background image

2

A high surge current from lightning or other sources may 
cause damage to the air conditioner.

Do not touch the switch with wet fingers. 

Touching a switch with wet fingers can cause electric shock. 

Be sure to install an earth leakage breaker.

Failure to install an earth leakage breaker may result in elec-
tric shocks, or fire.

Do not install the air conditioner in the following locations:

(a) where a mineral oil mist or an oil spray or vapor is pro-

duced, for example in a kitchen 
Plastic parts may deteriorate and fall off or result in water 
leakage.

(b) where corrosive gas, such as sulfurous acid gas, is pro-

duced 
Corroding copper pipes or soldered parts may result in 
refrigerant leakage.

(c) near machinery emitting electromagnetic waves 

Electromagnetic waves may disturb the operation of the 
control system and result in a malfunction of the equipment.

Heat exchanger fins are sharp enough to cut.

To avoid injury wear gloves or cover the fins when working 
around them.

Use of unspecified parts could lead to the unit falling, 
leaks and, in worse cases, electric shock or fire.

Entrust installation to the place of purchase or a quali-
fied serviceman.

Improper installation could lead to leaks and, in worse cases, 
electric shock or fire.

Refrigerant pipes may be very hot or very cold during or 
immediately after operation.

Touching them could result in burns or frostbite. To avoid 
injury give the pipes time to return to normal temperature or, 
if you must touch them, be sure to wear proper gloves.

CAUTION

While following the instructions in this installation man-
ual, install drain piping in order to ensure proper drain-
age and insulate piping in order to prevent condensation.

Improper drain piping may result in water leakage and prop-
erty damage.

Be very careful about product transportation.

Some products use PP bands for packaging. Do not use any 
PP bands for a means of transportation. It is dangerous.

Do not turn off the power immediately after stopping 
operation.

Always wait at least five minutes before turning off the power. 
Otherwise, water leakage and trouble may occur.

Make sure to provide for adequate measures in order to 
prevent that the outdoor unit be used as a shelter by 
small animals.

Small animals making contact with electrical parts can cause 
malfunctions, smoke or fire. Please instruct the customer to 
keep the area around the unit clean.

NOTE

Install the indoor and outdoor units, power supply wiring 
and connecting wires at least 3.5ft. away from televisions 
or radios in order to prevent image interference or noise.

(Depending on the radio waves, a distance of 3.5ft. may not 
be sufficient enough to eliminate the noise.)

Remote controller (wireless kit) transmitting distance 
can result shorter than expected in rooms with elec-
tronic fluorescent lamps. (inverter or rapid start types)

Install the indoor unit as far away from fluorescent lamps as 
possible.

Dismantling of the unit, treatment of the refrigerant, oil 
and eventual other parts, should be done in accordance 
with the relevant local and national regulations. 

2.

BEFORE INSTALLATION

WARNING

• Entrust installation to the place of purchase or a qualified ser-

viceman. Improper installation could lead to leaks and, in 
worse cases, electric shock or fire.

• Use of unspecified parts could lead to the unit falling, leaks 

and, in worse cases, electric shock or fire.

NOTE

• Be sure to read this manual before installing the indoor unit.

• Be sure to mount an air filter (part to be procured in the field) in 

the suction air passage in order to prevent water leaking, etc.

The accessories needed for installation must be retained in 
your custody until the installation work is completed. Do 
not discard them!

1. Decide upon a line of transport.
2. Leave the unit inside its packaging while moving, until reach-

ing the installation site. Where unpacking is unavoidable, 
use a sling of soft material or protective plates together with 
a rope when lifting, to avoid damage or scratches to the unit.

When moving the unit while removing it from the packing 
case, be sure to lift it by the four hanger brackets. Avoid 
putting any pressure on other parts especially the refriger-
ant piping.

Be sure to check the type of R410A refrigerant to be used 
before installing the unit.
(Using an incorrect refrigerant will prevent normal opera-
tion of the unit.)

For the installation of an outdoor unit, refer to the installation 
manual attached to the outdoor unit.

2-1 PRECAUTIONS

• Be sure to instruct customers how to properly operate the 

unit (operating different functions, and adjusting the temper-
ature ) by having them carry out operations themselves while 
looking at the operation manual.

• Do not install in locations where the air contains high levels of 

salt such as that near the ocean and where voltage fluctuates 
greatly such as that in factories, or in vehicles or vessels.

Summary of Contents for FXDQ07MVJU

Page 1: ...MVJU FXDQ09MVJU FXDQ12MVJU FXDQ18MVJU FXDQ24MVJU SYSTEM Inverter Air Conditioners INSTALLATION MANUAL Read these instructions carefully before installation Keep this manual in a handy place for future...

Page 2: ...ury or death Do not ground units to water pipes telephone wires or lightning rods because incomplete grounding could cause a severe shock hazard resulting in severe injury or death and to gas pipes be...

Page 3: ...t the customer to keep the area around the unit clean NOTE Install the indoor and outdoor units power supply wiring and connecting wires at least 3 5ft away from televisions or radios in order to prev...

Page 4: ...mid 6 Name Screwsforduct flanges 7 Washerforhanger bracket 8 Clamp Washer fixing plate 11 Quantity 1 set 8 pcs 1 set 4 pcs Shape Large 9 8 pcs small 10 4 pcs Name Conduit mounting plate Screw for con...

Page 5: ...er to prevent image interference or noise Depending on the radio waves a distance of 3 5 ft may not be sufficient enough to eliminate the noise 2 Use suspension bolts for installation Check whether th...

Page 6: ...he provided accessories and specified parts desig nated by our company 1 Install the indoor unit temporarily Attach the hanger bracket to the suspension bolt Be sure to fix it securely by using a nut...

Page 7: ...lare and cause leaks Be careful for oil not to adhere to any portions other than a flare part If oil adhere to resin parts etc there is a pos sibility of damaging by deterioration Refer to Table 2 if...

Page 8: ...ON The connection opening on the drain piping may vary depending on the model so check the model name and use the right method for that model Make sure all water is out before making the duct connecti...

Page 9: ...1 Remove the lid of the control box Connect the remote controller and power supply single phase 60Hz 208 230V respectively to the terminal block and securely connect the ground also as shown in the fi...

Page 10: ...ng and piping between the outdoor unit and an indoor unit are mismatched the system may cause a malfunction Install a wiring interrupter or ground fault circuit interrupter for the power wiring Make s...

Page 11: ...he entire system Connecting electrical wiring remote controller wiring and transmission wiring Refer to Fig 15 Power supply wiring and Ground wire Remove the control box lid Next pull the wires into t...

Page 12: ...troller PC board is attached to the upper part of remote controller Indoor unit A Indoor unit B Most downstream Indoor unit Power supply single phase 60Hz 208 230V Power supply single phase 60Hz 208 2...

Page 13: ...tly make sure the customer keeps the Field Settings manual along with the operating manual in a safe place 11 1 SETTING THE STATIC PRESSURE SELECTION Select the SECOND CODE NO for the resistance of th...

Page 14: ...stal display to identify the point of trouble An explanation of malfunction codes and the correspond ing trouble is provided in CAUTION FOR SERVICING of the outdoor unit If the display shows any of th...

Page 15: ...0601 HT 3PN06240 4E EM05A056 FS...

Reviews: