![background image](http://html1.mh-extra.com/html/daikin/fxaq12mvju/fxaq12mvju_operation-manual_2459651017.webp)
15
CAUTION
Be sure to attach the sealing material and putty (field supplied) to hole of wiring to prevent the infiltration
of water as well as any insects and other small creatures from outside. Otherwise a short-circuit may
occur inside the electric parts box.
When clamping the wirings, be sure no tension is applied to the wire connections by using the included
clamp. Also, when wiring, make sure the lid on the electric parts box fits snugly by arranging the wirings
neatly and attaching the service lid firmly. When attaching the service lid, make sure no wirings get caught
in the edges. Pass wiring through the wiring through holes to prevent damage to them.
Make sure the remote controller wiring, and transmission wire the wiring between the units, and other elec-
trical wiring do not pass through the same locations outside the unit, separating them by at least 5”, other-
wise electrical noise (external static) could cause mistaken operation or breakage.
Use only specified wire and tightly connect wires to terminals. Be careful wires do not place external stress
on terminals. Keep wiring in neat order and so as not to obstruct other equipment such as popping open the
service cover. Make sure the cover closes tight. Incomplete connections could result in overheating, and in
worse case, electric shock or fire.