background image

13 Piping installation

Installation and operation manual

16

FXDA10~63A2VEB

VRV system air conditioner

3P599562-1 – 2020.05

a

b

a

Drain plug

b

Philips screwdriver

To check for water leaks

The  procedure  differs  depending  on  whether  installation  of  the
system is already completed. When installation of the system is not
yet  completed,  temporarily  connect  the  user  interface  and  power
supply to the unit.

When installation of the system is not yet completed

1

Temporarily connect electrical wiring.

▪ Remove the service cover.
▪ Connect the power supply (a).
▪ Connect the user interface (b).
▪ Reattach the service cover.

L

N

a

b

a

Power supply terminal block

b

User interface terminal block

2

Turn ON the power supply.

3

Start fan only operation (see the reference guide or the service
manual of the user interface).

4

Remove the water inlet cover (1 screw).

5

Gradually  pour  approximately  1  l  of  water  through  the  water
inlet, and check for leaks.

b

d

f

e

a

c

a

Water inlet

b

Portable pump

c

Water inlet cover

d

Bucket (adding water through water inlet)

e

Drain outlet for maintenance

f

Refrigerant pipes

6

Turn OFF the power.

7

Disconnect the electrical wiring.

▪ Remove the service cover.
▪ Disconnect the power supply.
▪ Disconnect the user interface.
▪ Reattach the service cover.

When installation of the system is already completed

1

Start  cooling  operation  (see  the  reference  guide  or  the  service
manual of the user interface).

2

Gradually  pour  approximately  1  l  of  water  through  the  water
inlet, and check for leaks (see 

"When installation of the system

is not yet completed" 

[

4

 16]).

13

Piping installation

13.1

Preparing refrigerant piping

13.1.1

Refrigerant piping requirements

CAUTION

Piping MUST be installed according to instructions given in

"13  Piping  installation" 

[

4

  16].  Only  mechanical  joints  (e.g.

braze+flare connections) that are compliant with the latest
version of ISO14903 can be used.

NOTICE

The  piping  and  other  pressure-containing  parts  shall  be
suitable  for  refrigerant.  Use  phosphoric  acid  deoxidised
seamless copper for refrigerant.

▪ Foreign materials inside pipes (including oils for fabrication) must

be ≤30 mg/10 m.

Refrigerant piping diameter

For  piping  connections  of  the  indoor  unit  use  the  following  piping
diameters:

Class

Pipe outer diameter (mm)

Liquid piping

Gas piping

10~32

Ø6.4 mm

Ø9.5 mm

40~63

Ø6.4 mm

Ø12.7 mm

Refrigerant piping material

Piping material:

 Phosphoric acid deoxidised seamless copper.

Flare connections:

 Only use annealed material.

Piping temper grade and thickness:

Outer diameter

(Ø)

Temper grade

Thickness (t)

(a)

6.4 mm (1/4")

Annealed (O)

≥0.8 mm

t

Ø

9.5 mm (3/8")

12.7 mm (1/2")

(a)

Depending on the applicable legislation and the maximum
working pressure of the unit (see "PS High" on the unit name
plate), larger piping thickness might be required.

13.1.2

Refrigerant piping insulation

▪ Use polyethylene foam as insulation material:

▪ with a heat transfer rate between 0.041 and 0.052 W/mK (0.035

and 0.045 kcal/mh°C)

▪ with a heat resistance of at least 120°C

▪ Insulation thickness

Summary of Contents for FXDA10A2VEB

Page 1: ...and operation manual VRV system air conditioner English Installation and operation manual VRV system air conditioner FXDA10A2VEB FXDA15A2VEB FXDA20A2VEB FXDA25A2VEB FXDA32A2VEB FXDA40A2VEB FXDA50A2VEB...

Page 2: ...v e cu condi ia ca acestea s fie utilizate n conformitate cu instruc iunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili on vas...

Page 3: ...ndoor unit 17 15 Commissioning 18 15 1 Checklist before commissioning 18 15 2 To perform a test run 19 16 Configuration 19 16 1 Field setting 19 17 Technical data 20 17 1 Wiring diagram 20 17 1 1 Unif...

Page 4: ...ill not come into direct contact with people Do NOT use booster fans in the duct Use the function to adjust the fan rate setting automatically see 16 1 Field setting 419 Refrigerant piping installatio...

Page 5: ...operate the unit with wet hands Do NOT place any objects containing water on the unit CAUTION Do NOT place any objects or equipment on top of the unit Do NOT sit climb or stand on the unit Units are...

Page 6: ...or your health to expose your body to the air flow for a long time CAUTION To avoid oxygen deficiency ventilate the room sufficiently if equipment with burner is used together with the system CAUTION...

Page 7: ...or a cooker this may result in fire or the formation of a harmful gas Turn off any combustible heating devices ventilate the room and contact the dealer where you purchased the unit Do NOT use the un...

Page 8: ...discoloured or the coating peeled off If it is heavily dirty soak a cloth in water diluted neutral detergent squeeze it well and wipe the panel clean Wipe it with another dry cloth NOTICE NEVER press...

Page 9: ...ver replace a fuse with a fuse of a wrong ampere ratings or other wires when a fuse blows out Use of wire or copper wire may cause the unit to break down or cause a fire CAUTION After a long use check...

Page 10: ...r to ensure smoother operation As soon as the power is turned on the user interface display appears Insert batteries in the user interface if applicable 7 5 About the refrigerant This product contains...

Page 11: ...INFORMATION The minimum airflow during normal operation or during the refrigerant leakage detection is always 240 m3 h 8 Troubleshooting If one of the following malfunctions occur take the measures sh...

Page 12: ...tion in an environment with a lot of organic solvents such as ink and siloxane WARNING The appliance shall be stored in a room without continuously operating ignition sources example open flames an op...

Page 13: ...door unit 12 2 Mounting the indoor unit 12 2 1 Guidelines when installing the indoor unit INFORMATION Optional equipment When installing optional equipment also read the installation manual of the opt...

Page 14: ...wooden structure separate the duct and wall electrically Install the outlet grille in a position where the airflow will not come into direct contact with people Do NOT use booster fans in the duct Use...

Page 15: ...and T joints with the correct gauge for the operating capacity of the units 100 600 mm a a T joint To connect the drain piping to the indoor unit NOTICE Incorrect connection of the drain hose might ca...

Page 16: ...of the user interface 2 Gradually pour approximately 1 l of water through the water inlet and check for leaks see When installation of the system is not yet completed 416 13 Piping installation 13 1 P...

Page 17: ...rom the base of the unit to the top of the flare nut NOTICE Make sure to insulate all refrigerant piping Any exposed piping might cause condensation 14 Electrical installation DANGER RISK OF ELECTROCU...

Page 18: ...1 T2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 N L a d c b L N N L N L N L a Outdoor unit b Indoor unit c User interface d Most downstream indoor unit NOTICE Group control connection is NO...

Page 19: ...x 3 0 02 3 0 x 3 5 03 Setting Static pressure Change the value number in accordance with the external static pressure of the duct to be connected as in the table below See technical documentation for...

Page 20: ...subset of the latest technical data is available on the regional Daikin website publicly accessible The full set of latest technical data is available on the Daikin Business Portal authentication req...

Page 21: ...ker Q DI KLM Earth leak circuit breaker Q L Overload protector Q M Thermo switch Q R Residual current device R Resistor R T Thermistor RC Receiver S C Limit switch S L Float switch S NG Refrigerant le...

Page 22: ......

Page 23: ......

Page 24: ...3P599562 1 2020 05 Copyright 2020 Daikin Verantwortung f r Energie und Umwelt...

Reviews: