background image

10

When screwing in the indoor unit

Remove the front grill. 

(Refer to Fig. 7)

Secure the indoor unit to the installation panel (1) with the securing 
screws (6). 

(Refer to Fig. 11)

5. REFRIGERANT PIPING WORK

For refrigerant piping of outdoor units, see the installation manual attached to the outdoor unit.

〉 

Execute heat insulation work completely on both sides of the gas piping and the liquid piping. 

Otherwise, a water leakage can result sometimes.

〉 

(

When using a heat pump, the temperature of the gas piping can reach up to approximately 250°F, so use 

insulation which is sufficiently resistant.)

Also, in cases where the temperature and humidity of the refrigerant piping sections might exceed 

86°F or RH80 %, reinforce the refrigerant insulation. (13/16” or thicker) Condensation may form on the 
surface of the insulating material.

Before refrigerant piping work, check which type of refrigerant is used. Proper operation is not pos-

sible if the types of refrigerant are not the same.

NOTE

• Use a pipe cutter and flare suitable for the type of refrigerant.

• To prevent dust, moisture or other foreign matter from infiltrating the tube, either pinch the end 

or cover it with tape.

• Do not allow anything other than the designated refrigerant to get mixed into the refrigerant 

circuit, such as air, etc. 

• If any refrigerant gas leaks while working on the unit, ventilate the room thoroughly right away.

The outdoor unit is charged with refrigerant.

Use copper alloy seamless pipes.

Be sure to use both a spanner and torque wrench together, as shown 
in the drawing, when connecting or disconnecting pipes to/from the 
unit.

 (Refer to Fig. 12)

Refer to “Table 1” for the dimensions of flare.

When connecting the flare  nut, coat the flare section (both inside and 
outside) with ester oil or ether oil, rotate three or four times first, then 
screw in.

 (Refer to Fig. 13)

CAUTION

Over-tightening may cause the flare nuts to crack or the refrigerant
to leak. 

Use the flare nut included with the unit.

Summary of Contents for FXAQ12MVJU

Page 1: ...U FXAQ18MVJU FXAQ24MVJU SYSTEM Inverter Air Conditioners Read these instructions carefully before installation Keep this manual in a handy place for future reference This manual should be left with th...

Page 2: ...TALLATION 3 3 SELECTING INSTALLATION SITE 5 4 INDOOR UNIT INSTALLATION 6 5 REFRIGERANT PIPING WORK 10 6 DRAIN PIPING WORK 12 7 ELECTRIC WIRING WORK 13 8 WIRING EXAMPLE AND HOW TO SET THE REMOTE CONTRO...

Page 3: ...CAUTION Indication a potentially hazardous situation which if not avoided may result in minor or moderate injury It may also be sued to alert against unsafe practices NOTE Indication situation that m...

Page 4: ...gers Touching a switch with wet fingers can cause electric shock Install a leak circuit breaker as required If a leak circuit breaker is not installed electric shock may result Do not install the air...

Page 5: ...n site Where unpacking is unavoidable use a sling of soft material or protective plates together with a rope when lifting to avoid dam age or scratches to the unit For the installation of an outdoor u...

Page 6: ...one what is likely to occur Check Are the indoor and outdoor unit fixed firmly The units may drop vibrate or make noise Is the gas leak test finished It may result in insufficient cooling Is the unit...

Page 7: ...g blocks the air passage Where condensate can be properly drained Where the wall is not significantly tilted Where not exposed to flammable gases Where piping between indoor and outdoor units is possi...

Page 8: ...t This may damage the horizontal flaps 1 Open the piping through hole The refrigerant pipe and drain pipe can be passed out in one of 5 directions left bottom left back left bottom right and back righ...

Page 9: ...oncrete use commercially available foundation bolts M8 M10 or equivalent 3 If using the left bottom left or bottom right positions for the piping cut out the through hole for the piping in the front g...

Page 10: ...he screws 2 places in case of 12 type 3 places in case of 18 24 type securing the front grill 3 Remove the tabs 3 places securing the front grill by pushing them in the direction of the arrows 4 Makin...

Page 11: ...ONNECT WIRINGS and remote controller wiring through the wiring guide in through the back of the indoor unit and to the front 8 Connect the piping See 5 REFRIGERANT PIPING WORK and Fig 10 Seal the pipi...

Page 12: ...ant is used Proper operation is not pos sible if the types of refrigerant are not the same NOTE Use a pipe cutter and flare suitable for the type of refrigerant To prevent dust moisture or other forei...

Page 13: ...gerant piping only begin brazing after having carried out nitrogen substitution NOTE 1 or while inserting nitrogen into the refrigerant piping NOTE 2 Once this is done connect the indoor unit with a f...

Page 14: ...t for the points in the figure 16 when performing drain work When extending the drain hose use a commercially available drain extension hose and be sure to insulate the extended section of the drain h...

Page 15: ...units Mark each indoor unit as unit A unit B and be sure the terminal block wiring to the outdoor unit and BS unit is properly matched If wiring and piping between the outdoor unit and indoor unit ar...

Page 16: ...clamp small 5 Refer to Fig 21 Connect the power supply wiring and ground wiring to the power supply terminal block 3P When doing this firmly secure using the included clamp small 5 according to the fi...

Page 17: ...o wirings get caught in the edges Pass wiring through the wiring through holes to prevent damage to them Make sure the remote controller wiring and transmission wire the wiring between the units and o...

Page 18: ...l not be properly tightened If the terminal screws are tightened too hard screws might be damaged Refer to the table below for the tightening torque of the terminal screws 3 Do not connect wires of di...

Page 19: ...wer supply wiring of each unit with a switch and fuse as shown in the drawing COMPLETE SYSTEM EXAMPLE 3 systems 1 When using 1 remote controller for 1 indoor unit Normal operation 2 For group control...

Page 20: ...MAIN SUB CHANGEOVER 1 Insert a screwdriver into the recess between the upper and lower part of remote controller and working from the 2 positions pry off the upper part The remote controller PC board...

Page 21: ...ails refer to the manual of each optional controllers for centralized control 9 FIELD SETTINGS 1 Make sure the service lids are closed on the indoor and outdoor units 2 Field settings must be made fro...

Page 22: ...l display to identify the point of trouble An explanation of malfunction codes and the corresponding trouble is provided in the installation manual of the outdoor unit If any of the items in Table 5 a...

Page 23: ...0407 HT 3PN01417 9V EM04A013 Daikin US Corporation 375 Park Avenue Suite 3308 New York NY 10152 www daikinac com info daikinac com...

Reviews: