background image

2 Specific installer safety instructions

Installation and operation manual

4

FXDA10~63A2VEB

VRV system air conditioner

3P599562-1 – 2020.05

2

Specific installer safety
instructions

Always observe the following safety instructions and regulations.

General

WARNING

Make  sure  installation,  servicing,  maintenance,  repair  and
applied materials follow the instructions from Daikin and, in
addition,  comply  with  applicable  legislation  and  are
performed  by  qualified  persons  only.  In  Europe  and  areas
where  IEC  standards  apply,  EN/IEC  60335-2-40  is  the
applicable standard.

Installation site (see 

"12.1 Preparing the installation

site" 

[

4

 12])

WARNING

The  appliance  shall  be  stored  in  a  room  without
continuously  operating  ignition  sources  (example:  open
flames, an operating gas appliance or an operating electric
heater).

CAUTION

Appliance not accessible to the general public, install it in a
secured area, protected from easy access.

This  unit,  both  indoor  and  outdoor,  is  suitable  for
installation 

in 

commercial 

and 

light 

industrial

environment.

CAUTION

The  total  refrigerant  charge  in  the  system  cannot  exceed
the  requirements  for  minimum  floor  area  of  the  smallest
room that is served. For minimum floor area requirements
for  indoor  units,  see  the  installation  and  operation  manual
of the outdoor unit.

Duct installation (see 

"12.2.2 Guidelines when installing the

ducting" 

[

4

 14])

WARNING

Do  NOT  install  operating  ignition  sources  (example:  open
flames, an operating gas appliance or an operating electric
heater) in the duct work.

CAUTION

▪ Make sure the installation of the duct does NOT exceed

the setting range of the external static pressure for the
unit. Refer to the technical datasheet of your model for
the setting range.

▪ Make  sure  to  install  the  canvas  duct  so  vibrations  are

NOT  transmitted  to  the  duct  or  ceiling.  Use  a  sound-
absorbing material (insulation material) for the lining of
the  duct  and  apply  vibration  insulation  rubber  to  the
hanging bolts.

▪ When  welding,  make  sure  NOT  to  spatter  onto  the

drain pan or the air filter.

▪ If the metal duct passes through a metal lath, wire lath

or  metal  plate  of  the  wooden  structure,  separate  the
duct and wall electrically.

▪ Install the outlet grille in a position where the airflow will

not come into direct contact with people.

▪ Do NOT use booster fans in the duct. Use the function

to  adjust  the  fan  rate  setting  automatically  (see

"16.1 Field setting" 

[

4

 19]).

Refrigerant piping installation (see 

"13 Piping

installation" 

[

4

 16])

CAUTION

▪ Do NOT use mineral oil on flared part.

▪ Do NOT reuse piping from previous installations.

▪ NEVER  install  a  drier  to  this  R32  unit  to  guarantee  its

lifetime. The drying material may dissolve and damage
the system.

CAUTION

▪ Incomplete flaring may cause refrigerant gas leakage.

▪ Do  NOT  re-use  flares.  Use  new  flares  to  prevent

refrigerant gas leakage.

▪ Use  flare  nuts  that  are  included  with  the  unit.  Using

different flare nuts may cause refrigerant gas leakage.

CAUTION

Install  the  refrigerant  piping  or  components  in  a  position
where  they  are  unlikely  to  be  exposed  to  any  substance
which  may  corrode  components  containing  refrigerant,
unless  the  components  are  constructed  of  materials  that
are  inherently  resistant  to  corrosion  or  are  suitably
protected against corrosion.

WARNING: MILDLY FLAMMABLE MATERIAL

The refrigerant inside this unit is mildly flammable.

Electrical installation (see 

"14 Electrical installation" 

[

4

 17])

WARNING

▪ All  wiring  MUST  be  performed  by  an  authorised

electrician  and  MUST  comply  with  the  applicable
legislation.

▪ Make electrical connections to the fixed wiring.

▪ All  components  procured  on-site  and  all  electrical

construction  MUST  comply  with  the  applicable
legislation.

WARNING

▪ If  the  power  supply  has  a  missing  or  wrong  N-phase,

equipment might break down.

▪ Establish  proper  earthing.  Do  NOT  earth  the  unit  to  a

utility  pipe,  surge  absorber,  or  telephone  earth.
Incomplete earthing may cause electrical shock.

▪ Install the required fuses or circuit breakers.

▪ Secure  the  electrical  wiring  with  cable  ties  so  that  the

cables  do  NOT  come  in  contact  with  sharp  edges  or
piping, particularly on the high-pressure side.

▪ Do  NOT  use  taped  wires,  stranded  conductor  wires,

extension  cords,  or  connections  from  a  star  system.
They can cause overheating, electrical shock or fire.

▪ Do  NOT  install  a  phase  advancing  capacitor,  because

this  unit  is  equipped  with  an  inverter.  A  phase
advancing  capacitor  will  reduce  performance  and  may
cause accidents.

WARNING

ALWAYS use multicore cable for power supply cables.

WARNING

Use  an  all-pole  disconnection  type  breaker  with  at  least
3  mm  between  the  contact  point  gaps  that  provide  full
disconnection under overvoltage category III.

Summary of Contents for FXDA10A2VEB

Page 1: ...and operation manual VRV system air conditioner English Installation and operation manual VRV system air conditioner FXDA10A2VEB FXDA15A2VEB FXDA20A2VEB FXDA25A2VEB FXDA32A2VEB FXDA40A2VEB FXDA50A2VEB...

Page 2: ...v e cu condi ia ca acestea s fie utilizate n conformitate cu instruc iunile noastre skladni z naslednjimi standardi in drugimi normativi pod pogojem da se uporabljajo v skladu z na imi navodili on vas...

Page 3: ...ndoor unit 17 15 Commissioning 18 15 1 Checklist before commissioning 18 15 2 To perform a test run 19 16 Configuration 19 16 1 Field setting 19 17 Technical data 20 17 1 Wiring diagram 20 17 1 1 Unif...

Page 4: ...ill not come into direct contact with people Do NOT use booster fans in the duct Use the function to adjust the fan rate setting automatically see 16 1 Field setting 419 Refrigerant piping installatio...

Page 5: ...operate the unit with wet hands Do NOT place any objects containing water on the unit CAUTION Do NOT place any objects or equipment on top of the unit Do NOT sit climb or stand on the unit Units are...

Page 6: ...or your health to expose your body to the air flow for a long time CAUTION To avoid oxygen deficiency ventilate the room sufficiently if equipment with burner is used together with the system CAUTION...

Page 7: ...or a cooker this may result in fire or the formation of a harmful gas Turn off any combustible heating devices ventilate the room and contact the dealer where you purchased the unit Do NOT use the un...

Page 8: ...discoloured or the coating peeled off If it is heavily dirty soak a cloth in water diluted neutral detergent squeeze it well and wipe the panel clean Wipe it with another dry cloth NOTICE NEVER press...

Page 9: ...ver replace a fuse with a fuse of a wrong ampere ratings or other wires when a fuse blows out Use of wire or copper wire may cause the unit to break down or cause a fire CAUTION After a long use check...

Page 10: ...r to ensure smoother operation As soon as the power is turned on the user interface display appears Insert batteries in the user interface if applicable 7 5 About the refrigerant This product contains...

Page 11: ...INFORMATION The minimum airflow during normal operation or during the refrigerant leakage detection is always 240 m3 h 8 Troubleshooting If one of the following malfunctions occur take the measures sh...

Page 12: ...tion in an environment with a lot of organic solvents such as ink and siloxane WARNING The appliance shall be stored in a room without continuously operating ignition sources example open flames an op...

Page 13: ...door unit 12 2 Mounting the indoor unit 12 2 1 Guidelines when installing the indoor unit INFORMATION Optional equipment When installing optional equipment also read the installation manual of the opt...

Page 14: ...wooden structure separate the duct and wall electrically Install the outlet grille in a position where the airflow will not come into direct contact with people Do NOT use booster fans in the duct Use...

Page 15: ...and T joints with the correct gauge for the operating capacity of the units 100 600 mm a a T joint To connect the drain piping to the indoor unit NOTICE Incorrect connection of the drain hose might ca...

Page 16: ...of the user interface 2 Gradually pour approximately 1 l of water through the water inlet and check for leaks see When installation of the system is not yet completed 416 13 Piping installation 13 1 P...

Page 17: ...rom the base of the unit to the top of the flare nut NOTICE Make sure to insulate all refrigerant piping Any exposed piping might cause condensation 14 Electrical installation DANGER RISK OF ELECTROCU...

Page 18: ...1 T2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 P1 P2 F1 F2 T1 T2 N L a d c b L N N L N L N L a Outdoor unit b Indoor unit c User interface d Most downstream indoor unit NOTICE Group control connection is NO...

Page 19: ...x 3 0 02 3 0 x 3 5 03 Setting Static pressure Change the value number in accordance with the external static pressure of the duct to be connected as in the table below See technical documentation for...

Page 20: ...subset of the latest technical data is available on the regional Daikin website publicly accessible The full set of latest technical data is available on the Daikin Business Portal authentication req...

Page 21: ...ker Q DI KLM Earth leak circuit breaker Q L Overload protector Q M Thermo switch Q R Residual current device R Resistor R T Thermistor RC Receiver S C Limit switch S L Float switch S NG Refrigerant le...

Page 22: ......

Page 23: ......

Page 24: ...3P599562 1 2020 05 Copyright 2020 Daikin Verantwortung f r Energie und Umwelt...

Reviews: