background image

English

3

Also review the “SAFETY PRECAUTIONS”.

b. Items to be checked at time of delivery

c. Points for explanation about operations

3. SELECTING INSTALLATION SITE

CAUTION

When moving the unit during or after unpacking, make sure
to lift it by holding its lifting lugs.  Do not exert any pressure on 
other parts, especially the refrigerant piping, drain piping and 
flange parts.

If you think the humidity inside the ceiling might exceed
30°C and RH80%, reinforce the insulation on the unit body.
Use glass wool or polyethylene foam as insulation so that
it is no thicker than 10mm and fits inside the ceiling open-
ing.

(1) Select an installation site where the following conditions

are fulfilled and that meets with your customer’s approval.

Where optimum air distribution can be ensured.

Where nothing blocks air passage.

Where condensate can be properly drained.

Where the ceiling is strong enough to bear the indoor unit 

weight.

Where the false ceiling is not noticeably on an incline.

Where there is no risk of flammable gas leakage.

Where sufficient clearance for maintenance and service

can be ensured. 

(Refer to Fig. 1)

Where piping between indoor and outdoor units is possi-

ble within the allowable limit. (Refer to the installation

manual for the outdoor unit.)

The equipment is not intended for use in a potentially

explosive atmosphere.

*H1 dimension means the minimum height of the unit.

Select the *H1, *H2 dimension such that a downward
slope of at least 1/100 is ensured as indicated in

7. DRAIN PIPING WORK

”.

The maintenance space marked with “*” is required when
the installation box for adaptor PC board (KRP1BA101)
sold separately is used.

[ PRECAUTION ]

Install the indoor and outdoor units, power supply wiring
and connecting wires at least 1 m away from televisions or 
radios in order to prevent image interference or noise.
(Depending on the radio waves, a distance of 1 m may not 
be sufficient enough to eliminate the noise.)

If installing the wireless kit in a room with electronic fluo-
rescent lighting (inverter or rapid start type), the remote
controller’s transmission distance may be shortened.
Indoor units should be installed as far away from fluores-
cent lighting as possible.

(2) Use suspension bolts for installation. Check whether

the ceiling is strong enough to support the weight of
the unit or not. If there is a risk, reinforce the ceiling
before installing the unit.

To avoid contact with the fan, one of the following precaution
actions must be taken:

-

Install the unit as high as possible at a minimum bottom
height of 2.7 m.

-

Install the unit as high as possible at a minimum bottom
height of 2.5 m in case the fan is externally screened by
parts which can be removed without the aid of tools (e.g.
false sealing, grill...).

-

Install the unit with ducting and grill which can only be
removed with the aid of tooling. It shall be installed so that
it gives adequate protection against touching the fan. If a
maintenance panel exists in the ducting, it shall only be
possible to remove the panel by the aid of tooling to avoid
contact with the fan. The protection shall be according to
relevant European and local legislation. There are no
restrictions concerning the installation height.

Is something blocking the air 
outlet or inlet of either the 
indoor or outdoor units?

It may result in insufficient 
cooling.

Are refrigerant piping length 
and additional refrigerant 
charge noted down?

The refrigerant charge in the 
system is not clear.

Items to be checked

Check

Did you explain about operations while showing the 
operation manual to your customer?
Did you hand the operation manual and warranty over to 
your customer?
Did you explain about the way of maintaining and cleaning 
local procurements (air filter, grille (both air outlet and suc-
tion grille), etc.) to your customer?
Did you hand manuals of local procurements (in case 
equipped) over to your customer?

The items with 

WARNING and 

CAUTION marks in 

the operation manual are the items pertaining to 
possibilities for bodily injury and material damage in 
addition to the general usage of the product. Accordingly, it 
is necessary that you make a full explanation about the 
described contents and also ask your customers to read the 
operation manual.

200

Fig. 1

(length : mm)

Floor surface

Ceiling

*H2=20 or more

*300
or
more

300 or 
more

Maintenance 
space

Maintenance 
space

Control box

*H1=

240 or more

2500 or more

4PEN325876-1F.book  Page 3  Thursday, April 20, 2017  8:20 AM

Summary of Contents for FXDQ-A3

Page 1: ...INSTALLATION MANUAL FXDQ15A3VEB FXDQ20A3VEB FXDQ25A3VEB FXDQ32A3VEB FXDQ40A3VEB FXDQ50A3VEB FXDQ63A3VEB System Inverter Air Conditioners 4PEN325876 1F book Page 1 Thursday April 20 2017 8 20 AM ...

Page 2: ...da B secondo il Certificato C 07 Σημείωση όπως καθορίζεται στο A και κρίνεται θετικά από το B σύμφωνα με το Πιστοποιητικό C 08 Nota tal como estabelecido em A e com o parecer positivo de B de acordo com o Certificado C 09 Примечание как указано в A и в соответствии с положительным решением B согласно Свидетельству C 10 Bemærk som anført i A og positivt vurderet af B i henhold til Certifikat C 11 I...

Page 3: ...llation work may result in the unit falling and causing accidents Make sure that a separate power supply circuit is provided for this unit and that all electrical work is carried out by qual ified personnel according to local laws and regulations and this installation manual An insufficient power supply capacity or improper electrical construction may lead to electric shocks or fire Make sure that...

Page 4: ... the unit by the hanger brackets Do not apply force to the refrigerant piping drain piping or flange parts Be sure to check the type of R410A refrigerant to be used before installing the unit Using an incorrect refrigerant will prevent normal opera tion of the unit For the installation of an outdoor unit refer to the installation manual attached to the outdoor unit 2 1 PRECAUTIONS Be sure to instr...

Page 5: ...hould be installed as far away from fluores cent lighting as possible 2 Use suspension bolts for installation Check whether the ceiling is strong enough to support the weight of the unit or not If there is a risk reinforce the ceiling before installing the unit To avoid contact with the fan one of the following precaution actions must be taken Install the unit as high as possible at a minimum bott...

Page 6: ... prevent shaking Consult an architect or carpenter for details 4 Install the suspension bolts Use W3 8 to M10 suspension bolts Use a hole in anchor for existing ceilings and a sunken insert sunken anchor or other part to be procured in the field to reinforce the ceiling to bearing the weight of the unit for new ceiling Refer to Fig 3 5 In case of bottom suction 1 Remove the chamber lid 7 locations...

Page 7: ...ra ture above the ceiling might reach 30 C or the humidity RH80 Condensation may form on the surface of the insu lation CAUTION Follow the points at below Use a pipe cutter and flare suitable for the type of refrigerant Apply ester oil or ether oil to the flare section when using a flare connection Only use the flare nuts included with the unit Using different flare nuts may cause the refrigerant ...

Page 8: ...phosphor copper brazer BCuP 2 JIS Z 3264 B Cu93P 710 795 ISO 3677 which does not require flux Using a flux containing chlorine may cause the piping to corrode Using a welding flux containing fluorine may cause the refrigerant lubricant to deteriorate and affect adversely the refrigerant piping system Not recommendable but in case of emergency You must use a torque wrench but if you are obliged to ...

Page 9: ...o Fig 13 PRECAUTIONS Drain piping connections Do not connect the drain piping directly to sewage pipes that smell of ammonia The ammonia in the sewage might enter the indoor unit through the drain piping and corrode the heat exchanger Do not twist or bend the drain hose 2 so that excessive force is not applied to it This type of treatment may cause leaking If you are using central drain piping fol...

Page 10: ...ion area with aluminum tape or something similar to prevent air escaping CAUTION When attaching a duct to the intake side be sure to attach an air filter inside the air passage on the intake side Use an air filter whose dust collecting efficiency is at least 50 in a gravimetric technique The included filter is not used when the intake duct is attached Air outlet side Connect the duct according to ...

Page 11: ...Do not turn on the power supply circuit breaker or earth leak age breaker until all other work is done 9 2 SPECIFICATIONS FOR FIELD SUPPLIED FUSES AND WIRE Power related NOTES 1 Shows only in case of protected pipes Use H07RN F in case of no protection 2 Insulated thickness 1mm or more 3 If the wiring is in a place where people it can be easily touched by people install an earth leakage breaker to...

Page 12: ...wer sup ply wiring to the remote controller or transmission wiring terminal block Doing so can destroy the entire system Connecting electrical wiring remote controller wiring and transmission wiring Refer to Fig 18 Power supply and Earth wiring Remove the control box lid Next pull the wires into the unit through the wiring through hole and connect to the terminal block 3P Be sure to put the part o...

Page 13: ...ystem For group control or use with 2 remote controllers Terminal block Tightening torque N m Remote controller transmission wiring terminal block 6P 0 79 0 97 Power supply wiring terminal block 3P 1 18 1 44 Insulation sleeve Round crimp style terminal Electric wire Do not connect wires of different gauges Do not connect wires of the same gauge to one side Connect wires of the same gauge to both s...

Page 14: ... achieve remote control See the 11 FIELD SETTING AND TEST RUN for details on operation 10 4 CENTRALIZED CONTROL For centralized control it is necessary to designate the group No For details refer to the manual of each optional control lers for centralized control L N F F1 2 F F1 2 F F1 2 F F1 2 IN D IN D OUT D OUT D 1 P P 2 1 F 2 N F L 1 2 T T 1 P 2 P Power supply single phase 50Hz 220 240V or sin...

Page 15: ...on man ual included with the wireless remote controller for details on how to make the settings 3 Perform a test run according to the outdoor unit s installation manual The operation lamp of the remote controller will flash when a malfunction occurs Check the malfunction code on the liquid crystal display to identify the point of trouble An explanation of malfunction codes and the correspond ing t...

Page 16: ...OT LAMP LIGHT EMITTINGDIODE S NPL PRESSURESENSOR LOW HAP LIGHT EMITTINGDIODE SERVICEMONITOR GREEN S PH HPS PRESSURESWITCH HIGH HIGH VOLTAGE HIGH VOLTAGE S PL PRESSURESWITCH LOW IES INTELLIGENT EYESENSOR S T THERMOSTAT IPM INTELLIGENT POWER MODULE S W SW OPERATION SWITCH K R KCR KFR KHuR MAGNETIC RELAY SA SURGE ARRESTOR L LIVE SR WLU SIGNAL RECEIVER L COIL SS SELECTOR SWITCH L R REACTOR SHEET METAL...

Page 17: ...4P325876 1H book Page 1 Thursday April 27 2017 10 43 AM ...

Page 18: ...4P325876 1F 2017 02 Copyright 2012 Daikin 4PEN325876 1F book Page 1 Thursday April 20 2017 8 20 AM ...

Reviews: