background image

8

 

PRECAUTIONS FOR DRAIN RAISING PIPE 

• Make sure the drain raising pipe height is no higher than

23-5/8 in..

• Place the drain raising pipe vertically and make sure it is no 

further than 11-3/4 in. from the unit.

 (Refer to Fig. 13)

 

PRECAUTIONS 

Drain piping connections

• Do not connect the drain piping directly to sewage pipes that 

smell of ammonia. The ammonia in the sewage might enter 
the indoor unit through the drain piping and corrode the heat 
exchanger.

• Do not twist or bend the drain hose (2), so that excessive 

force is not applied to it.
(This type of treatment may cause leaking.)

• If you are using central drain piping, follow the procedure

outlined in the figure 10.

• Select central drain piping of proper size according to the 

capacity of the connected unit.

(2) After piping work is finished, check drainage flows 

smoothly.

• Gradually insert approximately 1 L of water into the drain 

pan to check drainage in the manner described below.

Metal clamp (1)

Drain hose (2)

Tape

Fig. 11

Fig. 12

1/8 in.

Large sealing 
pad (5)

Metal clamp (1)

(accessory)

(accessory)

(accessory)

(accessory)

Drain raising pipe

Metal clamp (1) (accessory)

Drain hose (2) (accessory)

Ceiling slab

11-3/4 in. or less

Hanging bracket

Adjustable range

(23-5/8 in. or less)

(Field supply)

3-5 ft.

Fig. 13

CAUTION

• The electric wiring work shall be performed by qualified 

electricians.

• If workers not having the electrician qualification have per-

formed the electric wiring work, the steps 3 to 7 shall be 
performed after the 

TEST RUN

.

1. Remove the lid of the control box.  Connect the remote 

controller and power supply (single-phase, 60Hz 208-
230V) respectively to the terminal block and securely 
connect the ground also. (as shown in the figure below).

CAUTION

Securely clamp the cables with the clamps (9)(10) 
offered as accessories as shown in Fig. 14 so that ten-
sion will not be applied on the cable connection areas.

2. Confirm that the lid of the control box is closed before 

turning on the power.

3. Remove the inspection lid.

4. Gradually pour approximately 1 L of water from the water 

inlet into the drain pan to check drainage.

CAUTION

Be sure to prevent an external force from being exerted 
on the float switch. (This may cause breakage.)

5. Attach the inspection lid.

6. Perform the following operation using the remote control-

ler, and check drainage.

• Select the inspection/test operation button “

” 

using the remote controller.  The unit will engage the 
test operation. Press the operation selector button 

”, and select FAN OPERATION “

”.

• Press the ON/OFF button “

”. (The indoor fan and 

drain pump will operate.)

CAUTION

The fan will turn also at the same time. Take due care.
Do not touch the drain pump to prevent electric shock.

7. Make sure to use the remote controller in finishing the 

operation.

TEST

TRANSMISSION

WIRING

REMOTE

CNTRL

T1

F1

FORCED

OFF

P2

F2

P1

T2

TRANSMISSION

WIRING

REMOTE

CNTRL

T1

F1

FORCED

OFF

P2

F2

P1

T2

L

N

L2

L1

Water inlet

Portable pump

Inspection lid

Refrigerant pipes

Bucket

Service drain hole

Drain outlet

(with rubber cap)

Indoor PCboard 

(ASSY)

Terminal block

Terminal block

Remote controller 
terminal connection 
method

Power supply: 
Single phase,
60Hz,208-230V
Power terminal 
connection 
method

Summary of Contents for FXDQ07MVJU

Page 1: ...MVJU FXDQ09MVJU FXDQ12MVJU FXDQ18MVJU FXDQ24MVJU SYSTEM Inverter Air Conditioners INSTALLATION MANUAL Read these instructions carefully before installation Keep this manual in a handy place for future...

Page 2: ...ury or death Do not ground units to water pipes telephone wires or lightning rods because incomplete grounding could cause a severe shock hazard resulting in severe injury or death and to gas pipes be...

Page 3: ...t the customer to keep the area around the unit clean NOTE Install the indoor and outdoor units power supply wiring and connecting wires at least 3 5ft away from televisions or radios in order to prev...

Page 4: ...mid 6 Name Screwsforduct flanges 7 Washerforhanger bracket 8 Clamp Washer fixing plate 11 Quantity 1 set 8 pcs 1 set 4 pcs Shape Large 9 8 pcs small 10 4 pcs Name Conduit mounting plate Screw for con...

Page 5: ...er to prevent image interference or noise Depending on the radio waves a distance of 3 5 ft may not be sufficient enough to eliminate the noise 2 Use suspension bolts for installation Check whether th...

Page 6: ...he provided accessories and specified parts desig nated by our company 1 Install the indoor unit temporarily Attach the hanger bracket to the suspension bolt Be sure to fix it securely by using a nut...

Page 7: ...lare and cause leaks Be careful for oil not to adhere to any portions other than a flare part If oil adhere to resin parts etc there is a pos sibility of damaging by deterioration Refer to Table 2 if...

Page 8: ...ON The connection opening on the drain piping may vary depending on the model so check the model name and use the right method for that model Make sure all water is out before making the duct connecti...

Page 9: ...1 Remove the lid of the control box Connect the remote controller and power supply single phase 60Hz 208 230V respectively to the terminal block and securely connect the ground also as shown in the fi...

Page 10: ...ng and piping between the outdoor unit and an indoor unit are mismatched the system may cause a malfunction Install a wiring interrupter or ground fault circuit interrupter for the power wiring Make s...

Page 11: ...he entire system Connecting electrical wiring remote controller wiring and transmission wiring Refer to Fig 15 Power supply wiring and Ground wire Remove the control box lid Next pull the wires into t...

Page 12: ...troller PC board is attached to the upper part of remote controller Indoor unit A Indoor unit B Most downstream Indoor unit Power supply single phase 60Hz 208 230V Power supply single phase 60Hz 208 2...

Page 13: ...tly make sure the customer keeps the Field Settings manual along with the operating manual in a safe place 11 1 SETTING THE STATIC PRESSURE SELECTION Select the SECOND CODE NO for the resistance of th...

Page 14: ...stal display to identify the point of trouble An explanation of malfunction codes and the correspond ing trouble is provided in CAUTION FOR SERVICING of the outdoor unit If the display shows any of th...

Page 15: ...0601 HT 3PN06240 4E EM05A056 FS...

Reviews: