background image

English

11

• Remote controller and transmission wiring

Pull the wires into the unit through the wiring through hole
and connect to the terminal block (6P).
Be sure to put the part of the sheathed vinyl into the control
box.

Precautions when laying power supply wiring 

Wiring of different thicknesses cannot be connected to the
power supply wiring terminal block. (Slack in the power sup-
ply wiring may cause abnormal heat.)

Use sleeve-insulated round crimp-style terminals for connec-
tions to the power supply wiring terminal block. When none
are available, connect wires of the same diameter to both
sides, as shown in the figure.

Follow the instructions are below if the wiring may get very 
hot due to slack in the power supply wiring.

For wiring, use the designated power supply wiring and con-
nect firmly, then secure to prevent outside pressure being
exerted on the terminal board.

Use the correct screwdriver for tightening the terminal
screws. If the blade of screwdriver is too small, the head of
the screw might be damaged, and the screw will not be prop-
erly tightened.

If the terminal screws are tightened too hard, screws might
be damaged.

Refer to the table below for the tightening torque of the termi-
nal screws.

[ WIRING EXAMPLE

 

]

No. 1 system When using 1 remote controller for 

1 indoor unit 

No. 2 system For group control or use with 2 remote 

controllers

Terminal block

Tightening torque (N·m)

Remote controller / transmission wiring 
terminal block (6P)

0.79 – 0.97

Power supply wiring terminal block (3P)

1.18 – 1.44

Insulation sleeve

Round crimp-style terminal

Electric wire

Do not connect 
wires of different 
gauges. 

Do not connect 
wires of the same 
gauge to one side.

Connect wires of 
the same gauge to 
both sides.

F

T

1

L

1

1

1

P

P

2

P

N

1

2

P

T

F

2

F

P

F

1

2

2

2

P

1

N

2

P

2

F

IN/D

1

OUT/D

1

P

F

2

F

1

P

L

F

1

2

T

2

T

1

P

P

2

1

F

2

N

F

L

1

2

T T

P

L N

L N

L N

 (option) 

 (option) 

 (option) 

Fig. 19

Remote controller

Remote controller

Remote controller

Outdoor unit

Power supply 

single phase 

50Hz 220-240V 

or single phase 

60Hz 220V

Power supply 

single phase 

50Hz 220-240V 

or single phase 

60Hz 220V

Power supply 

single phase 

50Hz 220-240V 

or single phase 

60Hz 220V

Most 
downstream 
indoor unit 

Indoor unit B

Indoor unit A

L N

1

P

2

P

1

P

2

P

1

P

2

P

1

P

P

2

1

F

2

N

F

L

N

L

1

2

F

F

1

2

F

F

1

2

T T

1

P

P

2

1

F

2

F

1

2

T T

N

L

1

P

P

2

1

F

2

F

1

2

T T

IN/D OUT/D

Power supply 

single phase 

50Hz 220-240V 

or single phase 

60Hz 220V

 (option) 

 (option) 

Remote controller

Remote controller

Remote controller

Fig. 20

Case of group control

For use with 2 
remote controllers

Most 
downstream 
indoor unit

Indoor unit B

Indoor 
unit A

Note)  There is not need to set the indoor unit 

address when using group control. 
(It is automatically set when the power 
is turned on.)

Outdoor unit

4PEN325876-1F.book  Page 11  Thursday, April 20, 2017  8:20 AM

Summary of Contents for FXDQ-A3

Page 1: ...INSTALLATION MANUAL FXDQ15A3VEB FXDQ20A3VEB FXDQ25A3VEB FXDQ32A3VEB FXDQ40A3VEB FXDQ50A3VEB FXDQ63A3VEB System Inverter Air Conditioners 4PEN325876 1F book Page 1 Thursday April 20 2017 8 20 AM ...

Page 2: ...da B secondo il Certificato C 07 Σημείωση όπως καθορίζεται στο A και κρίνεται θετικά από το B σύμφωνα με το Πιστοποιητικό C 08 Nota tal como estabelecido em A e com o parecer positivo de B de acordo com o Certificado C 09 Примечание как указано в A и в соответствии с положительным решением B согласно Свидетельству C 10 Bemærk som anført i A og positivt vurderet af B i henhold til Certifikat C 11 I...

Page 3: ...llation work may result in the unit falling and causing accidents Make sure that a separate power supply circuit is provided for this unit and that all electrical work is carried out by qual ified personnel according to local laws and regulations and this installation manual An insufficient power supply capacity or improper electrical construction may lead to electric shocks or fire Make sure that...

Page 4: ... the unit by the hanger brackets Do not apply force to the refrigerant piping drain piping or flange parts Be sure to check the type of R410A refrigerant to be used before installing the unit Using an incorrect refrigerant will prevent normal opera tion of the unit For the installation of an outdoor unit refer to the installation manual attached to the outdoor unit 2 1 PRECAUTIONS Be sure to instr...

Page 5: ...hould be installed as far away from fluores cent lighting as possible 2 Use suspension bolts for installation Check whether the ceiling is strong enough to support the weight of the unit or not If there is a risk reinforce the ceiling before installing the unit To avoid contact with the fan one of the following precaution actions must be taken Install the unit as high as possible at a minimum bott...

Page 6: ... prevent shaking Consult an architect or carpenter for details 4 Install the suspension bolts Use W3 8 to M10 suspension bolts Use a hole in anchor for existing ceilings and a sunken insert sunken anchor or other part to be procured in the field to reinforce the ceiling to bearing the weight of the unit for new ceiling Refer to Fig 3 5 In case of bottom suction 1 Remove the chamber lid 7 locations...

Page 7: ...ra ture above the ceiling might reach 30 C or the humidity RH80 Condensation may form on the surface of the insu lation CAUTION Follow the points at below Use a pipe cutter and flare suitable for the type of refrigerant Apply ester oil or ether oil to the flare section when using a flare connection Only use the flare nuts included with the unit Using different flare nuts may cause the refrigerant ...

Page 8: ...phosphor copper brazer BCuP 2 JIS Z 3264 B Cu93P 710 795 ISO 3677 which does not require flux Using a flux containing chlorine may cause the piping to corrode Using a welding flux containing fluorine may cause the refrigerant lubricant to deteriorate and affect adversely the refrigerant piping system Not recommendable but in case of emergency You must use a torque wrench but if you are obliged to ...

Page 9: ...o Fig 13 PRECAUTIONS Drain piping connections Do not connect the drain piping directly to sewage pipes that smell of ammonia The ammonia in the sewage might enter the indoor unit through the drain piping and corrode the heat exchanger Do not twist or bend the drain hose 2 so that excessive force is not applied to it This type of treatment may cause leaking If you are using central drain piping fol...

Page 10: ...ion area with aluminum tape or something similar to prevent air escaping CAUTION When attaching a duct to the intake side be sure to attach an air filter inside the air passage on the intake side Use an air filter whose dust collecting efficiency is at least 50 in a gravimetric technique The included filter is not used when the intake duct is attached Air outlet side Connect the duct according to ...

Page 11: ...Do not turn on the power supply circuit breaker or earth leak age breaker until all other work is done 9 2 SPECIFICATIONS FOR FIELD SUPPLIED FUSES AND WIRE Power related NOTES 1 Shows only in case of protected pipes Use H07RN F in case of no protection 2 Insulated thickness 1mm or more 3 If the wiring is in a place where people it can be easily touched by people install an earth leakage breaker to...

Page 12: ...wer sup ply wiring to the remote controller or transmission wiring terminal block Doing so can destroy the entire system Connecting electrical wiring remote controller wiring and transmission wiring Refer to Fig 18 Power supply and Earth wiring Remove the control box lid Next pull the wires into the unit through the wiring through hole and connect to the terminal block 3P Be sure to put the part o...

Page 13: ...ystem For group control or use with 2 remote controllers Terminal block Tightening torque N m Remote controller transmission wiring terminal block 6P 0 79 0 97 Power supply wiring terminal block 3P 1 18 1 44 Insulation sleeve Round crimp style terminal Electric wire Do not connect wires of different gauges Do not connect wires of the same gauge to one side Connect wires of the same gauge to both s...

Page 14: ... achieve remote control See the 11 FIELD SETTING AND TEST RUN for details on operation 10 4 CENTRALIZED CONTROL For centralized control it is necessary to designate the group No For details refer to the manual of each optional control lers for centralized control L N F F1 2 F F1 2 F F1 2 F F1 2 IN D IN D OUT D OUT D 1 P P 2 1 F 2 N F L 1 2 T T 1 P 2 P Power supply single phase 50Hz 220 240V or sin...

Page 15: ...on man ual included with the wireless remote controller for details on how to make the settings 3 Perform a test run according to the outdoor unit s installation manual The operation lamp of the remote controller will flash when a malfunction occurs Check the malfunction code on the liquid crystal display to identify the point of trouble An explanation of malfunction codes and the correspond ing t...

Page 16: ...OT LAMP LIGHT EMITTINGDIODE S NPL PRESSURESENSOR LOW HAP LIGHT EMITTINGDIODE SERVICEMONITOR GREEN S PH HPS PRESSURESWITCH HIGH HIGH VOLTAGE HIGH VOLTAGE S PL PRESSURESWITCH LOW IES INTELLIGENT EYESENSOR S T THERMOSTAT IPM INTELLIGENT POWER MODULE S W SW OPERATION SWITCH K R KCR KFR KHuR MAGNETIC RELAY SA SURGE ARRESTOR L LIVE SR WLU SIGNAL RECEIVER L COIL SS SELECTOR SWITCH L R REACTOR SHEET METAL...

Page 17: ...4P325876 1H book Page 1 Thursday April 27 2017 10 43 AM ...

Page 18: ...4P325876 1F 2017 02 Copyright 2012 Daikin 4PEN325876 1F book Page 1 Thursday April 20 2017 8 20 AM ...

Reviews: