(3) If using the left, bottom-left, right, or bottom-right positions for the piping, cut out the through-hole
for the piping in the front grille. (Refer to Fig. 4)
(4) Remove the front panel and the service cover. (Refer to Fig. 5)
< How to remove the front panel and service cover >
(1) Open the front panel to the point where it stops.
(2) Push the hooks on either side of the front panel towards the sides of the main unit and remove. (You can
also remove it by sliding the front panel either to the left or right and pulling it forward.)
(3) Remove the screw from the service cover and pull the handle forward.
(5) Point the pipe in the direction it will be passed out.
For right, bottom-right, and back-right piping (Refer to Fig. 6)
•
Wrap the drain hose and the refrigerant piping together with the
insulating tape (4) so that the drain hose is below the refrigerant
piping.
For left, bottom-left, and left-back piping
•
Remove the front grille.
(Refer to Fig. 7)
< How to remove the front grille >
Remove the front grille as described below when securing the
indoor unit with screws or when attaching Optional Accessories
(wireless remote controller, adapter PC board, etc.).
(1) Remove the front panel.
(2) Remove the screws (2 places in case of FXAQ15,20,25,32 class/3 places in case of FXAQ40,50,63
class) securing the front grille.
(3) Remove the tabs (3 places) securing the front grille by pushing them in the direction of the arrows.
Installation plate (1)
Temporary screw
(In case of 15-32 type 1pc)
(In case of 40-63 type 2pcs)
Right pipe
Left pipe
Back-left pipe
Back-right pipe
Bottom-left pipe
Bottom-right pipe
Front grille
Cut out along
the groove.
Cut away
Fig. 3
Fig. 4
Hook
Fig. 5
Handle
Screw
Service cover
Front panel
(1)
(2)
(2)
(3)
Hook
Hook
Insulating tape (4)
Drain hose
Fig. 6
Refrigerant piping
4PEN494115-1A.book Page 7 Tuesday, October 3, 2017 10:51 AM