11-3 SETTING THE FILTER SIGN DISPLAY INTERVAL

• Explain the following to the customer if the filter dirt settings 

have been changed.

• The filter sign display time is set to 2500 hours 

(equivalent to 1 year’s use) when shipped.

• The settings can be changed to not display.
• When installing the unit in a place with much dusts, set the fil-

ter sign display time to shorter intervals (1,250 hours).

• Explain it to the customer that the filter needs to be cleaned 

regularly to prevent clogging and also the time that is set.

11-4 SETTINGS FOR SEPARATELY SOLD 

ACCESSORIES

• See the instruction manuals included with separately sold 

accessories for the necessary settings.

 When using a wireless remote controller 

• A wireless remote controller address needs to be set when 

using a wireless remote controller. See the installation man-
ual included with the wireless remote controller for details on 
how to make the settings.

(3) Perform a test run according to the outdoor unit’s 

installation manual.

• The operation lamp of the remote controller will flash 

when a malfunction occurs. Check the malfunction code 
on the liquid crystal display to identify the point of trouble. 
An explanation of malfunction codes and the correspond-
ing trouble is provided in “CAUTION FOR SERVICING” of 
the outdoor unit.
If the display shows any of the following, there is a possi-
bility that the wiring was done incorrectly or that the 
power is not on, so check again.

CAUTION

• Always stop the test run using the remote controller to stop 

operation.

(4) After finishing the test run, make sure to check drain-

age in the drain pump according to “7. DRAIN PIPING 
WORK”.

Mode No.

FIRST CODE NO.

SECOND 

CODE NO.

01

02

10 (20)

0

Filter dirt

low

high

1 (low/high)

Displayed time

(units: hours)

2500/

1250

10000/

5000

3

Filter sign display

ON

OFF

Remote control display

Content

”  display

• There is a short circuit at the FORCED 

OFF terminals (T1, T2).

”  display

• The test-run has not been performed.

”  display

”  display

• The power on the outdoor unit is off.
• The outdoor unit has not been wired for 

power supply.

• Wiring is incorrect for the transmission 

wiring and / or FORCED OFF wiring.

• The transmission wiring is cut.

”  display

• Reversed transmission wiring

No display

• The power on the indoor unit is off.
• The indoor unit has not been wired for 

power supply.

• Wiring is incorrect for the remote con-

troller wiring, the transmission wiring 
and / or the FORCED OFF wiring.

• The remote controller wiring is cut.

Summary of Contents for FXDQ07MVJU

Page 1: ...MVJU FXDQ09MVJU FXDQ12MVJU FXDQ18MVJU FXDQ24MVJU SYSTEM Inverter Air Conditioners INSTALLATION MANUAL Read these instructions carefully before installation Keep this manual in a handy place for future...

Page 2: ...ury or death Do not ground units to water pipes telephone wires or lightning rods because incomplete grounding could cause a severe shock hazard resulting in severe injury or death and to gas pipes be...

Page 3: ...t the customer to keep the area around the unit clean NOTE Install the indoor and outdoor units power supply wiring and connecting wires at least 3 5ft away from televisions or radios in order to prev...

Page 4: ...mid 6 Name Screwsforduct flanges 7 Washerforhanger bracket 8 Clamp Washer fixing plate 11 Quantity 1 set 8 pcs 1 set 4 pcs Shape Large 9 8 pcs small 10 4 pcs Name Conduit mounting plate Screw for con...

Page 5: ...er to prevent image interference or noise Depending on the radio waves a distance of 3 5 ft may not be sufficient enough to eliminate the noise 2 Use suspension bolts for installation Check whether th...

Page 6: ...he provided accessories and specified parts desig nated by our company 1 Install the indoor unit temporarily Attach the hanger bracket to the suspension bolt Be sure to fix it securely by using a nut...

Page 7: ...lare and cause leaks Be careful for oil not to adhere to any portions other than a flare part If oil adhere to resin parts etc there is a pos sibility of damaging by deterioration Refer to Table 2 if...

Page 8: ...ON The connection opening on the drain piping may vary depending on the model so check the model name and use the right method for that model Make sure all water is out before making the duct connecti...

Page 9: ...1 Remove the lid of the control box Connect the remote controller and power supply single phase 60Hz 208 230V respectively to the terminal block and securely connect the ground also as shown in the fi...

Page 10: ...ng and piping between the outdoor unit and an indoor unit are mismatched the system may cause a malfunction Install a wiring interrupter or ground fault circuit interrupter for the power wiring Make s...

Page 11: ...he entire system Connecting electrical wiring remote controller wiring and transmission wiring Refer to Fig 15 Power supply wiring and Ground wire Remove the control box lid Next pull the wires into t...

Page 12: ...troller PC board is attached to the upper part of remote controller Indoor unit A Indoor unit B Most downstream Indoor unit Power supply single phase 60Hz 208 230V Power supply single phase 60Hz 208 2...

Page 13: ...tly make sure the customer keeps the Field Settings manual along with the operating manual in a safe place 11 1 SETTING THE STATIC PRESSURE SELECTION Select the SECOND CODE NO for the resistance of th...

Page 14: ...stal display to identify the point of trouble An explanation of malfunction codes and the correspond ing trouble is provided in CAUTION FOR SERVICING of the outdoor unit If the display shows any of th...