background image

6

(4) Tighten the upper nut.

6.

REFRIGERANT PIPING WORK

For refrigerant piping of outdoor units, see the installation 

manual attached to the outdoor unit.

Execute heat insulation work completely on both sides of 

the gas piping and the liquid piping. Otherwise, a water 
leakage can result sometimes.
Use insulation that can withstand temperatures of at least 
250°F. Reinforce the insulation on the refrigerant piping 
according to the installation environment. If the temperature 
above the ceiling might reach 86°F or the humidity RH80%. 
Condensation may form on the surface of the insulation.

CAUTION

Follow the points at below.

• Use a pipe cutter and flare suitable for the type of refrigerant.
• Apply ester oil or ether oil to the flare section when using a 

flare connection.

• Only use the flare nuts included with the unit. Using different 

flare nuts may cause the refrigerant to leak.

• To prevent dust, moisture or other foreign matter from infil-

trating the piping, either pinch the end or cover it with tape.

• Do not allow anything other than the designated refrigerant to 

get mixed into the refrigerant circuit, such as air, etc. If any 
refrigerant gas leaks while working on the unit, ventilate the 
room thoroughly right away.

(1) Connect the piping.

• The outdoor unit is charged with refrigerant.
• Be sure to use both a spanner and torque wrench together, 

as shown in the drawing, when connecting or disconnecting 
pipes to/from the unit. 

(Refer to Fig. 6)

• Refer to the Table 1 for the dimensions of flare nut spaces.
• Apply ester oil or ether oil to flare section (both inside and 

out) when using flare nut connections and then turn 3 or 4 
times by hand. 

(Refer to Fig. 7)

• Refer to Table 1 for tightening torque.

Table 1

CAUTION

Overtightening may damage the flare and cause leaks.
Be careful for oil not to adhere to any portions other than 
a flare part. If oil adhere to resin parts etc., there is a pos-
sibility of damaging by deterioration.

• Refer to Table 2 if no torque wrench is available.

Using a wrench to tighten flare nuts causes the tightening 
torque to suddenly grow much tighter after a certain point.
From there, tighten the nut further by the appropriate angle 
listed in Table 2.

(2) After the work is finished, make sure to check that 

there is no gas leak.

(3) After checking for gas leaks, be sure to insulate the 

pipe connections referring to Fig. 8.

• Insulate using the insulation for fitting (3) (4) included with 

the liquid and gas pipes. Besides, make sure the insula-
tion for fitting (3) (4) on the liquid and gas piping has its 
seams facing up.
(Tighten both edges with clamp (9).)

• For the gas piping, wrap the mid. sealing pad (6) over the 

insulation for fitting (4) (flare nut part).

CAUTION

Be sure to insulate any field piping all the way to the piping 
connection inside the unit. Any exposed piping may cause 
condensation or burns if touched.

Vinyl tube

Level

Torque wrench

Spanner

Ester oil or ether oil

Piping union

Flare nut

Fig. 6

Fig. 7

Pipe size 

(in.)

Tightening torque 

(ft.lbf)

Flare dimensions A

(in.)

Flare shape (in.)

φ

1/4

10.4–12.7

0.342–0.358

φ

3/8

24.1–29.4

0.504–0.520

φ

1/2

36.5–44.5

0.638–0.654

φ

5/8

45.6–55.6

0.760–0.776

R0.016-0.031

A

90˚± 2˚ 

45˚±2˚

Gas pipe

Piping insulation 
material (main unit)

Attach to base

Flare nut connection

Turn seams up

Mid. sealing pad (6) (accessory)

Insulation for fitting (4) (accessory)

Gas Piping Insulation Procedure

Liquid Piping Insulation Procedure

(accessory)

Clamp (9)

Piping insulation material
(Field supply)

Clamp (9) (accessory)

Flare nut connection

Turn seams up

Piping insulation material
(Field supply)

Piping insulation material 
(main unit)

Attach to base

Main unit

Fig. 8

Liquid pipe

Insulation for fitting (3) (accessory)

Wrap over the top of 
the flare nut connection.

Main unit

Summary of Contents for FXDQ07MVJU

Page 1: ...MVJU FXDQ09MVJU FXDQ12MVJU FXDQ18MVJU FXDQ24MVJU SYSTEM Inverter Air Conditioners INSTALLATION MANUAL Read these instructions carefully before installation Keep this manual in a handy place for future...

Page 2: ...ury or death Do not ground units to water pipes telephone wires or lightning rods because incomplete grounding could cause a severe shock hazard resulting in severe injury or death and to gas pipes be...

Page 3: ...t the customer to keep the area around the unit clean NOTE Install the indoor and outdoor units power supply wiring and connecting wires at least 3 5ft away from televisions or radios in order to prev...

Page 4: ...mid 6 Name Screwsforduct flanges 7 Washerforhanger bracket 8 Clamp Washer fixing plate 11 Quantity 1 set 8 pcs 1 set 4 pcs Shape Large 9 8 pcs small 10 4 pcs Name Conduit mounting plate Screw for con...

Page 5: ...er to prevent image interference or noise Depending on the radio waves a distance of 3 5 ft may not be sufficient enough to eliminate the noise 2 Use suspension bolts for installation Check whether th...

Page 6: ...he provided accessories and specified parts desig nated by our company 1 Install the indoor unit temporarily Attach the hanger bracket to the suspension bolt Be sure to fix it securely by using a nut...

Page 7: ...lare and cause leaks Be careful for oil not to adhere to any portions other than a flare part If oil adhere to resin parts etc there is a pos sibility of damaging by deterioration Refer to Table 2 if...

Page 8: ...ON The connection opening on the drain piping may vary depending on the model so check the model name and use the right method for that model Make sure all water is out before making the duct connecti...

Page 9: ...1 Remove the lid of the control box Connect the remote controller and power supply single phase 60Hz 208 230V respectively to the terminal block and securely connect the ground also as shown in the fi...

Page 10: ...ng and piping between the outdoor unit and an indoor unit are mismatched the system may cause a malfunction Install a wiring interrupter or ground fault circuit interrupter for the power wiring Make s...

Page 11: ...he entire system Connecting electrical wiring remote controller wiring and transmission wiring Refer to Fig 15 Power supply wiring and Ground wire Remove the control box lid Next pull the wires into t...

Page 12: ...troller PC board is attached to the upper part of remote controller Indoor unit A Indoor unit B Most downstream Indoor unit Power supply single phase 60Hz 208 230V Power supply single phase 60Hz 208 2...

Page 13: ...tly make sure the customer keeps the Field Settings manual along with the operating manual in a safe place 11 1 SETTING THE STATIC PRESSURE SELECTION Select the SECOND CODE NO for the resistance of th...

Page 14: ...stal display to identify the point of trouble An explanation of malfunction codes and the correspond ing trouble is provided in CAUTION FOR SERVICING of the outdoor unit If the display shows any of th...

Page 15: ...0601 HT 3PN06240 4E EM05A056 FS...

Reviews: