No. 3 system When including BS unit

10-2 CONTROL BY 2 REMOTE CONTROLLERS (Con-

trolling 1 indoor unit by 2 remote controllers)

When using 2 remote controllers, one must be set to “MAIN”
and the other to “SUB”.

MAIN/SUB CHANGEOVER

(1) Insert a 

 screwdriver into the recess between the

upper and lower part of remote controller and, working
from the 2 positions, pry off the upper part (2 loca-
tions).

The remote controller PC board is attached to the upper
part of remote controller.

(2) Turn the MAIN/SUB changeover switch on one of the

two remote controller PC boards to “S”.

(Leave the switch of the other remote controller set to “M”.)

Wiring Method

 (See ‘‘9. ELECTRIC WIRING WORK’’)

(3) Remove the control box lid.

(4) Add remote controller 2 (SUB) to the terminal block for

remote controller (P

1

, P

2

) in the control box.

(There is no polarity.)

[ PRECAUTIONS ]

Crossover wiring is needed when using group control and
2 remote controllers at the same time.

Connect the indoor unit at the end of the crossover wire
(P

1

, P

2

) to remote controller 2 (SUB).

10-3 REMOTE CONTROL (FORCED OFF AND ON/

OFF OPERATION)

Connect input lines from the outside to the terminals T

1

and T

2

 on the terminal block (6P) for remote controller to

achieve remote control.

See the “

11. FIELD SETTING AND TEST RUN”

 for

details on operation.

10-4 CENTRALIZED CONTROL

For centralized control, it is necessary to designate the group 
No. For details, refer to the manual of each optional control-
lers for centralized control.

L

N

F

F

1

2

F

F

1

2

F

F

1

2

F

F

1

2

IN/D

IN/D

OUT/D

OUT/D

1

P

P

2

1

F

2

N

F

L

1

2

T T

1

P

2

P

Power supply 

single phase 

50Hz 220-240V 

or single phase 

60Hz 220V

Fig. 21

Remote controller

(option)

Indoor unit A

BS unit

Outdoor unit

Upper part of 
remote controller

Lower part of 
remote controller

Insert the screwdriver here and gently work off the 
upper part of remote controller.

Only one remote controller 
needs to be changed if 
factory settings have 
remained untouched.

(Factory setting)

S

M

S

S

M

Remote controller 
PC board

Wire specification

Sheathed vinyl cord or cable (2 wires)

Gauge

0.75 - 1.25 mm

2

Length

Max. 100 m

External terminal

Contact that can ensure the minimum applica-
ble load of 15 V DC, 1 mA.

1

P

2

P

1

F

2

F

1

T

2

T

FORCED

OFF

REMOTE
CONTRL

TRANSMISSION

WIRING

Remote 
controller 1 
(MAIN)

Remote 
controller 2 
(SUB)

Remote controller wiring 
terminal block

Remote controller 2 
(SUB)

Remote controller 1 
(MAIN)

Crossover wire (P

1

.P

2

)

Max. No. of 

indoor units

Indoor unit 2

Indoor unit 1

1

P

2

P

1

F

2

F

1

T

2

T

FORCED

OFF

REMOTE

CONTRL

TRANSMISSION

WIRING

Input A

4PEN325876-1F.book  Page 12  Thursday, April 20, 2017  8:20 AM

Summary of Contents for FXDQ-A3

Page 1: ...INSTALLATION MANUAL FXDQ15A3VEB FXDQ20A3VEB FXDQ25A3VEB FXDQ32A3VEB FXDQ40A3VEB FXDQ50A3VEB FXDQ63A3VEB System Inverter Air Conditioners 4PEN325876 1F book Page 1 Thursday April 20 2017 8 20 AM ...

Page 2: ...da B secondo il Certificato C 07 Σημείωση όπως καθορίζεται στο A και κρίνεται θετικά από το B σύμφωνα με το Πιστοποιητικό C 08 Nota tal como estabelecido em A e com o parecer positivo de B de acordo com o Certificado C 09 Примечание как указано в A и в соответствии с положительным решением B согласно Свидетельству C 10 Bemærk som anført i A og positivt vurderet af B i henhold til Certifikat C 11 I...

Page 3: ...llation work may result in the unit falling and causing accidents Make sure that a separate power supply circuit is provided for this unit and that all electrical work is carried out by qual ified personnel according to local laws and regulations and this installation manual An insufficient power supply capacity or improper electrical construction may lead to electric shocks or fire Make sure that...

Page 4: ... the unit by the hanger brackets Do not apply force to the refrigerant piping drain piping or flange parts Be sure to check the type of R410A refrigerant to be used before installing the unit Using an incorrect refrigerant will prevent normal opera tion of the unit For the installation of an outdoor unit refer to the installation manual attached to the outdoor unit 2 1 PRECAUTIONS Be sure to instr...

Page 5: ...hould be installed as far away from fluores cent lighting as possible 2 Use suspension bolts for installation Check whether the ceiling is strong enough to support the weight of the unit or not If there is a risk reinforce the ceiling before installing the unit To avoid contact with the fan one of the following precaution actions must be taken Install the unit as high as possible at a minimum bott...

Page 6: ... prevent shaking Consult an architect or carpenter for details 4 Install the suspension bolts Use W3 8 to M10 suspension bolts Use a hole in anchor for existing ceilings and a sunken insert sunken anchor or other part to be procured in the field to reinforce the ceiling to bearing the weight of the unit for new ceiling Refer to Fig 3 5 In case of bottom suction 1 Remove the chamber lid 7 locations...

Page 7: ...ra ture above the ceiling might reach 30 C or the humidity RH80 Condensation may form on the surface of the insu lation CAUTION Follow the points at below Use a pipe cutter and flare suitable for the type of refrigerant Apply ester oil or ether oil to the flare section when using a flare connection Only use the flare nuts included with the unit Using different flare nuts may cause the refrigerant ...

Page 8: ...phosphor copper brazer BCuP 2 JIS Z 3264 B Cu93P 710 795 ISO 3677 which does not require flux Using a flux containing chlorine may cause the piping to corrode Using a welding flux containing fluorine may cause the refrigerant lubricant to deteriorate and affect adversely the refrigerant piping system Not recommendable but in case of emergency You must use a torque wrench but if you are obliged to ...

Page 9: ...o Fig 13 PRECAUTIONS Drain piping connections Do not connect the drain piping directly to sewage pipes that smell of ammonia The ammonia in the sewage might enter the indoor unit through the drain piping and corrode the heat exchanger Do not twist or bend the drain hose 2 so that excessive force is not applied to it This type of treatment may cause leaking If you are using central drain piping fol...

Page 10: ...ion area with aluminum tape or something similar to prevent air escaping CAUTION When attaching a duct to the intake side be sure to attach an air filter inside the air passage on the intake side Use an air filter whose dust collecting efficiency is at least 50 in a gravimetric technique The included filter is not used when the intake duct is attached Air outlet side Connect the duct according to ...

Page 11: ...Do not turn on the power supply circuit breaker or earth leak age breaker until all other work is done 9 2 SPECIFICATIONS FOR FIELD SUPPLIED FUSES AND WIRE Power related NOTES 1 Shows only in case of protected pipes Use H07RN F in case of no protection 2 Insulated thickness 1mm or more 3 If the wiring is in a place where people it can be easily touched by people install an earth leakage breaker to...

Page 12: ...wer sup ply wiring to the remote controller or transmission wiring terminal block Doing so can destroy the entire system Connecting electrical wiring remote controller wiring and transmission wiring Refer to Fig 18 Power supply and Earth wiring Remove the control box lid Next pull the wires into the unit through the wiring through hole and connect to the terminal block 3P Be sure to put the part o...

Page 13: ...ystem For group control or use with 2 remote controllers Terminal block Tightening torque N m Remote controller transmission wiring terminal block 6P 0 79 0 97 Power supply wiring terminal block 3P 1 18 1 44 Insulation sleeve Round crimp style terminal Electric wire Do not connect wires of different gauges Do not connect wires of the same gauge to one side Connect wires of the same gauge to both s...

Page 14: ... achieve remote control See the 11 FIELD SETTING AND TEST RUN for details on operation 10 4 CENTRALIZED CONTROL For centralized control it is necessary to designate the group No For details refer to the manual of each optional control lers for centralized control L N F F1 2 F F1 2 F F1 2 F F1 2 IN D IN D OUT D OUT D 1 P P 2 1 F 2 N F L 1 2 T T 1 P 2 P Power supply single phase 50Hz 220 240V or sin...

Page 15: ...on man ual included with the wireless remote controller for details on how to make the settings 3 Perform a test run according to the outdoor unit s installation manual The operation lamp of the remote controller will flash when a malfunction occurs Check the malfunction code on the liquid crystal display to identify the point of trouble An explanation of malfunction codes and the correspond ing t...

Page 16: ...OT LAMP LIGHT EMITTINGDIODE S NPL PRESSURESENSOR LOW HAP LIGHT EMITTINGDIODE SERVICEMONITOR GREEN S PH HPS PRESSURESWITCH HIGH HIGH VOLTAGE HIGH VOLTAGE S PL PRESSURESWITCH LOW IES INTELLIGENT EYESENSOR S T THERMOSTAT IPM INTELLIGENT POWER MODULE S W SW OPERATION SWITCH K R KCR KFR KHuR MAGNETIC RELAY SA SURGE ARRESTOR L LIVE SR WLU SIGNAL RECEIVER L COIL SS SELECTOR SWITCH L R REACTOR SHEET METAL...

Page 17: ...4P325876 1H book Page 1 Thursday April 27 2017 10 43 AM ...

Page 18: ...4P325876 1F 2017 02 Copyright 2012 Daikin 4PEN325876 1F book Page 1 Thursday April 20 2017 8 20 AM ...

Reviews: