12 Unit installation

Installation and operation manual

14

FXDA10~63A2VEB

VRV system air conditioner

3P599562-1 – 2020.05

e: A

e:

 500

(mm)

a

b

b

d

c

a

Nut (field supply)

b

Washer (accessories)

c

Hanger bracket

d

Double nut (field supply)

e

Suspension bolt pitch

  12‒2 Suspension bolt pitch (A)

Class

A (mm)

10~32

740

40~50

940

63

1140

Level

. Make sure the unit is level at all four corners using a level

or a water-filled vinyl tube.

b

a

a

Water level

b

Vinyl tube

NOTICE

Do  NOT  install  the  unit  tilted. 

Possible  consequence: 

If

the unit is tilted against the direction of the condensate flow
(the  drain  piping  side  is  raised),  the  float  switch  might
malfunction and cause water to drip.

12.2.2

Guidelines when installing the ducting

WARNING

Do  NOT  install  operating  ignition  sources  (example:  open
flames, an operating gas appliance or an operating electric
heater) in the duct work.

CAUTION

▪ Make sure the installation of the duct does NOT exceed

the setting range of the external static pressure for the
unit. Refer to the technical datasheet of your model for
the setting range.

▪ Make  sure  to  install  the  canvas  duct  so  vibrations  are

NOT  transmitted  to  the  duct  or  ceiling.  Use  a  sound-
absorbing material (insulation material) for the lining of
the  duct  and  apply  vibration  insulation  rubber  to  the
hanging bolts.

▪ When  welding,  make  sure  NOT  to  spatter  onto  the

drain pan or the air filter.

▪ If the metal duct passes through a metal lath, wire lath

or  metal  plate  of  the  wooden  structure,  separate  the
duct and wall electrically.

▪ Install the outlet grille in a position where the airflow will

not come into direct contact with people.

▪ Do NOT use booster fans in the duct. Use the function

to  adjust  the  fan  rate  setting  automatically  (see

"16.1 Field setting" 

[

4

 19]).

The ducting is to be field supplied.

1

Air inlet side.

 Connect the inlet side flange (field supply) to the

indoor  unit,  use  screws  from  accessory  (table  below).  Connect
the  canvas  duct  to  the  inside  of  the  inlet  side  flange.  Connect
the duct to the canvas duct.

Number of screws according to class

10~32

40~50

63

16

22

26

2

Air  outlet  side.

  Connect  the  canvas  duct  to  the  inside  of  the

outlet side flange. Connect the duct to the canvas duct.

a

b

c

b

a

f

f

e

e

d

d

a

Screws for duct flanges

For air inlet side:

 accessory

For air outlet side:

 on the unit

b

Flange

For air inlet side:

 field supply

For air outlet side:

 on the unit

c

Indoor unit

d

Insulation (field supply)

e

Canvas duct (field supply)

f

Aluminium tape (field supply)

3

Wind aluminium tape around the flange and duct connection on
both  sides.  Make  sure  there  are  no  air  leaks  at  any  other
connection.

4

Insulate  the  duct  to  prevent  condensation  from  forming.  Use
glass wool or polyethylene foam 25 mm thick.

Filter. 

Be sure to attach an air filter inside the air passage on the

intake  side.  Use  an  air  filter  with  dust  collecting  efficiency  ≥50%
(gravimetric  method).  The  included  filter  is  not  used  when  the
intake duct is attached.

12.2.3

Guidelines when installing the drain
piping

Make  sure  condensation  water  can  be  evacuated  properly.  This
involves:

▪ General guidelines

▪ Connecting the drain piping to the indoor unit

Summary of Contents for FXDA10A2VEB

Page 1: ...and operation manual VRV system air conditioner English Installation and operation manual VRV system air conditioner FXDA10A2VEB FXDA15A2VEB FXDA20A2VEB FXDA25A2VEB FXDA32A2VEB FXDA40A2VEB FXDA50A2VEB...

Page 2: ...v e cu condi ia ca acestea s fie utilizate n conformitate cu instruc iunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili on vas...

Page 3: ...ndoor unit 17 15 Commissioning 18 15 1 Checklist before commissioning 18 15 2 To perform a test run 19 16 Configuration 19 16 1 Field setting 19 17 Technical data 20 17 1 Wiring diagram 20 17 1 1 Unif...

Page 4: ...ill not come into direct contact with people Do NOT use booster fans in the duct Use the function to adjust the fan rate setting automatically see 16 1 Field setting 419 Refrigerant piping installatio...

Page 5: ...operate the unit with wet hands Do NOT place any objects containing water on the unit CAUTION Do NOT place any objects or equipment on top of the unit Do NOT sit climb or stand on the unit Units are...

Page 6: ...or your health to expose your body to the air flow for a long time CAUTION To avoid oxygen deficiency ventilate the room sufficiently if equipment with burner is used together with the system CAUTION...

Page 7: ...or a cooker this may result in fire or the formation of a harmful gas Turn off any combustible heating devices ventilate the room and contact the dealer where you purchased the unit Do NOT use the un...

Page 8: ...discoloured or the coating peeled off If it is heavily dirty soak a cloth in water diluted neutral detergent squeeze it well and wipe the panel clean Wipe it with another dry cloth NOTICE NEVER press...

Page 9: ...ver replace a fuse with a fuse of a wrong ampere ratings or other wires when a fuse blows out Use of wire or copper wire may cause the unit to break down or cause a fire CAUTION After a long use check...

Page 10: ...r to ensure smoother operation As soon as the power is turned on the user interface display appears Insert batteries in the user interface if applicable 7 5 About the refrigerant This product contains...

Page 11: ...INFORMATION The minimum airflow during normal operation or during the refrigerant leakage detection is always 240 m3 h 8 Troubleshooting If one of the following malfunctions occur take the measures sh...

Page 12: ...tion in an environment with a lot of organic solvents such as ink and siloxane WARNING The appliance shall be stored in a room without continuously operating ignition sources example open flames an op...

Page 13: ...door unit 12 2 Mounting the indoor unit 12 2 1 Guidelines when installing the indoor unit INFORMATION Optional equipment When installing optional equipment also read the installation manual of the opt...

Page 14: ...wooden structure separate the duct and wall electrically Install the outlet grille in a position where the airflow will not come into direct contact with people Do NOT use booster fans in the duct Use...

Page 15: ...and T joints with the correct gauge for the operating capacity of the units 100 600 mm a a T joint To connect the drain piping to the indoor unit NOTICE Incorrect connection of the drain hose might ca...

Page 16: ...of the user interface 2 Gradually pour approximately 1 l of water through the water inlet and check for leaks see When installation of the system is not yet completed 416 13 Piping installation 13 1 P...

Page 17: ...rom the base of the unit to the top of the flare nut NOTICE Make sure to insulate all refrigerant piping Any exposed piping might cause condensation 14 Electrical installation DANGER RISK OF ELECTROCU...

Page 18: ...1 T2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 N L a d c b L N N L N L N L a Outdoor unit b Indoor unit c User interface d Most downstream indoor unit NOTICE Group control connection is NO...

Page 19: ...x 3 0 02 3 0 x 3 5 03 Setting Static pressure Change the value number in accordance with the external static pressure of the duct to be connected as in the table below See technical documentation for...

Page 20: ...subset of the latest technical data is available on the regional Daikin website publicly accessible The full set of latest technical data is available on the Daikin Business Portal authentication req...

Page 21: ...ker Q DI KLM Earth leak circuit breaker Q L Overload protector Q M Thermo switch Q R Residual current device R Resistor R T Thermistor RC Receiver S C Limit switch S L Float switch S NG Refrigerant le...

Page 22: ......

Page 23: ......

Page 24: ...3P599562 1 2020 05 Copyright 2020 Daikin Verantwortung f r Energie und Umwelt...

Reviews: