED OFF at factory set 12 TEST OPER...

Page 15: ...1511 HT 3P172532 7B EM02A086D 00_CV_3P172532 7B fm Page 2 Monday August 31 2015 5 20 PM...

Reviews: