background image

2

English

Install the air conditioner on a foundation strong enough to withstand the weight of the unit. 
If a foundation does not have sufficient strength, the equipment may fall and cause injury.

The electrical work must be carried out by the qualified electrician in accordance with the local laws and 
regulations and this installation manual. Make sure to provide a dedicated power supply circuit and never 
connect additional wiring to the existing circuit.
An insufficient power supply capacity or improper electrical work may lead to electric shocks or fire.

Be sure to earth the air conditioner. 
Do not earth the unit to a utility pipe, lightning conductor or telephone earth lead. 
Imperfect earthing may result in electric shocks or fire. 
A high surge current from lightning or other sources may cause damage to the air conditioner.

Be sure to install an earth leakage breaker. 
Failure to install an earth leakage breaker may result in electric shocks or fire.

Be sure to switch off the unit before touching any electrical parts. 
Touching a live part may result in electric shock.

For wiring, use the specified wires and connect and fasten them firmly so that no external force from the 
wires may be applied to the terminal connections.
If the wires are not firmly connected and fastened, it may cause heating, fire or the like.

Wiring for power supply and between the indoor and outdoor units must be properly laid and formed, and 
the control box cover must be firmly fastened so that the wiring may not push up the structural parts such 
as the cover.
If the cover is improperly fastened, it may cause electric shock or fire.

If refrigerant gas leaks during installation, ventilate the area immediately. 
Toxic gas may be produced if the refrigerant comes into contact with fire.

After completing installation, check for refrigerant gas leakage. 
Toxic gas may be produced if the refrigerant gas leaks into the room and comes into contact with a source 
of fire, such as a fan heater, stove or cooker.

Do not directly touch refrigerant that has leaked from refrigerant pipes or other areas, as there is a danger 
of frostbite.

If the supply cord is damaged, it must be replaced by the manufacturer, a service agent or similarly qualified 
persons in order to avoid a hazard.

CAUTION

Carry out drain piping properly following this installation manual and insulate the pipe to prevent conden-
sation.
Improper drain piping may result in indoor water leakage and property damage.

Install the indoor and outdoor units, power cord and connecting wires at least 1 meter away from televisions 
or radios to prevent picture interference and noise. 
(Depending on the incoming signal strength, a distance of 1 meter may not be sufficient to eliminate noise.)

Install the indoor unit as far as possible from fluorescent lamps.
If a wireless kit is installed in a room where the electronic lighting type (inverter or rapid start types) fluo-
rescent lamps exist, the transmitting distance of a remote controller may be shorter.

Do not install the air conditioner in the following locations:
1. Where there is a high concentration of mineral oil spray or vapour (e.g. a kitchen). 

Plastic parts may deteriorate and cause parts to fall off or water to leak.

2. Where corrosive gas, such as sulphurous acid gas, is produced. 

Corrosion of copper pipes or brazed parts may occur and cause refrigerant leakage.

3. Where there is a machine that generates electromagnetic wave and where voltage fluctuation often occurs such 

as a factory.
Control system may malfunction and as a result the unit may not properly operate.

4. Where flammable gas may leak, where carbon fibre or ignitable dust is suspending in the air, or where 

volatile flammables such as paint thinner or gasoline are handled.
Operating the unit in such conditions may result in fire.

The air conditioner is not intended for use in a potentially explosive atmosphere.

Sound pressure level is less than 70 dB(A).

4PEN494115-1A.book  Page 2  Tuesday, October 3, 2017  10:51 AM

Summary of Contents for FXAQ15AUV1B

Page 1: ...INSTALLATION MANUAL FXAQ15AUV1B FXAQ20AUV1B FXAQ25AUV1B FXAQ32AUV1B FXAQ40AUV1B FXAQ50AUV1B FXAQ63AUV1B System air conditioners...

Page 2: ...elecido em A e com o parecer positivo de B de acordo com o Certificado C 09 A B C 10 Bem rk som anf rt i A og positivt vurderet af B i henhold til Certifikat C 11 Information enligt A och godk nts av...

Page 3: ...may be serious depending on the circumstances After completing installation conduct a test run to confirm that the equipment operates without any problems Then explain to the customer how to operate...

Page 4: ...roduced if the refrigerant gas leaks into the room and comes into contact with a source of fire such as a fan heater stove or cooker Do not directly touch refrigerant that has leaked from refrigerant...

Page 5: ...man Improper installation could lead to leaks and in worse cases electric shock of fire Use only parts provided with the unit or parts satisfying required specifications Unspecified parts could cause...

Page 6: ...k Are the indoor and outdoor unit fixed firmly The units may drop vibrate or make noise Is the outdoor unit fully installed The unit may malfunction or the compo nents burn out Is the gas leak test fi...

Page 7: ...the wall is not significantly tilted Where not exposed to combustible gases Where pipe between indoor and outdoor units is possible within the allowable limit Refer to the installation manual of the...

Page 8: ...he unit 4 INDOOR UNIT INSTALLATION Use only accessories and parts which are of the designated specification when installing CAUTION Install so that the unit does not tilt to either side or forward Do...

Page 9: ...the insulating tape 4 so that the drain hose is below the refrigerant piping For left bottom left and left back piping Remove the front grille Refer to Fig 7 How to remove the front grille Remove the...

Page 10: ...raved on the installation plate 1 Replacing the drain hose and drain plug 1 Remove the drain plug and insulation tubing 2 Remove the drain hose and replace onto the left side 3 Replace the drain plug...

Page 11: ...ce from the power supply earth wirings that is on the other side of the power supply earth wirings Then fix them securely on the refrigerant pipe Seal the piping through hole with putty corking materi...

Page 12: ...orce the refrigerant insulation 20 mm or thicker Condensation may form on the surface of the insulating material Before refrigerant piping work check which type of refrigerant is used Proper operation...

Page 13: ...e the phosphor copper brazing filler metal BCuP 2 JIS Z 3264 B Cu93P 710 795 ISO 3677 which does not require flux Flux has extremely harmful influence on refrigerant piping systems For instance if the...

Page 14: ...touched 6 DRAIN PIPING WORK 1 Install the drain piping Refer to Fig 16 The drain pipe should be short with a downward slope and should prevent air pockets from forming Watch out for the points in the...

Page 15: ...ind that it will become the cause of getting drain pipe blocked if water collects on drain pipe 7 ELECTRIC WIRING WORK 7 1 GENERAL INSTRUCTIONS All field supplied parts and materials and electric work...

Page 16: ...emote controller wiring are as follows 1 Outdoor unit Indoor unit Max 1000m Max wiring length 2000m 2 Indoor unit Remote controller Max 500m NOTE 1 Shows only in case of protected pipes Use H07RN F in...

Page 17: ...n of water as well as any insects and other small creatures from the outside Otherwise a short circuit may occur inside the control box PRECAUTIONS Observe the notes mentioned below when wiring to the...

Page 18: ...re CAUTION Be sure to attach the sealing material and putty field supplied to hole of wiring to prevent the infiltration of water as well as any insects and other small creatures from outside Otherwis...

Page 19: ...rnal stress on terminals Keep wiring in neat order and so as not to obstruct other equipment such as popping open the service cover Make sure the cover closes tight Incomplete connections could result...

Page 20: ...UB MAIN SUB CHANGEOVER Refer to the manual attached to the remote controller Wiring Method 1 Remove the control box cover IN D OUT D F1 F2 F1 F2 Control box LN P1 P2 P1 P2 F1 F2 T1 T2 LN P1 P2 F1 F2 T...

Page 21: ...llers for centralized control Wire specification Sheathed vinyl cord or cable 2 wire Gauge 0 75 1 25 mm2 Length Max 100 m External terminal Contact that can ensure the minimum applicable load of 15V D...

Page 22: ...trol box cover Refer to 5 INDOOR UNIT INSTALLATION 2 Lay crossover between the terminals P1 P2 inside the control box for the remote controller There is no polarity Refer to Fig 29 NOTE Terminal numbe...

Page 23: ...OW from the field Change the SECOND CODE NO as shown in Table 3 to suit your needs SECOND CODE NO is factory set to 01 for Standard Table 3 When using wireless remote controllers When using wireless r...

Page 24: ...work is completed if the interior work has not been finished at the end of the test run If the air conditioner is operated substances discharged from the paint adhesive etc can contaminate the indoor...

Page 25: ...DS DIP SWITCH R T THERMISTOR E H HEATER RC RECEIVER F U FU FOR CHARACTERISTICS REFER TOPCBINSIDE YOUR UNIT FUSE S C LIMIT SWITCH FG CONNECTOR FRAMEGROUND S L FLOAT SWITCH H HARNESS S NPH PRESSURESENS...

Page 26: ......

Page 27: ......

Page 28: ...4P494115 1A 2017 08 Copyright 2017 Daikin...

Reviews: