![Daikin FXDQ-M Engineering Data Download Page 5](http://html1.mh-extra.com/html/daikin/fxdq-m/fxdq-m_engineering-data_2459674005.webp)
Specifications
EDUS39-600-F2_a
4
FXDQ-M
Slim Ceilin
g
-Mounted Duct Type
Notes:
1.
N
ominal cooling capacities are based on the follo
w
ing conditions:
Return air temperature: 80°FDB, 67°FWB
Outdoor temperature: 95°FDB
E
q
uivalent ref. piping length: 25 ft / 7.5 m (Horizontal)
2.
N
ominal heating capacities are based on the follo
w
ing conditions:
Return air temperature: 70°FDB.
Outdoor temperature: 47°FDB, 43°FWB
E
q
uivalent ref. piping length: 25 ft / 7.5 m (Horizontal)
3. Capacities are net, including a deduction for cooling (an addition for heating) for indoor fan motor heat.
4. The airflo
w
is set to STA
N
DARD before leaving the factory. You can s
w
itch bet
w
een STA
N
DARD ESP and HIGH ESP
w
ith the remote controller.
Refer to the fan curves for actual fan performance.
5. Anechoic chamber conversion value, measured under JISB8616 conditions. During actual operation,
these values are normally some
w
hat higher as a result of installation conditions.
6. Refer to page 10 for Po
w
er Input.
Model
FXDQ1
8
MVJU
FXDQ24MVJU
Cooling Capacity
1
Btu/h
18,000
24,000
Heating Capacity
2
Btu/h
20,000
27,000
Casing / Color
Galvanized Steel Plate
Galvanized Steel Plate
Dimensions: (H × W × D)
in
(mm)
7-7/8
×
35-7/16
×
24-7/16”
(200 x 901.7 x 622.3 mm)
7-7/8
×
43-5/16
×
24-7/16”
(200 x 1100 x 622.3 mm)
Coil (Cross
Fin Coil)
Ro
w
s × Stages × FPI
3
×
12
×
17
3
×
12
×
17
Face Area
ft²
1.89’
2.44’
Fan
Model
—
—
Type
Sirocco Fan
Sirocco Fan
Motor Output
kW
0.13
0.13
Air Flo
w
Rate (H/L)
cfm
440/350 (H/L)
580/460 (H/L)
External Static Pressure
4
in.Wg
0.17 - 0.06
0.17 - 0.06
Drive
Direct Drive
Direct Drive
Temperature Control
Microprocessor Thermostat
for Cooling and Heating
Microprocessor Thermostat
for Cooling and Heating
Sound Absorbing Thermal Insulation Material
Foamed Polyethylene
Foamed Polyethylene
Air Filter
Removal, Washable, Milde
w
Proof
Removal, Washable, Milde
w
Proof
Piping
Connections
Li
q
uid Pipes
in / mm
φ
1/4” / 6.4 mm (Flare Connection)
φ
3/8” / 9.5 mm (Flare Connection)
Gas Pipes
in / mm
φ
1/2” / 12.7 mm (Flare Connection)
φ
5/8” / 15.8 mm (Flare Connection)
Drain Pipe
in / mm
External Dia. 1-1/32” / 26.2 mm
Internal Dia. 25/32” / 19.8 mm
External Dia. 1-1/32” / 26.2 mm
Internal Dia. 25/32” / 19.8 mm
Machine Weight (Mass)
Lbs
63
71
Sound Level (H/L)
5
dBA
35/31
36/32
Safety Devices
Fuse,
Thermal Protector for Fan Motor
Fuse,
Thermal Protector for Fan Motor
Refrigerant Control
Electronic Expansion
V
alve
Electronic Expansion
V
alve
Connectable outdoor unit
R-410A Series
R-410A Series
Standard Accessories
Operation Manual, Installation Manual, Paper Pattern for
Installation, Drain Hose, Clamp Metal, Insulation for Fitting,
Sealing Pads, Clamps, Scre
w
s, Washers, Conduit Mounting
Plate, Insulation Tube.
Operation Manual, Installation Manual, Paper Pattern for
Installation, Drain Hose, Clamp Metal, Insulation for Fitting,
Sealing Pads, Clamps, Scre
w
s, Washers, Conduit Mounting
Plate, Insulation Tube.
Dra
w
ing
N
o.
C:3D051780A
Summary of Contents for FXDQ-M
Page 1: ...EDUS 39 600 F2_a AMERICAS FXDQ M Slim Ceiling Mounted Duct Type...
Page 6: ...EDUS39 600 F2_a Dimensions FXDQ M 5 3 Dimensions FXDQ07 09 12MVJU 3D051759...
Page 7: ...Dimensions EDUS39 600 F2_a 6 FXDQ M FXDQ18MVJU 3D051760...
Page 8: ...EDUS39 600 F2_a Dimensions FXDQ M 7 FXDQ24MVJU 3D051761...
Page 11: ...Electric Characteristics EDUS39 600 F2_a 10 FXDQ M 6 Electric Characteristics 4D051757...