12

(2) Turn the MAIN/SUB changeover switch on one of the 

two remote controller PC boards to “S”.

(Leave the switch of the other remote controller set to “M”.)

Wiring Method

 (See ‘‘9 ELECTRIC WIRING WORK’’)

(3)

Remove the control box lid

.

(4) Add remote controller 2 (SUB) to the terminal block for 

remote controller (P

1

, P

2

) in the control box. 

(There is no polarity.)

[ PRECAUTIONS ]

• Crossover wiring is needed when using group control and 

2 remote controllers at the same time.

• Connect the indoor unit at the end of the crossover wire 

(P

1

, P

2

) to remote controller 2 (SUB).

10-3 REMOTE CONTROL (FORCED OFF AND ON/

OFF OPERATION)

• Connect input lines from the outside to the terminals T

1

 

and T

2

 on the terminal block (6P) for remote controller to 

achieve remote control.

• See the “

11. FIELD SETTING AND TEST RUN”

 for 

details on operation.

10-4 CENTRALIZED CONTROL 

• For centralized control, it is necessary to designate the group 

No. For details, refer to the manual of each optional control-
lers for centralized control.

11. FIELD SETTING AND TEST RUN

Field settings may have to be performed using the remote 

controller, depending on the type of installation.

(1) Make sure the control box lids are closed on the indoor 

and outdoor units.

(2) Depending on the type of installation, make the field 

settings from the remote controller after the power is 
turned on, following the “Field Settings” manual which 
came with the remote controller.

• The settings can select “Mode No.”, “FIRST CODE NO.” 

and “SECOND CODE NO.”.

• The “Field Settings” included with the remote controller 

lists the order of the settings and method of operation.

• Lastly, make sure the customer keeps the “Field Settings” 

manual, along with the operating manual, in a safe place.

11-1 SETTING THE STATIC PRESSURE SELECTION

• Select the SECOND CODE NO. for the resistance of the con-

nected duct. 
(The SECOND CODE NO. is set to “01” when shipped.)

• See the technical documentation for details. 

11-2 REMOTE CONTROL SETTING

• Forced off and ON/OFF operation should be selected by select-

ing the SECOND CODE  NO. as shown in the table below.
(The SECOND CODE NO. is set to “01” when shipped.)

• Input A of forced off and ON/OFF operation work as shown in 

the table below.

Only one remote controller 
needs to be changed 
if factory settings have 
remained untouched.

(Factory setting)

S

M

S

S

M

Remote controller 
PC board

Remote controller wiring 
terminal block

Remote 
controller 2
(SUB)

Remote 
controller 1
(MAIN)

1

P

2

P

1

F

2

F

1

T

2

T

FORCED

OFF

REMOTE
CONTRL

TRANSMISSION

WIRING

Indoor unit 1

Indoor unit 2

Max. No. of 
indoor units

Crossover wire (P

1

.P

2

)

Remote controller 1
(MAIN)

Remote controller 2
(SUB)

Input A

1

P

2

P

1

F

2

F

1

T

2

T

FORCED

OFF

REMOTE

CONTRL

TRANSMISSION

WIRING

Wire specification

Sheathed vinyl cord or cable (2 wires)

Gauge

AWG18 – 16

Length

Max. 328 ft.

External terminal

Contact that can ensure the minimum applica-
ble load of 15 V DC, 1 mA.

External static pressure

Mode No.

FIRST 

CODE NO.

SECOND 

CODE NO.

Standard

13(23)

5

01

High static pressure setting

02

External ON/OFF input

Mode No.

FIRST 

CODE NO.

SECOND 

CODE NO.

Forced off

12(22)

1

01

ON/OFF operation

02

Forced off

ON/OFF operation

Input A “on” to force a stop 
(remote controller reception prohibited)

Unit operated by changing input A 
from “off” to “on”

Input A “off” to allow remote con-
troller

Unit stopped by changing input A 
from “on” to “off”

SETTING

Mode No.

SECOND 
CODE NO.

FIELD SET 
MODE

FIRST 
CODE NO.

Summary of Contents for FXDQ07MVJU

Page 1: ...MVJU FXDQ09MVJU FXDQ12MVJU FXDQ18MVJU FXDQ24MVJU SYSTEM Inverter Air Conditioners INSTALLATION MANUAL Read these instructions carefully before installation Keep this manual in a handy place for future...

Page 2: ...ury or death Do not ground units to water pipes telephone wires or lightning rods because incomplete grounding could cause a severe shock hazard resulting in severe injury or death and to gas pipes be...

Page 3: ...t the customer to keep the area around the unit clean NOTE Install the indoor and outdoor units power supply wiring and connecting wires at least 3 5ft away from televisions or radios in order to prev...

Page 4: ...mid 6 Name Screwsforduct flanges 7 Washerforhanger bracket 8 Clamp Washer fixing plate 11 Quantity 1 set 8 pcs 1 set 4 pcs Shape Large 9 8 pcs small 10 4 pcs Name Conduit mounting plate Screw for con...

Page 5: ...er to prevent image interference or noise Depending on the radio waves a distance of 3 5 ft may not be sufficient enough to eliminate the noise 2 Use suspension bolts for installation Check whether th...

Page 6: ...he provided accessories and specified parts desig nated by our company 1 Install the indoor unit temporarily Attach the hanger bracket to the suspension bolt Be sure to fix it securely by using a nut...

Page 7: ...lare and cause leaks Be careful for oil not to adhere to any portions other than a flare part If oil adhere to resin parts etc there is a pos sibility of damaging by deterioration Refer to Table 2 if...

Page 8: ...ON The connection opening on the drain piping may vary depending on the model so check the model name and use the right method for that model Make sure all water is out before making the duct connecti...

Page 9: ...1 Remove the lid of the control box Connect the remote controller and power supply single phase 60Hz 208 230V respectively to the terminal block and securely connect the ground also as shown in the fi...

Page 10: ...ng and piping between the outdoor unit and an indoor unit are mismatched the system may cause a malfunction Install a wiring interrupter or ground fault circuit interrupter for the power wiring Make s...

Page 11: ...he entire system Connecting electrical wiring remote controller wiring and transmission wiring Refer to Fig 15 Power supply wiring and Ground wire Remove the control box lid Next pull the wires into t...

Page 12: ...troller PC board is attached to the upper part of remote controller Indoor unit A Indoor unit B Most downstream Indoor unit Power supply single phase 60Hz 208 230V Power supply single phase 60Hz 208 2...

Page 13: ...tly make sure the customer keeps the Field Settings manual along with the operating manual in a safe place 11 1 SETTING THE STATIC PRESSURE SELECTION Select the SECOND CODE NO for the resistance of th...

Page 14: ...stal display to identify the point of trouble An explanation of malfunction codes and the correspond ing trouble is provided in CAUTION FOR SERVICING of the outdoor unit If the display shows any of th...

Page 15: ...0601 HT 3PN06240 4E EM05A056 FS...

Reviews: