Installation
EDUS39-600-F2_a
30
FXDQ-M
• The
FIELD SETTINGS
included
w
ith the remote con-
troller list the order of the settings and method of oper-
ation.
• Lastly, make sure the customer keeps the
FIELD SET-
TINGS
manual, along
w
ith the operating manual, in a safe
place.
11-1 SETTING THE STATIC PRESSURE SELECTION
• Select the SECO
N
D CODE
N
O. for the resistance of the
connected duct.
(The SECO
N
D CODE
N
O. is set to
01
w
hen shipped.
• See the technical documentation for details.
11-2 REMOTE CONTROL SETTING
• Forced OFF and O
N
/OFF operation should be selected by
selecting the SECO
N
D CODE
N
O. as sho
w
n in the table
belo
w
.
The SECO
N
D CODE
N
O. is set to
01
w
hen shipped.
• Input A of forced off and O
N
/OFF operation
w
ork as sho
w
n
in the table belo
w
.
11-3
SETTING THE FILTER SIGN DISPLAY INTERVAL
• Explain the follo
w
ing to the customer if the filter dirt settings
have been changed.
• The filter sign display time is set to 2500 hours
(e
q
uivalent to 1 year’s use)
w
hen shipped.
• The settings can be changed to prevent display.
• When installing the unit in a place
w
ith a lot of dust, set the
filter-sign display time to shorter intervals (1,250 hours).
Explain to the customer that the filter needs to be cleaned
regularly to prevent clogging, and the time that is set.
External static pressure
Mode
N
o.
FIRST
CODE
N
O.
SECO
N
D
CODE
N
O.
Standard
13(23)
5
01
High static pressure setting
02
External O
N
/OFF input
Mode
N
o.
FIRST
CODE
N
O.
SECO
N
D
CODE
N
O.
Forced off
12(22)
1
01
O
N
/OFF operation
02
FORCED OFF (Manual Restart)
Mode
N
o. 12
First Code
N
o. 1
Second Code
N
o. 01
DEFAULT SETTING
ON/OFF OPERATION
Mode
N
o. 12
First Code
N
o. 1
Second Code
N
o. 02
Input A OFF (Open Circuit)
An open circuit bet
w
een termi-
nals T1 and T2 allo
w
s the unit to
run normally.
Input A OFF (Open Circuit)
An open circuit bet
w
een termi-
nals T1 and T2 prevents unit
operation.
Input A ON (Closed Circuit)
Closing the normally open cir-
cuit bet
w
een terminals T1 and
T2 stops operation of the unit.
When T1-T2 is opened, the unit
must be restarted
w
ith the
remote controller.
Unit stopped by changing input A
from “on” to “off”
SETTI
N
G
Mode
SECO
N
D
CODE
N
O.
FIELD SET
MODE
FIRST
CODE
N
O.
Summary of Contents for FXDQ-M
Page 1: ...EDUS 39 600 F2_a AMERICAS FXDQ M Slim Ceiling Mounted Duct Type...
Page 6: ...EDUS39 600 F2_a Dimensions FXDQ M 5 3 Dimensions FXDQ07 09 12MVJU 3D051759...
Page 7: ...Dimensions EDUS39 600 F2_a 6 FXDQ M FXDQ18MVJU 3D051760...
Page 8: ...EDUS39 600 F2_a Dimensions FXDQ M 7 FXDQ24MVJU 3D051761...
Page 11: ...Electric Characteristics EDUS39 600 F2_a 10 FXDQ M 6 Electric Characteristics 4D051757...